Bryant 580F II. Lubrication, III. Blower Belt Adjustment, IV. Manual OUTDOOR-AIR Damper

Page 48

Fig. 39 — Separating Coil Sections

II. LUBRICATION

A. Compressors

Each compressor is charged with the correct amount of oil at the factory.

B. Fan Motor Bearings

Fan motor bearings are of the permanently lubricated type. No further lubrication is required. No lubrication of con- denser or evaporator fan motors is required.

III. BLOWER BELT ADJUSTMENT

Inspect blower belt for wear, proper belt tension, and pulley alignment as conditions require or at the beginning of each heating and air conditioning season.

Refer to Step 9 — Adjust Evaporator-Fan Speed on page 24 for adjustment and alignment procedures.

Check belt tension at least once each heating or cooling sea- son or as conditions require. Adjust as required.

IV. MANUAL OUTDOOR-AIR DAMPER

If outdoor-air damper blade adjustment is required, see Manual Outdoor-Air Damper section on page 14.

V. ECONOMI$ER+ ADJUSTMENT

Refer to Optional EconoMi$er+ section on page 15.

VI. CONDENSER-FAN ADJUSTMENT (Fig. 40)

Shut off unit power supply. Remove condenser-fan assembly (grille, motor, and fan) and loosen fan hub setscrews. Adjust fan height as shown in Fig. 40. Tighten setscrews and replace condenser-fan assembly.

VII. REFRIGERANT CHARGE

Amount of refrigerant charge is listed on unit nameplate (also refer to Table 1). Compressor must run a minimum of 10 minutes before adjusting or checking charge.

Unit panels must be in place when unit is operating during charging procedure.

Fig. 40 — Condenser-Fan Adjustment

A. No Charge

Use standard evacuating techniques. After evacuating sys- tem, to 500 microns, weigh in the specified amount of refrig- erant. (Refer to Table 1.)

B. Low-Charge Cooling

Using Cooling Charging Charts, Fig. 41-44, vary refrigerant until the conditions of the appropriate chart are met. Note the charging charts are different from type normally used. Charts are based on charging the units to the correct super- heat for the various operating conditions. Accurate pressure gage and temperature sensing device are required. Do not use pocket type thermometers for measuring surface temper- atures as they are not designed for this type of measure- ment. Connect the pressure gage to the service port on the suction line. Mount the temperature sensing device on the suction line and insulate it so that outdoor ambient tempera- ture does not affect the reading. Indoor-air cfm must be within the normal operating range of the unit.

C. To Use Cooling Charging Chart

Take the outdoor ambient temperature and read the suction pressure gage. Refer to chart to determine what suction tem- perature should be. If suction temperature is high, add refrigerant. If suction temperature is low, carefully recover some of the charge. Recheck the suction pressure as charge is adjusted.

EXAMPLE: (Fig. 43)

Outdoor Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 F Suction Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80 psig Suction Temperature should be . . . . . . . . . . . . . . . . . . . 76 F (Suction Temperature may vary 5 F.)

VIII. FLUE GAS PASSAGEWAYS

To inspect the flue collector box and upper areas of the heat exchanger:

1.Remove the combustion blower wheel and motor assembly according to directions in Combustion-Air Blower section on page 49.

2.Remove the flue cover to inspect the heat exchanger.

3.Clean all surfaces as required using a wire brush.

