Bryant 580F installation instructions Physical Data

Page 8

Table 1 — Physical Data

UNIT SIZE 580F

 

036

 

 

048

 

060

 

 

072

 

 

073

NOMINAL CAPACITY (tons)

 

3

 

 

4

 

5

 

 

6

 

 

6

 

OPERATING WEIGHT (lb)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Al/Al*

 

460

 

 

470

 

490

 

 

565

 

 

615

Al/Cu*

 

465

 

 

476

 

497

 

 

576

 

 

Cu/Cu*

 

468

 

 

482

 

505

 

 

587

 

 

Economizer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EconoMi$er+

 

50

 

 

50

 

50

 

 

50

 

 

50

Roof Curb†

 

115

 

 

115

 

115

 

 

115

 

 

115

COMPRESSOR

 

 

 

 

 

Reciprocating

 

 

 

 

 

 

Scroll

 

 

Quantity

 

1

 

 

1

 

1

 

 

1

 

 

1

 

 

 

 

 

 

No. Cylinders (per Circuit)

 

2

 

 

2

 

2

 

 

2

 

 

2

 

Oil (oz)

 

50

 

 

50

 

50

 

 

54

 

 

60

REFRIGERANT TYPE

 

 

 

 

 

 

 

 

R-22

 

 

 

 

 

 

Expansion Device

 

 

 

 

 

 

Fixed Orifice Metering Device

 

 

 

 

 

 

Operating Charge (lb-oz)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Circuit 1

 

4-4

 

 

6-6

 

6-14

 

 

9-0

 

 

11-0

Circuit 2

 

 

 

 

 

 

 

 

CONDENSER COIL

 

 

 

 

 

Enhanced Copper Tubes, Aluminum Lanced Fins

 

 

Rows...Fins/in.

 

1...17

 

 

2...17

 

2...17

 

 

2...17

 

 

2...17

 

 

 

 

 

Total Face Area (sq ft)

 

8.36

 

 

8.36

 

10.42

 

 

10.42

 

 

16.5

CONDENSER FAN

 

 

 

 

 

 

 

 

Propeller Type

 

 

 

 

 

 

Nominal Cfm

 

3500

 

 

4000

 

4000

 

 

4000

 

 

4100

 

 

 

 

 

Quantity...Diameter (in.)

 

1...22.0

 

 

1...22.0

 

1...22.0

 

 

1...22.0

 

 

1...22.0

Motor Hp...Rpm

 

1/ ...1100

 

 

1/ ...1100

 

1/ ...1100

 

 

1/ ...1100

 

 

1/ ...1100

Watts Input (Total)

 

4

 

 

 

4

 

 

4

 

 

 

4

 

 

 

4

 

 

325

 

 

325

 

325

 

 

325

 

 

320

EVAPORATOR COIL

 

 

 

Enhanced Copper Tubes, Aluminum Double-Wavy Fins

 

 

Rows...Fins/in.

 

2...15

 

 

2...15

 

3...15

 

 

4...15

 

 

4...15

 

 

 

 

 

Total Face Area (sq ft)

 

4.17

 

 

5.5

 

5.5

 

 

5.5

 

 

5.5

EVAPORATOR FAN

 

 

 

 

 

 

 

Centrifugal Type

 

 

 

 

 

 

Quantity...Size (in.)

Std

1...10 x 10

 

 

1...10 x 10

 

1...11 x 10

 

 

1...10 x 10

 

 

1...10 x 10

 

 

 

 

 

 

Alt

1...10 x 10

 

 

1...10 x 10

 

1...10 x 10

 

 

 

 

 

High-Static

1...10 x 10

 

 

1...10 x 10

 

1...11 x 10

 

 

1...10 x 10

 

 

1...10 x 10

Type Drive

Std

Direct

 

 

Direct

 

Direct

 

 

Belt

 

 

Belt

 

Alt

Belt

 

 

Belt

 

Belt

 

 

 

 

Nominal Cfm

High-Static

Belt

 

