Bryant 580F installation instructions Manual Mode, Error Mode, XV. ECONOMI$ER+ Configuration

Page 43

6.Verify the configuration point by pushing button #1. The red LED should flash twice to indicate point 2, and then the green LEDs will flash the current setting.

NOTE: Since the occupied minimum position MUST be 1 greater than the IAQ minimum position (item 15), the IAQ minimum position must be changed first. (IAQ min has a default value of 5%, which is higher than the 2% value in this example.)

7.Use button #2 (ADVANCE/MANUAL) to get to config- uration point 15 (IAQ Minimum Position).

NOTE: Before performing Step 8, be ready to push button #1; there is a limited time window that can easily be missed when the DS3 green LED comes on, and again when the DS4 green LED comes on.

8.Verify the configuration point by pushing button #1. The red LED should flash 15 times to indicate point 15, then the green LEDs will flash the current setting.

9.Next, the green DS3 LED will turn on steady for 2 seconds. During this time, do NOT do anything so that the position defaults to 0.

10.The DS3 LED will turn off and the green DS4 LED will go on steady for 2 seconds. During this time, push button #1 once to set the point to 1%.

11.Wait until the green LEDs turn off then verify the setting by pushing button #1 to read the value. DS3 should not blink, and DS4 should blink once.

12.Now configure the Occupied Minimum Position to 2%. Use button #2 (ADVANCE/MANUAL) to get to configuration point 2.

NOTE: Before performing Step 13, be ready to push button #1; there is a limited time window that can easily be missed when the DS3 green LED comes on, and again when the DS4 green LED comes on.

13.Verify the configuration point by pushing button #1. The red LED should flash twice to indicate point 2, then the green LEDs will flash the current setting.

14.Next, the green DS3 LED will turn on steady for 2 seconds. During this time, do NOT do anything so that the position goes to 0.

15.The DS3 LED will turn off and the green DS4 LED will go on steady for 2 seconds. During this time, push button #1 twice to set the point to 2%.

16.Wait until the green LEDs turn off then verify the setting by pushing button #1 to read the value. DS3 should not blink, and DS4 should blink twice.

NOTE: Configuration items 2, 15, 11, 12, 18 and 19 (in Table 37) are dependent upon other items. Before attempt- ing to change one of these items, be sure to check the value of the item it depends upon (as described in Example 2 above).

IMPORTANT: During SETUP MODE, changes are allowed when the DS3 LED and DS4 LED are lit for 2 seconds (as described in Example 1 and 2 above). During this time, if button #1 is pushed to change one position and not the other, the value for that one position will change and the other will default to zero (unless a dependency prevents the zero). How- ever, if button #1 is not pushed at all during the 2 seconds that the green LEDs are lit, the configuration item will not change.

F. Manual Mode

Manual mode is used to control the status of I/O channels for use in troubleshooting. See Table 38.

Enter the Manual mode by holding down the ADVANCE/ MANUAL (#2) button for at least 3 seconds until all LEDs flash and then the red LED comes on steady.

NOTE: A user can only enter the Manual mode from the RUN mode, which is entered by pushing buttons #1 and #2 for at least 3 seconds.

All EconoMi$er+ control outputs are turned off. “I/O Inputs” 1-5 can be adjusted even if the unit is in operation.

In manual mode, the yellow DS2 LED flashes once to indi- cate the I/O channel. See Table 38. If the value is less than 5, the yellow DS2 LED will count out the value using 1-second flashes. If the value is greater than 4, the yellow DS2 LED will count out groups of 5 at a high flash rate and then follow with the additional value at a flash rate of once per second. For example a flash of 1 indicates Compressor Relay Output 1.

Push READ/ADJUST button (#1) to read the value. The yel- low LED will flash the I/O Channel number being viewed.

Once the channel number is displayed it will then turn on the appropriate green LED (DS3 or DS4) to indicate the sta- tus of the output. For relay outputs if the DS3 LED is on, then the output is on. If DS4 is on, then the output is off. The green DS3 and DS4 LEDs will remain on for about 2 seconds and if during this time the READ/ADJUST (#1) button is pushed, then the output will toggle to the alternate state. To change again, push the READ/ADJUST button and repeat the test or change the status of the output. As an example, for channel 5 (EconoMi$er+ control damper motor) use the READ/ADJUST button to toggle the motor from open to close in %.

