Bryant 580F XII. Safety Relief, XIII. Ventilation Continuous FAN, XIV. ECONOMI$ER+ Controller

Page 39

XII. SAFETY RELIEF

A soft solder joint at the suction service Schrader port pro- vides pressure relief under abnormal temperature and pres- sure conditions (i.e., fire in building).

XIII. VENTILATION (CONTINUOUS FAN)

Set fan and system selector switches at ON and OFF posi- tions, respectively. Evaporator fan operates continuously to provide constant air circulation. When the evaporator-fan selector switch is turned to the OFF position, there is a 30-second delay before the fan turns off.

XIV. ECONOMI$ER+ CONTROLLER

The EconoMi$er+ controller is mounted to the top of the EconoMi$er+ damper and is accessible by removing the filter access door of the unit.

The EconoMi$er+ controller is protected by a sheet metal enclosure mounted over the controller. Remove the single screw on the front of the enclosure and lift off the top for access to the controller. The primary purpose of the controller is to provide control of the EconoMi$er+ dampers and the cooling compression stages. The status of the indoor fan is monitored through the G input but is not directly controlled by the controller. The heating function is completely indepen- dent of the controller.

IMPORTANT: The controller can only be used with conven- tional thermostats with Y1, Y2 and G input to the controller; it can NOT be used with electronic thermostats with a pro- portional room temperature input, or with Variable Air Vol- ume systems.

There are 4 LEDs on the controller, which are used to read values and display status and configuration information. There are 2 buttons (READ/ADJUST and ADVANCE/ MAN- UAL), which change modes and configure the controller. See Fig. 36.

The EconoMi$er+ microprocessor based control system pro- vides the following control functions:

EconoMi$er+ damper control for free cooling

Minimum position control for ventilation

Demand Ventilation Control using a CO2 sensor

Compressor Cooling Stage Control

Occupied/Unoccupied Control

Diagnostics Display and History

Manual test control

See Table 35 for Inputs and Outputs.

A. Integrated Display

The control board includes an integrated display, which is used for the following functions:

Configuration and setup

Set point and control adjustment

Error status and alarm monitoring

Manual control

Reading sensor values

There are 5 modes of display operation:

Startup Mode

Run Mode

Read Mode

Setup Mode

Manual Mode

External devices are not required to operate and configure the control.

B. Startup Mode

During the first 3 seconds after power is applied to the con- trol, the four LEDs flash as shown in Table 36, indicating

that the control is being initialized. The buttons are not operational during Startup mode.

C. Run Mode

Run mode indicates status of controller and unit. The mode can be changed to the Read, Setup, or Manual modes by pushing various buttons.

While the control is in Run mode, the DS1 heartbeat indica- tor LED (red) will flash to indicate the controller is operating properly. The DS2 Econo indicator LED (yellow) will flash whenever economizer is being used for free cooling. The DS3 first stage cooling indicator LED (green) will be on steady indicate demand for stage 1 cooling. The DS4 second stage cooling indicator LED (green) will be on steady to indicate demand for stage 2 cooling.

If the controller is in a different mode, the controller will return to Run mode after 10 minutes of user inactivity or if the READ/ADJUST (#1) and ADVANCE/MANUAL (#2) but- tons are held for at least 3 seconds until all LEDs flash.

D. Read Mode

Read mode is used to check set points (Table 37) and I/O channel status (Table 38). Enter the Read mode by pushing and releasing the READ/ADJUST (#1) button. A user can only enter Read mode from the Run mode (to get to Run mode, press both the #1 and #2 buttons for at least 3 seconds until all LEDs flash). In Read mode, LEDs are not lit until the READ/ADJUST button (#1) is pushed.

NOTE: If the user pushes and holds the READ/ADJUST but- ton (#1) for more than 3 seconds, then the control will go into the Setup mode, indicated by the yellow LED (on steady).

