Bryant 580F installation instructions Install Flue Hood, VI. Install GAS Piping

Page 6

MAXIMUM ALLOWABLE

DIFFERENCE (in.)

A-B

B-C

A-C

0.5

1.0

1.0

Fig. 4 — Unit Leveling Tolerances

HORIZONTAL

DRAIN PLUG

DRAIN PLUG

 

NOTE: Drain plug is shown in factory-installed position.

Fig. 5A — Condensate Drain Pan

NOTE: Trap should be deep enough to offset maximum unit static dif- ference. A 4-in. trap is recommended.

Fig. 5B — External Trap Condensate Drain

Do not install unit in an indoor location. Do not locate unit air inlets near exhaust vents or other sources of contami- nated air.

Be sure that unit is installed such that snow will not block the combustion intake or flue outlet.

Unit may be installed directly on wood flooring or on Class A, B, or C roof-covering material when roof curb is used.

Although unit is weatherproof, guard against water from higher level runoff and overhangs.

Flue vent discharge must have a minimum horizontal clear- ance of 4 ft from electric and gas meters, gas regulators, and gas relief equipment.

Minimum distance between unit and other electrically live parts is 48 inches.

Flue gas can deteriorate building materials. Orient unit such that flue gas will not affect building materials.

Adequate combustion-air space must be provided for proper operation of this equipment. Be sure that installation complies with all local codes and Section 5.3, Air for Combus- tion and Ventilation, NFGC (National Fuel Gas Code), and ANSI (American National Standards Institute) Z223.1, and NFPA (National Fire Protection Association) 54 TIA-54-84-1. In Canada, installation must be in accordance with the CAN1-B149 installation codes for gas burning appliances.

After unit is in position, remove rigging skids and shipping materials.

V. STEP 5 — INSTALL FLUE HOOD

Flue hood is shipped screwed to the basepan beside the burner compartment access panel. Remove from shipping location and using screws provided, install flue hood and screen in location shown in Fig. 7.

VI. STEP 6 — INSTALL GAS PIPING

Unit is equipped for use with type of gas shown on name- plate. Refer to local building codes, or in the absence of local codes, to ANSI Z223.1 entitled National Fuel Gas Code. In Canada, installation must be in accordance with the CAN1.B149.1 and CAN1.B149.2 installation codes for gas burning appliances.

For natural gas applications, gas pressure at unit gas con- nection must not be less than 4 in. wg or greater than

13.0in. wg while unit is operating. On 580F048,060,072 high heat units, the gas pressure at unit gas connection must not be less than 5 in. wg or greater than 13 in. wg while the unit is operating. For propane applications, the gas pressure must not be less than 5 in. wg or greater than 13 in. wg at the unit connection.

Size gas supply piping for 0.5 in. wg maximum pressure drop. Do not use supply pipe smaller than unit gas connec- tion. Support gas piping as shown in the table in Fig. 8. For example, a 3/4-in. gas pipe must have one field-fabricated support beam every 8 ft. Therefore, an 18-ft long gas pipe would have a minimum of 2 support beams, a 48-ft long pipe would have a minimum of 6 support beams.

See Fig. 8 for typical pipe guide and locations of external manual main shutoff valve.

CAUTION: When connecting the gas line to the unit gas valve, the installer MUST use a backup wrench to prevent valve damage.

