Bryant 580F installation instructions Optional EconoMi$er+, Hood BOX, Bracket

Page 15

B. Optional EconoMi$er+

See Fig. 16 for EconoMi$er+ component locations.

NOTE: These instructions are for the factory-installed optional EconoMi$er+ only. Refer to the accessory EconoMi$er+ installation instructions when field installing an EconoMi$er+ accessory.

1.To remove the existing unit filter access panel, raise the panel and swing the bottom outward. The panel is now disengaged from the track and can be removed. See Fig. 17.

2.The box with the EconoMi$er+ hood components is shipped in the compartment behind the EconoMi$er+. The EconoMi$er+ does not have to be removed to retrieve the hood box. Remove the screw holding the hood box bracket to the top of the EconoMi$er+. Slide the hood box out of the unit. See Fig. 18.

IMPORTANT: If a power exhaust accessory will be installed on the unit, the hood shipped with the unit will not be used and must be discarded. Save the aluminum filter for use in the power exhaust.

3.The indoor coil access panel will be used as the top of the hood. Remove the screws along the bottom of the indoor coil access panel. See Fig. 19.

4.Swing out the indoor coil access panel and insert the hood sides under the panel (hood top). Use the screws provided to attach the hood sides to the hood top. Use the screws provided to attach the hood sides to the unit. See Fig. 20.

5.Remove the shipping tape holding the EconoMi$er+ barometric relief damper in place.

6.Insert the hood divider between the hood sides. See Fig. 20. Secure hood divider with 2 screws on each hood side. The hood divider is also used as the bottom filter rack for the aluminum filter.

7.Open the filter clips which are located underneath the hood top. Insert the aluminum filter into the bot- tom filter rack (hood divider). Push the filter into po- sition past the open filter clips. Close the filter clips to lock the filter into place. See Fig. 21.

8.Caulk the ends of the joint between the unit top panel and the hood top. See Fig. 19.

9.Replace the filter access panel.

10.Install all EconoMi$er+ accessories. EconoMi$er+ wiring is shown in Fig. 22.

Barometric flow capacity is shown in Fig. 23. Outdoor air leakage is shown in Fig. 24. Return air pressure drop is shown in Fig. 25.

FILTER ACCESS PANEL

COMPRESSOR

ACCESS PANEL

OUTDOOR-AIR OPENING AND

INDOOR COIL ACCESS PANEL

Fig. 17 — Typical Access Panel Locations

 

 

 

x

 

 

 

o

 

o

B

 

HOOD BOX

H

od

 

 

 

 

 

BRACKET

 

 

 

 

Fig. 18 — Hood Box Removal

ECONOMI$ER+

ECONOMI$ER+

OUTDOOR

PLUG

CONTROLLER

AIR HOOD

 

(UNDER COVER)

 

 

 

 

SIDE

 

 

 

PANEL

 

HOOD

 

 

 

SHIPPING

 

 

 

BRACKET

 

 

 

ECONOMI$ER+

 

 

 

CONTROLLER

 

 

 

LABELS

 

 

 

 

 

TOP

 

GEAR

 

SIDE

 

 

PANEL

 

DRIVEN

 

CAULK

 

DAMPER

INDOOR

HERE

 

 

INDOOR

 

 

COIL

COIL

OUTDOOR AIR

BAROMETRIC

ACCESS

ACCESS

PANEL

PANEL

TEMPERATURE

RELIEF

 

 

SENSOR

DAMPER

 

 