While in Read mode, push button #1 then the DS1 LED (Red) flashes to indicate setup point number as defined in the setup table. The two green LEDs will then show the value of the display item. The DS3 LED will first display the tens digit and the DS4 LED will then display the ones digit. For example to display 54, the DS3 LED will flash 1 group of 5 at a high flash rate to indicate 50, and then follow with 4 flashes (DS4) at 1-second intervals to complete the display of the number 54.

NOTE: Do not try to count the “5 Fast Flashes” individually, but instead count how many groups of 5 flashes were dis- played. In this case, 1 group of 5 flashes, plus the 4 flashes at 1 second results in the value of 54.

To read the display again, push the READ/ADJUST (#1) but- ton and the sequence will repeat as many times as needed.

To advance to the next setup point, push the ADVANCE/ MANUAL (#2) button. The controller will cycle through all the setup channels (Table 37) and then the I/O channels (Table 38) and then back to the first setup channel.

NOTE: The user can only advance forward, not reset to #1 or go backwards. Cycling the EconoMi$er+ power will reset the item number (but not the item value) to item #1.

In the Read mode for setup variables, the LEDs will not turn on steady; the LEDs will always flash. Steady-on indicators are reserved for the configuration modes. No data is modified in the Read mode. The controller will always remain at the last read number even if reset back to normal operation.

NOTE: To enter another mode, the user first must exit the Read mode.

If no button is pushed in 10 minutes, Read mode will auto- matically be exited. Also, if the READ/ADJUST (#1) and ADVANCE/MANUAL (#2) buttons are pushed and held for more than 3 seconds, then Read mode will be exited to Run mode. While in the Read mode, the controller will continue to operate with normal unit control.

39

Image 39
Contents Installation Important Read Before InstallingContents Safety ConsiderationsBase Unit Dimensions 580F036-072 Base Unit Dimensions 580F073 IV. RIG and Place Unit III. Install External Trap for CONDEN- Sate DrainAlternate Unit Support II. Field Fabricate DuctworkCRRFCURB002A01 Unit Size Accessory CRRFCURB001A01Connector ALT Accessory Drain GAS PKG. Accy Hole PowerVI. Install GAS Piping Install Flue HoodRigging Details Unit 580F MAX WeightPhysical Data RETURN-AIR Filters Furnace SectionFreeze Protection Thermostat F OUTDOOR-AIR Inlet ScreensVII. Make Electrical Connections Field Power SupplyField Control Wiring Heat Anticipator SettingsPower Wiring Connections RLA LRA FLA MCA MOCP† Electrical Data Without Convenience OutletElectrical Data With Convenience Outlet Manual Outdoor-Air Damper VIII. Adjust FACTORY-INSTALLED OptionsOptional EconoMi$er+ Hood BOXBracket Iarh OarhIAQ OATEconoMi$er+ Controller Wiring Damper MovementThermostats Return Air Temperature RAT Sensor EconoMi$er+ Field-Installed AccessoriesOutdoor Air Temperature OAT Sensor Provided Supply Air Temperature SAT Sensor ProvidedOutdoor Air Humidity Sensor Indoor Air Quality Voltage SettingRange Resolution Temperature ResistanceEnthalpy Changeover Settings Indoor Air Humidity Sensor Occupied/Unoccupied SwitchPower Exhaust Remote EconoMi$er+ Enable ControlVentilation for People CO2 Sensor ConfigurationFull Occupancy Ventilation RateIX. Adjust EVAPORATOR-FAN Speed Direct-Drive MotorsBelt-Drive Motors Motor Data Fan Rpm at Motor Pulley Settings958 External Static Pressure in. wg Cfm Rpm Bhp Watts 900768 8701073 External Static Pressure in. wg Cfm Rpm Bhp Watts955 1181 970Low Speed 802 370840 432 935 802 370 912 489624 773856 967 579663 757941 Airflow Low Speed High SpeedBhp Watts 900 884762 777 859 458 944 579705 886 517 969 644790 353 896 470 990 599 790 353828 413 866 479944 635 1036 775 1119 924 828 413 930 535 1021 669866 479 964 607 1053 746 905 553 1000 687 1085 831966 771867 986START-UP Unit Preparation IV Internal WiringVI. Refrigerant Service Ports PRE-START-UPIX. Cooling Main BurnersXI. Heating XII. Safety Relief XIII. Ventilation Continuous FANXIV. ECONOMI$ER+ Controller Economizer Motor DS1 DS2 DS3 DS4Input Name Type USE INPUT/OUTPUT Conversion Connection PIN Thermostat InputsStart-Up Mode Sequence Configuration Variables Read and Setup ModesInput/Output Channels Setup Mode Manual Mode Error ModeXV. ECONOMI$ER+ Configuration Ventilation Air and Free Cooling Compressor Configuration and ControlCooling, Units without EconoMi$er+ Demand Ventilation ConfigurationPower Exhaust Configuration XVI. Operating SequenceCooling, Units with EconoMi$er+ Heating, Units without EconoMi$er+Service Cleaning IV. Manual OUTDOOR-AIR Damper III. Blower Belt AdjustmentECONOMI$ER+ Adjustment II. LubricationXVI. Replacement Parts Limit SwitchXIII. HIGH-PRESSURE Switch XIV. Loss of Charge SwitchSuction Line Pressure Psig Suction Line Temperature DEG. CSuction Line Temperature DEG. F Suction Line Pressure KilopascalsTON Unit 60 Hz Charging Chart Burner Section Details Troubleshooting ECONOMI$ER+ Troubleshooting RAM Test Failure Error Code 8 E2 Test FailureUnit Always in Unoccupied Mode II. Unit TroubleshootingHeating Service Analysis LED Error Code Service AnalysisCooling Service Analysis HPS FPTGND GVRAppendix a ECONOMI$ER+ Label Startup ModeAppendix a ECONOMI$ER+ Label Appendix B JOB Specific ECONOMI$ER+ Configuration Settings Index Call for Free Catalog Service TrainingPage III. START-UP Electrical START-UP ChecklistTemperatures Preliminary Information
Related manuals
Manual 80 pages 29.14 Kb Manual 52 pages 44.41 Kb