 

Belt

 

Belt

 

 

Belt

 

 

Belt

 

1200

 

 

1600

 

2000

 

 

2100

 

 

2100

Maximum Continuous Bhp

Std

.34

 

 

.75

 

1.20

 

 

2.40

 

 

2.40

 

Alt

1.20

 

 

1.20

 

1.30/2.40**

 

 

 

 

 

High-Static

2.40

 

 

2.40

 

2.90

 

 

2.90

 

 

2.90

Motor Frame Size

Std

48

 

 

48

 

48

 

 

56

 

 

56

 

Alt

48

 

 

48

 

56

 

 

 

 

 

High-Static

56

 

 

56

 

56

 

 

56

 

 

56

Nominal Rpm High/Low (Direct Drive)

Std

860/800

 

 

1075/970

 

1075/970

 

 

 

 

 

Alt

 

 

 

 

 

 

 

 

High-Static

 

 

 

 

 

 

 

Fan Rpm Range

Std

 

 

 

 

 

1070-1460

 

 

1070-1460

 

Alt

685-1045

 

 

770-1175

 

8778-1192

 

 

 

 

Motor Bearing Type

High-Static

1075-1455

 

 

1075-1455

 

1300-1685

 

 

1300-1685

 

 

1300-1685

 

Ball

 

 

Ball

 

Ball

 

 

Ball

 

 

Ball

Maximum Allowable Rpm

 

2100

 

 

2100

 

2100

 

 

2100

 

 

2100

Motor Pulley Pitch Diameter Min/Max (in.)

Std

 

 

 

 

 

2.8/3.8

 

 

2.8/3.8

 

Alt

1.9/2.9

 

 

1.9/2.9

 

2.4/3.4

 

 

 

 

 

High-Static

2.8/3.8

 

 

2.8/3.8

 

3.4/4.4

 

 

3.4/4.4

 

 

3.4/4.4

Nominal Motor Shaft Diameter (in.)

Std

1/

2

 

 

1/

2

 

1/

2

 

 

5/

8

 

 

5/

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

 

Alt

1/2

 

 

1/2

 

5/8

 

 

 

 

 

High-Static

5/

8

 

 

5/

8

 

5/

8

 

 

5/

8

 

 

7/

 

Fan Pulley Pitch Diameter (in.)

Std

 

 

 

 

 

 

 

 

 

 

 

8

 

 

 

 

 

4.5

 

 

4.5

 

Alt

4.5

 

 

4.0

 

4.5

 

 

 

 

 

High-Static

4.5

 

 

4.5

 

4.5

 

 

4.5

 

 

4.5

Belt, Quantity...Type...Length (in.)

Std

 

 

 

 

 

1...A...40

 

 

1...A...40

 

Alt

1...A...34

 

 

1...A...34

 

1...A...39

 

 

 

 

 

High-Static

1...A...39

 

 

1...A...39

 

1...A...40

 

 

1...A...40

 

 

1...A...40

Pulley Center Line Distance (in.)

Std

 

 

 

 

 

14.7-15.5

 

 

14.7-15.5

 

Alt

10.0-12.4

 

 

10.0-12.4

 

14.7-15.5

 

 

 

 

 

High-Static

10.0-12.4

 

 

10.0-12.4

 

14.7-15.5

 

 

14.7-15.5

 

 

14.7-15.5

Speed Change per Full Turn of

Std

 

 

 

 

 

80

 

 

80

Movable Pulley Flange (rpm)

Alt

48

 

 

70

 

80

 

 

 

 

 

High-Static

65

 

 

65

 

60

 

 

60

 

 

60

Movable Pulley Maximum Full Turns

Std

 

 

 

 

 

5

 

 

5

 

From Closed Position

Alt

5

 

 

5

 

6

 

 

 

 

 

High-Static

6

 

 

6

 

5

 

 

5

 

 

5

 

Factory Setting

Std

 

 

 

 

 

3

 

 

3

 

 

Alt

3

 

 

3

 

3

 

 

 

 

 

High-Static

31/

 

 

31/

 

31/

 

 

31/

 

 

31/

2

Factory Speed Setting (rpm)

Std

 

2

 

 

 

2

 

 

2

 

 

 

2

 

 

 

 

 

 

 

 

1226

 

 

1226

 

Alt

829

 

 

932

 

1035

 

 

 

 

 

High-Static

1233

 

 

1233

 

1416

 

 

1416

 

 

1416

Fan Shaft Diameter at Pulley (in.)