6

Image 6
Contents Safety Considerations Important Read Before InstallingContents InstallationBase Unit Dimensions 580F036-072 Base Unit Dimensions 580F073 II. Field Fabricate Ductwork III. Install External Trap for CONDEN- Sate DrainAlternate Unit Support IV. RIG and Place UnitPKG. Accy Hole Power Unit Size Accessory CRRFCURB001A01Connector ALT Accessory Drain GAS CRRFCURB002A01Install Flue Hood VI. Install GAS PipingUnit 580F MAX Weight Rigging DetailsPhysical Data OUTDOOR-AIR Inlet Screens Furnace SectionFreeze Protection Thermostat F RETURN-AIR FiltersHeat Anticipator Settings Field Power SupplyField Control Wiring VII. Make Electrical ConnectionsPower Wiring Connections Electrical Data Without Convenience Outlet RLA LRA FLA MCA MOCP†Electrical Data With Convenience Outlet VIII. Adjust FACTORY-INSTALLED Options Manual Outdoor-Air DamperOptional EconoMi$er+ Hood BOXBracket OAT OarhIAQ IarhEconoMi$er+ Controller Wiring Damper MovementThermostats Supply Air Temperature SAT Sensor Provided EconoMi$er+ Field-Installed AccessoriesOutdoor Air Temperature OAT Sensor Provided Return Air Temperature RAT SensorIndoor Air Quality Voltage Setting Outdoor Air Humidity SensorTemperature Resistance Range ResolutionEnthalpy Changeover Settings Remote EconoMi$er+ Enable Control Occupied/Unoccupied SwitchPower Exhaust Indoor Air Humidity SensorVentilation Rate CO2 Sensor ConfigurationFull Occupancy Ventilation for PeopleIX. Adjust EVAPORATOR-FAN Speed Direct-Drive MotorsBelt-Drive Motors Fan Rpm at Motor Pulley Settings Motor Data870 External Static Pressure in. wg Cfm Rpm Bhp Watts 900768 9581181 970 External Static Pressure in. wg Cfm Rpm Bhp Watts955 1073Low Speed 802 370840 432 773 802 370 912 489624 935757 967 579663 856884 Airflow Low Speed High SpeedBhp Watts 900 941762 886 517 969 644 859 458 944 579705 777866 479 790 353828 413 790 353 896 470 990 599905 553 1000 687 1085 831 828 413 930 535 1021 669866 479 964 607 1053 746 944 635 1036 775 1119 924986 771867 966PRE-START-UP IV Internal WiringVI. Refrigerant Service Ports START-UP Unit PreparationIX. Cooling Main BurnersXI. Heating XII. Safety Relief XIII. Ventilation Continuous FANXIV. ECONOMI$ER+ Controller Thermostat Inputs DS1 DS2 DS3 DS4Input Name Type USE INPUT/OUTPUT Conversion Connection PIN Economizer MotorStart-Up Mode Sequence Configuration Variables Read and Setup ModesInput/Output Channels Setup Mode Manual Mode Error ModeXV. ECONOMI$ER+ Configuration Compressor Configuration and Control Ventilation Air and Free CoolingXVI. Operating Sequence Demand Ventilation ConfigurationPower Exhaust Configuration Cooling, Units without EconoMi$er+Heating, Units without EconoMi$er+ Cooling, Units with EconoMi$er+Service Cleaning II. Lubrication III. Blower Belt AdjustmentECONOMI$ER+ Adjustment IV. Manual OUTDOOR-AIR DamperXIV. Loss of Charge Switch Limit SwitchXIII. HIGH-PRESSURE Switch XVI. Replacement PartsSuction Line Pressure Kilopascals Suction Line Temperature DEG. CSuction Line Temperature DEG. F Suction Line Pressure PsigTON Unit 60 Hz Charging Chart Burner Section Details Troubleshooting ECONOMI$ER+ Troubleshooting II. Unit Troubleshooting Error Code 8 E2 Test FailureUnit Always in Unoccupied Mode RAM Test FailureLED Error Code Service Analysis Heating Service AnalysisCooling Service Analysis GVR FPTGND HPSStartup Mode Appendix a ECONOMI$ER+ LabelAppendix a ECONOMI$ER+ Label Appendix B JOB Specific ECONOMI$ER+ Configuration Settings Index Service Training Call for Free CatalogPage Preliminary Information START-UP ChecklistTemperatures III. START-UP Electrical
Related manuals
Manual 80 pages 29.14 Kb Manual 52 pages 44.41 Kb

580F specifications

The Bryant 580F is a highly regarded gas furnace known for its exceptional heating performance and advanced technology. Designed for residential use, this model stands out for its reliability, efficiency, and user-friendly features that cater to modern heating demands.

One of the most notable features of the Bryant 580F is its efficiency rating. With an AFUE (Annual Fuel Utilization Efficiency) rating of up to 95%, this furnace maximizes heat output while minimizing energy consumption. This high level of efficiency not only results in lower utility bills but also reduces the environmental impact—a critical consideration for today’s eco-conscious homeowners.

The Bryant 580F is equipped with a multi-speed blower that ensures consistent airflow and enhances comfort by maintaining even temperatures throughout the home. This technology allows the furnace to adjust its operation based on the heating needs, leading to quieter operation and increased comfort levels.

In terms of construction, the Bryant 580F is built with durable materials that promise longevity and resilience against wear and tear. Its compact design makes installation easier, allowing it to fit into tight spaces without compromising its performance.

One of the standout technologies integrated into the Bryant 580F is its enhanced control system. The furnace works seamlessly with smart thermostats, allowing homeowners to monitor and adjust heating settings from their mobile devices. This feature not only provides convenience but also allows for energy-saving optimizations based on personal schedules and preferences.

Safety is also a primary concern with the Bryant 580F. It includes robust safety features such as a hot surface ignition system that eliminates the need for a standing pilot light, reducing the risk of gas leaks. Additionally, advanced diagnostics help in troubleshooting and maintenance, ensuring that potential issues can be identified and resolved quickly.

In conclusion, the Bryant 580F gas furnace is a remarkable choice for those seeking a blend of efficiency, comfort, and advanced technology. Its high AFUE rating, multi-speed blower, smart control compatibility, and safety features make it a reliable option for homeowners looking to invest in a dependable heating solution. As the demand for energy-efficient heating continues to grow, the Bryant 580F stands out as a model that meets and exceeds expectations in the modern heating landscape.