Fig. 16 — EconoMi$er+ Component Locations

Fig. 19 — Indoor Coil Access Panel Relocation

15

Image 15
Contents Installation Important Read Before InstallingContents Safety ConsiderationsBase Unit Dimensions 580F036-072 Base Unit Dimensions 580F073 IV. RIG and Place Unit III. Install External Trap for CONDEN- Sate DrainAlternate Unit Support II. Field Fabricate DuctworkCRRFCURB002A01 Unit Size Accessory CRRFCURB001A01Connector ALT Accessory Drain GAS PKG. Accy Hole PowerVI. Install GAS Piping Install Flue HoodRigging Details Unit 580F MAX WeightPhysical Data RETURN-AIR Filters Furnace SectionFreeze Protection Thermostat F OUTDOOR-AIR Inlet ScreensVII. Make Electrical Connections Field Power SupplyField Control Wiring Heat Anticipator SettingsPower Wiring Connections RLA LRA FLA MCA MOCP† Electrical Data Without Convenience OutletElectrical Data With Convenience Outlet Manual Outdoor-Air Damper VIII. Adjust FACTORY-INSTALLED OptionsOptional EconoMi$er+ Hood BOXBracket Iarh OarhIAQ OATEconoMi$er+ Controller Wiring Damper MovementThermostats Return Air Temperature RAT Sensor EconoMi$er+ Field-Installed AccessoriesOutdoor Air Temperature OAT Sensor Provided Supply Air Temperature SAT Sensor ProvidedOutdoor Air Humidity Sensor Indoor Air Quality Voltage SettingRange Resolution Temperature ResistanceEnthalpy Changeover Settings Indoor Air Humidity Sensor Occupied/Unoccupied SwitchPower Exhaust Remote EconoMi$er+ Enable ControlVentilation for People CO2 Sensor ConfigurationFull Occupancy Ventilation RateIX. Adjust EVAPORATOR-FAN Speed Direct-Drive MotorsBelt-Drive Motors Motor Data Fan Rpm at Motor Pulley Settings958 External Static Pressure in. wg Cfm Rpm Bhp Watts 900768 8701073 External Static Pressure in. wg Cfm Rpm Bhp Watts955 1181 970Low Speed 802 370840 432 935 802 370 912 489624 773856 967 579663 757941 Airflow Low Speed High SpeedBhp Watts 900 884762 777 859 458 944 579705 886 517 969 644790 353 896 470 990 599 790 353828 413 866 479944 635 1036 775 1119 924 828 413 930 535 1021 669866 479 964 607 1053 746 905 553 1000 687 1085 831966 771867 986START-UP Unit Preparation IV Internal WiringVI. Refrigerant Service Ports PRE-START-UPIX. Cooling Main BurnersXI. Heating XII. Safety Relief XIII. Ventilation Continuous FANXIV. ECONOMI$ER+ Controller Economizer Motor DS1 DS2 DS3 DS4Input Name Type USE INPUT/OUTPUT Conversion Connection PIN Thermostat InputsStart-Up Mode Sequence Configuration Variables Read and Setup ModesInput/Output Channels Setup Mode Manual Mode Error ModeXV. ECONOMI$ER+ Configuration Ventilation Air and Free Cooling Compressor Configuration and ControlCooling, Units without EconoMi$er+ Demand Ventilation ConfigurationPower Exhaust Configuration XVI. Operating SequenceCooling, Units with EconoMi$er+ Heating, Units without EconoMi$er+Service Cleaning IV. Manual OUTDOOR-AIR Damper III. Blower Belt AdjustmentECONOMI$ER+ Adjustment II. LubricationXVI. Replacement Parts Limit SwitchXIII. HIGH-PRESSURE Switch XIV. Loss of Charge SwitchSuction Line Pressure Psig Suction Line Temperature DEG. CSuction Line Temperature DEG. F Suction Line Pressure KilopascalsTON Unit 60 Hz Charging Chart Burner Section Details Troubleshooting ECONOMI$ER+ Troubleshooting RAM Test Failure Error Code 8 E2 Test FailureUnit Always in Unoccupied Mode II. Unit TroubleshootingHeating Service Analysis LED Error Code Service AnalysisCooling Service Analysis HPS FPTGND GVRAppendix a ECONOMI$ER+ Label Startup ModeAppendix a ECONOMI$ER+ Label Appendix B JOB Specific ECONOMI$ER+ Configuration Settings Index Call for Free Catalog Service TrainingPage III. START-UP Electrical START-UP ChecklistTemperatures Preliminary Information
Related manuals
Manual 80 pages 29.14 Kb Manual 52 pages 44.41 Kb

580F specifications

The Bryant 580F is a highly regarded gas furnace known for its exceptional heating performance and advanced technology. Designed for residential use, this model stands out for its reliability, efficiency, and user-friendly features that cater to modern heating demands.

One of the most notable features of the Bryant 580F is its efficiency rating. With an AFUE (Annual Fuel Utilization Efficiency) rating of up to 95%, this furnace maximizes heat output while minimizing energy consumption. This high level of efficiency not only results in lower utility bills but also reduces the environmental impact—a critical consideration for today’s eco-conscious homeowners.

The Bryant 580F is equipped with a multi-speed blower that ensures consistent airflow and enhances comfort by maintaining even temperatures throughout the home. This technology allows the furnace to adjust its operation based on the heating needs, leading to quieter operation and increased comfort levels.

In terms of construction, the Bryant 580F is built with durable materials that promise longevity and resilience against wear and tear. Its compact design makes installation easier, allowing it to fit into tight spaces without compromising its performance.

One of the standout technologies integrated into the Bryant 580F is its enhanced control system. The furnace works seamlessly with smart thermostats, allowing homeowners to monitor and adjust heating settings from their mobile devices. This feature not only provides convenience but also allows for energy-saving optimizations based on personal schedules and preferences.

Safety is also a primary concern with the Bryant 580F. It includes robust safety features such as a hot surface ignition system that eliminates the need for a standing pilot light, reducing the risk of gas leaks. Additionally, advanced diagnostics help in troubleshooting and maintenance, ensuring that potential issues can be identified and resolved quickly.

In conclusion, the Bryant 580F gas furnace is a remarkable choice for those seeking a blend of efficiency, comfort, and advanced technology. Its high AFUE rating, multi-speed blower, smart control compatibility, and safety features make it a reliable option for homeowners looking to invest in a dependable heating solution. As the demand for energy-efficient heating continues to grow, the Bryant 580F stands out as a model that meets and exceeds expectations in the modern heating landscape.