Bryant 580F installation instructions Low Speed, 802 370, 840 432

Page 28

 

 

 

 

Table 16 — Fan Performance 580F060 — Vertical Discharge Units, Standard Motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STANDARD MOTOR (DIRECT DRIVE)

 

 

 

 

 

 

 

Airflow

 

 

Low Speed

 

 

 

 

 

Medium Speed

 

 

 

 

High Speed

 

 

 

208 V

 

230,460,575 V

 

 

208 V

 

230,460,575 V

 

208 V

 

230,460,575 V

(Cfm)

 

 

 

 

 

 

 

 

 

ESP

Bhp

Watts

ESP

 

Bhp

Watts

 

ESP

Bhp

Watts

ESP

Bhp

Watts

ESP

Bhp

Watts

ESP

Bhp

Watts

1500

0.69

0.67

750

1.01

 

0.71

791

 

1.00

0.70

782

1.20

0.76

845

1.22

0.79

875

1.28

0.85

949

1600

0.49

0.70

780

0.85

 

0.74

824

 

0.85

0.74

821

1.06

0.79

883

1.09

0.82

913

1.17

0.89

988

1700

0.29

0.73

810

0.70

 

0.77

857

 

0.70

0.77

861

0.93

0.83

921

0.97

0.85

950

1.06

0.92

1027

1800

0.09

0.75

839

0.54

 

0.80

891

 

0.55

0.81

900

0.80

0.86

959

0.84

0.89

988

0.95

0.96

1066

1900

0.39

 

0.83

924

 

0.40

0.84

940

0.67

0.90

997

0.72

0.92

1025

0.84

0.99

1105

2000

0.23

 

0.86

957

 

0.25

0.88

979

0.54

0.93

1035

0.59

0.95

1063

0.73

1.03

1144

2100

0.08

 

0.89

990

 

0.10

0.91

1018

0.41

0.96

1073

0.46

0.99

1101

0.62

1.06

1183

2200

 

 

0.28

1.00

1111

0.34

1.02

1138

0.51

1.10

1222

2300

 

 

0.15

1.03

1149

0.21

1.06

1176

0.40

1.13

1261

2400

 

 

0.02

1.07

1187

0.09

1.09

1213

0.29

1.17

1300

2500

 

 

0.18

1.20

1340

 

 

LEGEND

 

 

 

 

 

 

 

 

See page 36 for general fan performance notes.

 

 

 

Bhp

Brake Horsepower Input to Fan

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ESP

External Static Pressure (in. wg)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 17 — Fan Performance 580F060 — Single-Phase, Vertical Discharge Unit,

Alternate Motor (Belt Drive)*

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

0.2

 

 

0.4

 

 

0.6

 

 

0.8

 

 

1.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

1500

802

0.42

370

912

0.55

489

1006

0.70

624

1088

0.87

773

1163

1.05

935

1600

840

0.49

432

947

0.63

557

1038

0.78

696

1119

0.95

848

1193

1.14

1013

1700

878

0.57

502

982

0.71

632

1071

0.87

776

1151

1.05

932

1224

1.24

1100

1800

917

0.65

581

1017

0.81

716

1105

0.97

864

1183

1.15

1024

1900

956

0.75

668

1053

0.91

808

1139

1.08

961

1216

1.27

1126

2000

995

0.86

764

1090

1.02

910

1173

1.20

1067

2100

1035

0.98

869

1127

1.15

1021

2200

1075

1.11

984

1164

1.29

1141

2300

1115

1.25

1110

2400

2500

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

1.2

 

 

1.4

 

 

1.6

 

 

1.8

 

 

2.0

 

(Cfm)

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

1500

1232

1.25

1109

1600

1700

1800

1900

2000

2100

2200

2300

2400

2500

LEGEND

Bhp — Brake Horsepower Input to Fan

Watts — Input Watts to Motor

*Motor drive range: 878 to 1192 rpm. All other rpms require a field- supplied drive.

NOTES:

1.Boldface indicates field-supplied drive is required.

2.Maximum continuous bhp is 1.30.

3.See page 36 for general fan performance notes.