At any time, the ADVANCE/MANUAL (#2) button can be used to advance to the next SET I/O. To exit the mode, push and hold the READ/ADJUST and ADVANCE/MANUAL but- tons (#1 and #2) for more than 3 seconds.

NOTE: After exiting the Manual mode, the controller will re-initialize and start with all outputs off.

G. Error Mode

The error mode is used to indicate that an error has occurred The error is indicated by LED #1 red and #2 yellow are on steady.

Enter the RUN mode by pushing the READ/ADJUST and ADVANCE/MANUAL buttons (#1 and #2) for at least 3 seconds until all LEDs flash. Next, push and release but- ton #1 to enter the Read mode. Then push button #2 to advance to item 20 (“first most recent error”). Determine the error by reading the value in items 20 to 24 and referring to the Troubleshooting section.

One the error has been fixed, press buttons #1 and 2 for at least 3 seconds to exit Read mode. All LEDs will flash.

Enter Setup mode by pressing the READ/ADJUST button (#1) for at least 3 seconds. All LEDs will flash. Push the ADVANCE/MANUAL button (#2) to advance to item 20. Push READ/ADJUST to read item 20.

To reset the error code while the green DS4 LED is on, press the READ/ADJUST button (#1) once. In addition to resetting the error mode, this will erase all error codes. Cycling the power will also erase the error code.

XV. ECONOMI$ER+ CONFIGURATION

For most applications, the factory setting will be used to con- trol the EconoMi$er+. However, there are 19 different vari- ables that can be used to configure the control for wide range of applications. The factory settings and variables are shown in Table 37.

43

Image 43
Contents Installation Important Read Before InstallingContents Safety ConsiderationsBase Unit Dimensions 580F036-072 Base Unit Dimensions 580F073 IV. RIG and Place Unit III. Install External Trap for CONDEN- Sate DrainAlternate Unit Support II. Field Fabricate DuctworkCRRFCURB002A01 Unit Size Accessory CRRFCURB001A01Connector ALT Accessory Drain GAS PKG. Accy Hole PowerVI. Install GAS Piping Install Flue HoodRigging Details Unit 580F MAX WeightPhysical Data RETURN-AIR Filters Furnace SectionFreeze Protection Thermostat F OUTDOOR-AIR Inlet ScreensVII. Make Electrical Connections Field Power SupplyField Control Wiring Heat Anticipator SettingsPower Wiring Connections RLA LRA FLA MCA MOCP† Electrical Data Without Convenience OutletElectrical Data With Convenience Outlet Manual Outdoor-Air Damper VIII. Adjust FACTORY-INSTALLED OptionsHood BOX Optional EconoMi$er+Bracket Iarh OarhIAQ OATDamper Movement EconoMi$er+ Controller WiringThermostats Return Air Temperature RAT Sensor EconoMi$er+ Field-Installed AccessoriesOutdoor Air Temperature OAT Sensor Provided Supply Air Temperature SAT Sensor ProvidedOutdoor Air Humidity Sensor Indoor Air Quality Voltage SettingRange Resolution Temperature ResistanceEnthalpy Changeover Settings Indoor Air Humidity Sensor Occupied/Unoccupied SwitchPower Exhaust Remote EconoMi$er+ Enable ControlVentilation for People CO2 Sensor ConfigurationFull Occupancy Ventilation RateDirect-Drive Motors IX. Adjust EVAPORATOR-FAN SpeedBelt-Drive Motors Motor Data Fan Rpm at Motor Pulley Settings958 External Static Pressure in. wg Cfm Rpm Bhp Watts 900768 8701073 External Static Pressure in. wg Cfm Rpm Bhp Watts955 1181 970802 370 Low Speed840 432 935 802 370 912 489624 773856 967 579663 757941 Airflow Low Speed High SpeedBhp Watts 900 884762 777 859 458 944 579705 886 517 969 644790 353 896 470 990 599 790 353828 413 866 479944 635 1036 775 1119 924 828 413 930 535 1021 669866 479 964 607 1053 746 905 553 1000 687 1085 831966 771867 986START-UP Unit Preparation IV Internal WiringVI. Refrigerant Service Ports PRE-START-UPMain Burners IX. CoolingXI. Heating XIII. Ventilation Continuous FAN XII. Safety ReliefXIV. ECONOMI$ER+ Controller Economizer Motor DS1 DS2 DS3 DS4Input Name Type USE INPUT/OUTPUT Conversion Connection PIN Thermostat InputsConfiguration Variables Read and Setup Modes Start-Up Mode SequenceInput/Output Channels Setup Mode Error Mode Manual ModeXV. ECONOMI$ER+ Configuration Ventilation Air and Free Cooling Compressor Configuration and ControlCooling, Units without EconoMi$er+ Demand Ventilation ConfigurationPower Exhaust Configuration XVI. Operating SequenceCooling, Units with EconoMi$er+ Heating, Units without EconoMi$er+Service Cleaning IV. Manual OUTDOOR-AIR Damper III. Blower Belt AdjustmentECONOMI$ER+ Adjustment II. LubricationXVI. Replacement Parts Limit SwitchXIII. HIGH-PRESSURE Switch XIV. Loss of Charge SwitchSuction Line Pressure Psig Suction Line Temperature DEG. CSuction Line Temperature DEG. F Suction Line Pressure KilopascalsTON Unit 60 Hz Charging Chart Burner Section Details Troubleshooting ECONOMI$ER+ Troubleshooting RAM Test Failure Error Code 8 E2 Test FailureUnit Always in Unoccupied Mode II. Unit TroubleshootingHeating Service Analysis LED Error Code Service AnalysisCooling Service Analysis HPS FPTGND GVRAppendix a ECONOMI$ER+ Label Startup ModeAppendix a ECONOMI$ER+ Label Appendix B JOB Specific ECONOMI$ER+ Configuration Settings Index Call for Free Catalog Service TrainingPage III. START-UP Electrical START-UP ChecklistTemperatures Preliminary Information
Related manuals
Manual 80 pages 29.14 Kb Manual 52 pages 44.41 Kb