 

5/

8

 

 

5/

8

 

5/

8

 

 

5/

8

 

 

5/

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

 

 

LEGEND

Al

Aluminum

Bhp —

Brake Horsepower

Cu

Copper

*Evaporator coil fin material/condenser coil fin material. Contact your local rep- resentative for details about coated fins.

†Weight of 14-in. roof curb. **Single phase/three-phase.

††Rollout switch lockout is manually reset by interrupting power to unit or reset- ting thermostat.

California rated three-phase high heat models.

***Three phase standard high-heat models have heating input values as shown. Single phase standard high heat models have one-stage heating with heating input values as follows:

580FJV036115 — 115,000 Btuh

580FJV048150 — 150,000 Btuh

580FJV060150 — 150,000 Btuh

†††California SCAQMD compliant Low NOx models have combustion products that are controlled to 40 nanograms per joule or less.

8

Image 8
Contents Important Read Before Installing ContentsSafety Considerations InstallationBase Unit Dimensions 580F036-072 Base Unit Dimensions 580F073 III. Install External Trap for CONDEN- Sate Drain Alternate Unit SupportII. Field Fabricate Ductwork IV. RIG and Place UnitUnit Size Accessory CRRFCURB001A01 Connector ALT Accessory Drain GASPKG. Accy Hole Power CRRFCURB002A01Install Flue Hood VI. Install GAS PipingUnit 580F MAX Weight Rigging DetailsPhysical Data Furnace Section Freeze Protection Thermostat FOUTDOOR-AIR Inlet Screens RETURN-AIR FiltersField Power Supply Field Control WiringHeat Anticipator Settings VII. Make Electrical ConnectionsPower Wiring Connections Electrical Data Without Convenience Outlet RLA LRA FLA MCA MOCP†Electrical Data With Convenience Outlet VIII. Adjust FACTORY-INSTALLED Options Manual Outdoor-Air DamperBracket Optional EconoMi$er+Hood BOX Oarh IAQOAT IarhThermostats EconoMi$er+ Controller WiringDamper Movement EconoMi$er+ Field-Installed Accessories Outdoor Air Temperature OAT Sensor ProvidedSupply Air Temperature SAT Sensor Provided Return Air Temperature RAT SensorIndoor Air Quality Voltage Setting Outdoor Air Humidity SensorTemperature Resistance Range ResolutionEnthalpy Changeover Settings Occupied/Unoccupied Switch Power ExhaustRemote EconoMi$er+ Enable Control Indoor Air Humidity SensorCO2 Sensor Configuration Full OccupancyVentilation Rate Ventilation for PeopleBelt-Drive Motors IX. Adjust EVAPORATOR-FAN SpeedDirect-Drive Motors Fan Rpm at Motor Pulley Settings Motor DataExternal Static Pressure in. wg Cfm Rpm Bhp Watts 900 768870 958External Static Pressure in. wg Cfm Rpm Bhp Watts 9551181 970 1073840 432 Low Speed802 370 802 370 912 489 624773 935967 579 663757 856Airflow Low Speed High Speed Bhp Watts 900884 941762 859 458 944 579 705886 517 969 644 777790 353 828 413866 479 790 353 896 470 990 599828 413 930 535 1021 669 866 479 964 607 1053 746905 553 1000 687 1085 831 944 635 1036 775 1119 924771 867986 966IV Internal Wiring VI. Refrigerant Service PortsPRE-START-UP START-UP Unit PreparationXI. Heating IX. CoolingMain Burners XIV. ECONOMI$ER+ Controller XII. Safety ReliefXIII. Ventilation Continuous FAN DS1 DS2 DS3 DS4 Input Name Type USE INPUT/OUTPUT Conversion Connection PINThermostat Inputs Economizer MotorInput/Output Channels Start-Up Mode SequenceConfiguration Variables Read and Setup Modes Setup Mode XV. ECONOMI$ER+ Configuration Manual ModeError Mode Compressor Configuration and Control Ventilation Air and Free CoolingDemand Ventilation Configuration Power Exhaust ConfigurationXVI. Operating Sequence Cooling, Units without EconoMi$er+Heating, Units without EconoMi$er+ Cooling, Units with EconoMi$er+Service Cleaning III. Blower Belt Adjustment ECONOMI$ER+ AdjustmentII. Lubrication IV. Manual OUTDOOR-AIR DamperLimit Switch XIII. HIGH-PRESSURE SwitchXIV. Loss of Charge Switch XVI. Replacement PartsSuction Line Temperature DEG. C Suction Line Temperature DEG. FSuction Line Pressure Kilopascals Suction Line Pressure PsigTON Unit 60 Hz Charging Chart Burner Section Details Troubleshooting ECONOMI$ER+ Troubleshooting Error Code 8 E2 Test Failure Unit Always in Unoccupied ModeII. Unit Troubleshooting RAM Test FailureLED Error Code Service Analysis Heating Service AnalysisCooling Service Analysis FPT GNDGVR HPSStartup Mode Appendix a ECONOMI$ER+ LabelAppendix a ECONOMI$ER+ Label Appendix B JOB Specific ECONOMI$ER+ Configuration Settings Index Service Training Call for Free CatalogPage START-UP Checklist TemperaturesPreliminary Information III. START-UP Electrical
Related manuals
Manual 80 pages 29.14 Kb Manual 52 pages 44.41 Kb