48

Image 48
Contents Important Read Before Installing ContentsSafety Considerations InstallationBase Unit Dimensions 580F036-072 Base Unit Dimensions 580F073 III. Install External Trap for CONDEN- Sate Drain Alternate Unit SupportII. Field Fabricate Ductwork IV. RIG and Place UnitUnit Size Accessory CRRFCURB001A01 Connector ALT Accessory Drain GASPKG. Accy Hole Power CRRFCURB002A01Install Flue Hood VI. Install GAS PipingUnit 580F MAX Weight Rigging DetailsPhysical Data Furnace Section Freeze Protection Thermostat FOUTDOOR-AIR Inlet Screens RETURN-AIR FiltersField Power Supply Field Control WiringHeat Anticipator Settings VII. Make Electrical ConnectionsPower Wiring Connections Electrical Data Without Convenience Outlet RLA LRA FLA MCA MOCP†Electrical Data With Convenience Outlet VIII. Adjust FACTORY-INSTALLED Options Manual Outdoor-Air DamperOptional EconoMi$er+ Hood BOXBracket Oarh IAQOAT IarhEconoMi$er+ Controller Wiring Damper MovementThermostats EconoMi$er+ Field-Installed Accessories Outdoor Air Temperature OAT Sensor ProvidedSupply Air Temperature SAT Sensor Provided Return Air Temperature RAT SensorIndoor Air Quality Voltage Setting Outdoor Air Humidity SensorTemperature Resistance Range ResolutionEnthalpy Changeover Settings Occupied/Unoccupied Switch Power ExhaustRemote EconoMi$er+ Enable Control Indoor Air Humidity SensorCO2 Sensor Configuration Full OccupancyVentilation Rate Ventilation for PeopleIX. Adjust EVAPORATOR-FAN Speed Direct-Drive MotorsBelt-Drive Motors Fan Rpm at Motor Pulley Settings Motor DataExternal Static Pressure in. wg Cfm Rpm Bhp Watts 900 768870 958External Static Pressure in. wg Cfm Rpm Bhp Watts 9551181 970 1073Low Speed 802 370840 432 802 370 912 489 624773 935967 579 663757 856Airflow Low Speed High Speed Bhp Watts 900884 941762 859 458 944 579 705886 517 969 644 777790 353 828 413866 479 790 353 896 470 990 599828 413 930 535 1021 669 866 479 964 607 1053 746905 553 1000 687 1085 831 944 635 1036 775 1119 924771 867986 966IV Internal Wiring VI. Refrigerant Service PortsPRE-START-UP START-UP Unit PreparationIX. Cooling Main BurnersXI. Heating XII. Safety Relief XIII. Ventilation Continuous FANXIV. ECONOMI$ER+ Controller DS1 DS2 DS3 DS4 Input Name Type USE INPUT/OUTPUT Conversion Connection PINThermostat Inputs Economizer MotorStart-Up Mode Sequence Configuration Variables Read and Setup ModesInput/Output Channels Setup Mode Manual Mode Error ModeXV. ECONOMI$ER+ Configuration Compressor Configuration and Control Ventilation Air and Free CoolingDemand Ventilation Configuration Power Exhaust ConfigurationXVI. Operating Sequence Cooling, Units without EconoMi$er+Heating, Units without EconoMi$er+ Cooling, Units with EconoMi$er+Service Cleaning III. Blower Belt Adjustment ECONOMI$ER+ AdjustmentII. Lubrication IV. Manual OUTDOOR-AIR DamperLimit Switch XIII. HIGH-PRESSURE SwitchXIV. Loss of Charge Switch XVI. Replacement PartsSuction Line Temperature DEG. C Suction Line Temperature DEG. FSuction Line Pressure Kilopascals Suction Line Pressure PsigTON Unit 60 Hz Charging Chart Burner Section Details Troubleshooting ECONOMI$ER+ Troubleshooting Error Code 8 E2 Test Failure Unit Always in Unoccupied ModeII. Unit Troubleshooting RAM Test FailureLED Error Code Service Analysis Heating Service AnalysisCooling Service Analysis FPT GNDGVR HPSStartup Mode Appendix a ECONOMI$ER+ LabelAppendix a ECONOMI$ER+ Label Appendix B JOB Specific ECONOMI$ER+ Configuration Settings Index Service Training Call for Free CatalogPage START-UP Checklist TemperaturesPreliminary Information III. START-UP Electrical
Related manuals
Manual 80 pages 29.14 Kb Manual 52 pages 44.41 Kb

580F specifications

The Bryant 580F is a highly regarded gas furnace known for its exceptional heating performance and advanced technology. Designed for residential use, this model stands out for its reliability, efficiency, and user-friendly features that cater to modern heating demands.

One of the most notable features of the Bryant 580F is its efficiency rating. With an AFUE (Annual Fuel Utilization Efficiency) rating of up to 95%, this furnace maximizes heat output while minimizing energy consumption. This high level of efficiency not only results in lower utility bills but also reduces the environmental impact—a critical consideration for today’s eco-conscious homeowners.

The Bryant 580F is equipped with a multi-speed blower that ensures consistent airflow and enhances comfort by maintaining even temperatures throughout the home. This technology allows the furnace to adjust its operation based on the heating needs, leading to quieter operation and increased comfort levels.

In terms of construction, the Bryant 580F is built with durable materials that promise longevity and resilience against wear and tear. Its compact design makes installation easier, allowing it to fit into tight spaces without compromising its performance.

One of the standout technologies integrated into the Bryant 580F is its enhanced control system. The furnace works seamlessly with smart thermostats, allowing homeowners to monitor and adjust heating settings from their mobile devices. This feature not only provides convenience but also allows for energy-saving optimizations based on personal schedules and preferences.

Safety is also a primary concern with the Bryant 580F. It includes robust safety features such as a hot surface ignition system that eliminates the need for a standing pilot light, reducing the risk of gas leaks. Additionally, advanced diagnostics help in troubleshooting and maintenance, ensuring that potential issues can be identified and resolved quickly.

In conclusion, the Bryant 580F gas furnace is a remarkable choice for those seeking a blend of efficiency, comfort, and advanced technology. Its high AFUE rating, multi-speed blower, smart control compatibility, and safety features make it a reliable option for homeowners looking to invest in a dependable heating solution. As the demand for energy-efficient heating continues to grow, the Bryant 580F stands out as a model that meets and exceeds expectations in the modern heating landscape.