580F specifications

The Bryant 580F is a highly regarded gas furnace known for its exceptional heating performance and advanced technology. Designed for residential use, this model stands out for its reliability, efficiency, and user-friendly features that cater to modern heating demands.

One of the most notable features of the Bryant 580F is its efficiency rating. With an AFUE (Annual Fuel Utilization Efficiency) rating of up to 95%, this furnace maximizes heat output while minimizing energy consumption. This high level of efficiency not only results in lower utility bills but also reduces the environmental impact—a critical consideration for today’s eco-conscious homeowners.

The Bryant 580F is equipped with a multi-speed blower that ensures consistent airflow and enhances comfort by maintaining even temperatures throughout the home. This technology allows the furnace to adjust its operation based on the heating needs, leading to quieter operation and increased comfort levels.

In terms of construction, the Bryant 580F is built with durable materials that promise longevity and resilience against wear and tear. Its compact design makes installation easier, allowing it to fit into tight spaces without compromising its performance.

One of the standout technologies integrated into the Bryant 580F is its enhanced control system. The furnace works seamlessly with smart thermostats, allowing homeowners to monitor and adjust heating settings from their mobile devices. This feature not only provides convenience but also allows for energy-saving optimizations based on personal schedules and preferences.

Safety is also a primary concern with the Bryant 580F. It includes robust safety features such as a hot surface ignition system that eliminates the need for a standing pilot light, reducing the risk of gas leaks. Additionally, advanced diagnostics help in troubleshooting and maintenance, ensuring that potential issues can be identified and resolved quickly.

In conclusion, the Bryant 580F gas furnace is a remarkable choice for those seeking a blend of efficiency, comfort, and advanced technology. Its high AFUE rating, multi-speed blower, smart control compatibility, and safety features make it a reliable option for homeowners looking to invest in a dependable heating solution. As the demand for energy-efficient heating continues to grow, the Bryant 580F stands out as a model that meets and exceeds expectations in the modern heating landscape.