580F specifications

The Bryant 580F is a highly regarded gas furnace known for its exceptional heating performance and advanced technology. Designed for residential use, this model stands out for its reliability, efficiency, and user-friendly features that cater to modern heating demands.

One of the most notable features of the Bryant 580F is its efficiency rating. With an AFUE (Annual Fuel Utilization Efficiency) rating of up to 95%, this furnace maximizes heat output while minimizing energy consumption. This high level of efficiency not only results in lower utility bills but also reduces the environmental impact—a critical consideration for today’s eco-conscious homeowners.

The Bryant 580F is equipped with a multi-speed blower that ensures consistent airflow and enhances comfort by maintaining even temperatures throughout the home. This technology allows the furnace to adjust its operation based on the heating needs, leading to quieter operation and increased comfort levels.

In terms of construction, the Bryant 580F is built with durable materials that promise longevity and resilience against wear and tear. Its compact design makes installation easier, allowing it to fit into tight spaces without compromising its performance.

One of the standout technologies integrated into the Bryant 580F is its enhanced control system. The furnace works seamlessly with smart thermostats, allowing homeowners to monitor and adjust heating settings from their mobile devices. This feature not only provides convenience but also allows for energy-saving optimizations based on personal schedules and preferences.

Safety is also a primary concern with the Bryant 580F. It includes robust safety features such as a hot surface ignition system that eliminates the need for a standing pilot light, reducing the risk of gas leaks. Additionally, advanced diagnostics help in troubleshooting and maintenance, ensuring that potential issues can be identified and resolved quickly.

In conclusion, the Bryant 580F gas furnace is a remarkable choice for those seeking a blend of efficiency, comfort, and advanced technology. Its high AFUE rating, multi-speed blower, smart control compatibility, and safety features make it a reliable option for homeowners looking to invest in a dependable heating solution. As the demand for energy-efficient heating continues to grow, the Bryant 580F stands out as a model that meets and exceeds expectations in the modern heating landscape.