28

Image 28
Contents Important Read Before Installing ContentsSafety Considerations InstallationBase Unit Dimensions 580F036-072 Base Unit Dimensions 580F073 III. Install External Trap for CONDEN- Sate Drain Alternate Unit SupportII. Field Fabricate Ductwork IV. RIG and Place UnitUnit Size Accessory CRRFCURB001A01 Connector ALT Accessory Drain GASPKG. Accy Hole Power CRRFCURB002A01Install Flue Hood VI. Install GAS PipingUnit 580F MAX Weight Rigging DetailsPhysical Data Furnace Section Freeze Protection Thermostat FOUTDOOR-AIR Inlet Screens RETURN-AIR FiltersField Power Supply Field Control WiringHeat Anticipator Settings VII. Make Electrical ConnectionsPower Wiring Connections Electrical Data Without Convenience Outlet RLA LRA FLA MCA MOCP†Electrical Data With Convenience Outlet VIII. Adjust FACTORY-INSTALLED Options Manual Outdoor-Air DamperHood BOX Optional EconoMi$er+Bracket Oarh IAQOAT IarhDamper Movement EconoMi$er+ Controller WiringThermostats EconoMi$er+ Field-Installed Accessories Outdoor Air Temperature OAT Sensor ProvidedSupply Air Temperature SAT Sensor Provided Return Air Temperature RAT SensorIndoor Air Quality Voltage Setting Outdoor Air Humidity SensorTemperature Resistance Range ResolutionEnthalpy Changeover Settings Occupied/Unoccupied Switch Power ExhaustRemote EconoMi$er+ Enable Control Indoor Air Humidity SensorCO2 Sensor Configuration Full OccupancyVentilation Rate Ventilation for PeopleDirect-Drive Motors IX. Adjust EVAPORATOR-FAN SpeedBelt-Drive Motors Fan Rpm at Motor Pulley Settings Motor DataExternal Static Pressure in. wg Cfm Rpm Bhp Watts 900 768870 958External Static Pressure in. wg Cfm Rpm Bhp Watts 9551181 970 1073802 370 Low Speed840 432 802 370 912 489 624773 935967 579 663757 856Airflow Low Speed High Speed Bhp Watts 900884 941762 859 458 944 579 705886 517 969 644 777790 353 828 413866 479 790 353 896 470 990 599828 413 930 535 1021 669 866 479 964 607 1053 746905 553 1000 687 1085 831 944 635 1036 775 1119 924771 867986 966IV Internal Wiring VI. Refrigerant Service PortsPRE-START-UP START-UP Unit PreparationMain Burners IX. CoolingXI. Heating XIII. Ventilation Continuous FAN XII. Safety ReliefXIV. ECONOMI$ER+ Controller DS1 DS2 DS3 DS4 Input Name Type USE INPUT/OUTPUT Conversion Connection PINThermostat Inputs Economizer MotorConfiguration Variables Read and Setup Modes Start-Up Mode SequenceInput/Output Channels Setup Mode Error Mode Manual ModeXV. ECONOMI$ER+ Configuration Compressor Configuration and Control Ventilation Air and Free CoolingDemand Ventilation Configuration Power Exhaust ConfigurationXVI. Operating Sequence Cooling, Units without EconoMi$er+Heating, Units without EconoMi$er+ Cooling, Units with EconoMi$er+Service Cleaning III. Blower Belt Adjustment ECONOMI$ER+ AdjustmentII. Lubrication IV. Manual OUTDOOR-AIR DamperLimit Switch XIII. HIGH-PRESSURE SwitchXIV. Loss of Charge Switch XVI. Replacement PartsSuction Line Temperature DEG. C Suction Line Temperature DEG. FSuction Line Pressure Kilopascals Suction Line Pressure PsigTON Unit 60 Hz Charging Chart Burner Section Details Troubleshooting ECONOMI$ER+ Troubleshooting Error Code 8 E2 Test Failure Unit Always in Unoccupied ModeII. Unit Troubleshooting RAM Test FailureLED Error Code Service Analysis Heating Service AnalysisCooling Service Analysis FPT GNDGVR HPSStartup Mode Appendix a ECONOMI$ER+ LabelAppendix a ECONOMI$ER+ Label Appendix B JOB Specific ECONOMI$ER+ Configuration Settings Index Service Training Call for Free CatalogPage START-UP Checklist TemperaturesPreliminary Information III. START-UP Electrical
Related manuals
Manual 80 pages 29.14 Kb Manual 52 pages 44.41 Kb

580F specifications

The Bryant 580F is a highly regarded gas furnace known for its exceptional heating performance and advanced technology. Designed for residential use, this model stands out for its reliability, efficiency, and user-friendly features that cater to modern heating demands.

One of the most notable features of the Bryant 580F is its efficiency rating. With an AFUE (Annual Fuel Utilization Efficiency) rating of up to 95%, this furnace maximizes heat output while minimizing energy consumption. This high level of efficiency not only results in lower utility bills but also reduces the environmental impact—a critical consideration for today’s eco-conscious homeowners.

The Bryant 580F is equipped with a multi-speed blower that ensures consistent airflow and enhances comfort by maintaining even temperatures throughout the home. This technology allows the furnace to adjust its operation based on the heating needs, leading to quieter operation and increased comfort levels.

In terms of construction, the Bryant 580F is built with durable materials that promise longevity and resilience against wear and tear. Its compact design makes installation easier, allowing it to fit into tight spaces without compromising its performance.

One of the standout technologies integrated into the Bryant 580F is its enhanced control system. The furnace works seamlessly with smart thermostats, allowing homeowners to monitor and adjust heating settings from their mobile devices. This feature not only provides convenience but also allows for energy-saving optimizations based on personal schedules and preferences.

Safety is also a primary concern with the Bryant 580F. It includes robust safety features such as a hot surface ignition system that eliminates the need for a standing pilot light, reducing the risk of gas leaks. Additionally, advanced diagnostics help in troubleshooting and maintenance, ensuring that potential issues can be identified and resolved quickly.

In conclusion, the Bryant 580F gas furnace is a remarkable choice for those seeking a blend of efficiency, comfort, and advanced technology. Its high AFUE rating, multi-speed blower, smart control compatibility, and safety features make it a reliable option for homeowners looking to invest in a dependable heating solution. As the demand for energy-efficient heating continues to grow, the Bryant 580F stands out as a model that meets and exceeds expectations in the modern heating landscape.