580F specifications

The Bryant 580F is a highly regarded gas furnace known for its exceptional heating performance and advanced technology. Designed for residential use, this model stands out for its reliability, efficiency, and user-friendly features that cater to modern heating demands.

One of the most notable features of the Bryant 580F is its efficiency rating. With an AFUE (Annual Fuel Utilization Efficiency) rating of up to 95%, this furnace maximizes heat output while minimizing energy consumption. This high level of efficiency not only results in lower utility bills but also reduces the environmental impact—a critical consideration for today’s eco-conscious homeowners.

The Bryant 580F is equipped with a multi-speed blower that ensures consistent airflow and enhances comfort by maintaining even temperatures throughout the home. This technology allows the furnace to adjust its operation based on the heating needs, leading to quieter operation and increased comfort levels.

In terms of construction, the Bryant 580F is built with durable materials that promise longevity and resilience against wear and tear. Its compact design makes installation easier, allowing it to fit into tight spaces without compromising its performance.

One of the standout technologies integrated into the Bryant 580F is its enhanced control system. The furnace works seamlessly with smart thermostats, allowing homeowners to monitor and adjust heating settings from their mobile devices. This feature not only provides convenience but also allows for energy-saving optimizations based on personal schedules and preferences.

Safety is also a primary concern with the Bryant 580F. It includes robust safety features such as a hot surface ignition system that eliminates the need for a standing pilot light, reducing the risk of gas leaks. Additionally, advanced diagnostics help in troubleshooting and maintenance, ensuring that potential issues can be identified and resolved quickly.

In conclusion, the Bryant 580F gas furnace is a remarkable choice for those seeking a blend of efficiency, comfort, and advanced technology. Its high AFUE rating, multi-speed blower, smart control compatibility, and safety features make it a reliable option for homeowners looking to invest in a dependable heating solution. As the demand for energy-efficient heating continues to grow, the Bryant 580F stands out as a model that meets and exceeds expectations in the modern heating landscape.