C. Install the Ceiling Firestop

C. Install the Ceiling Firestop

A ceiling firestop MUST be used between floors and attics.

SLP pipe only - Frame opening 9 in. x 9 in. (229 mm x 229 mm) whenever the vent penetrates a ceiling/floor (see Figure 8.3).

Frame the area with the same sized lumber as used in ceiling/floor joist.

The ceiling firestop may be installed above or below the ceiling joists when installed with a attic insulation shield. It must be under joists between floors that are not insulated. Refer to Figure 8.4.

Secure with three fasteners on each side.

WARNING! Risk of Fire! DO NOT pack insu- lation around the vent. Insulation must be kept back from the pipe to prevent overheating.

 

 

ATTIC ABOVE

 

 

A

 

 

A

 

PIPE

A

 

SLP

9 in. (229 mm)

Figure 8.3

Installing Ceiling Firestop

 

INSTALL ATTIC INSULATION SHIELDS

BEFORE OR AFTER INSTALLATION OF VENT SYSTEM

3 FASTENERS

 

PER SIDE

 

CEILING FIRESTOP

CEILING FIRESTOP

INSTALLED BELOW CEILING

INSTALLED ABOVE CEILING

Figure 8.4 Installing the Attic Shield

 

Heat & Glo • SLR32 • 2269-900 Rev. E • 4/12

35

Image 35
Contents Owner’s Manual NOTICEModel SLR32 •What to do if you smell gasHomeowner Reference Information A. Congratulations3 Maintenance and Service Table of ContentsSafety Alert Key Installer Guide13 Finishing 14 Appliance Setup15 Troubleshooting  = Contains updated informationWARRANTY PERIOD B. Limited Lifetime WarrantyLIMITED LIFETIME WARRANTY WARRANTY COVERAGEThis warranty is void if B. Limited Lifetime Warranty continuedWARRANTY CONDITIONS WARRANTY EXCLUSIONSB. Tempered Glass Specifications D. High Altitude Installations1 Listing and Code Approvals A. Appliance CertificationInstallation of Carbon Monoxide Detectors WARNING! Choking Hazard! Keep glass rock media A. Gas Fireplace Safety2 Operating Instructions User Guide B. Your FireplaceG. Before Lighting Fireplace E. Fixed Glass AssemblyC. Clear Space D. Decorative Doors and FrontsLIGHTING INSTRUCTIONS IPI H. Lighting Instructions IPIFinal inspection by FOR YOUR SAFETY READ BEFORE LIGHTING•Some people may be sensitive to smoke and odors J. Frequently Asked QuestionsI. After Fireplace is Lit Initial Break-inProcedureRemote Control 3 Maintenance and ServiceA. Maintenance Tasks-Homeowner Glass CleaningFirebox B.Maintenance Tasks-QualifiedService TechnicianGasket Seal and Glass Assembly Inspection VentingWALL SWITCH Getting StartedA. Typical Appliance System Installer GuideD. Inspect Appliance and Components B. Design and Installation ConsiderationsC. Tools and Supplies Needed A. Selecting Appliance Location 5 Framing and ClearancesHeat & Glo • SLR32 • 2269-900Rev. E • 4/12 B. Constructing the Appliance ChaseMINIMUM FRAMING DIMENSIONS C. ClearancesFront Side Finishing Detail D. Mantel and Wall ProjectionsCombustible Mantels Non-combustibleMantelsSHEATHING Figure 5.8 Non-CombustibleZone5 IN WALLA. Vent Termination Minimum Clearances 6 Termination LocationsV= VENT TERMINAL X = AIR SUPPLY INLET = AREA WHERE TERMINAL IS NOT PERMITTEDCovered Alcove Applications B. Vent Table Key 7 Vent Information and DiagramsE. Vent Diagrams A. Approved PipeVenting with 1 elbow Top Vent - Horizontal TerminationTop Vent - Horizontal Termination 1. Top Vent - Horizontal Termination - continuedVenting with 2 elbows INSTALLED HORIZONTALLYH2 V2 H1 1. Top Vent - Horizontal Termination - continuedTop Vent - Horizontal Termination Venting with 3 elbowsPILOT HOLES Top Vent - Vertical Termination No ElbowsV1 = 44 ft. Max. 13.4 m Exhaust restrictor InstructionsV1 Minimum Top Vent - Vertical TerminationVenting with 2 elbows SLR32V1 Minimum Venting with 3 elbowsTop Vent - Vertical Termination SLR32V1 MIN Venting with 4 elbowsTop Vent - Vertical Termination V3 H2 H1 V1Clearances to Combustibles Coaxial to Colinear VentingPrior to installing the gas appliance Table•Use separate vent system for this appliance TOP VENT•Vent this appliance directly outside Between ceiling firestops 8 Vent Clearances and FramingA. Pipe Clearances to Combustibles B. Wall Penetration FramingC. Install the Ceiling Firestop Vaulted Ceiling Installation D. Install Attic Insulation ShieldFlat Ceiling Installation A. Preparing Elbow Heat Shield 9 Appliance Preparation•Insulation backing or plastic B. Securing and Leveling the ApplianceWARNING! Risk of Fire! Prevent contact with •Sagging or loose insulationA. Assemble Vent Sections 10 Installing Vent Pipe SLP PipePilot hole B. Assemble Slip SectionsC. Secure The Vent Sections D. Disassemble Vent Sections E. Install Decorative Ceiling ComponentsCAULK F. Install Metal Roof FlashingG. Assemble and Install Storm Collar Figure 10.16 Wall Thimble H. Install Vertical Termination CapI. Install Decorative Wall Components FigureFigure 10.17 Venting through the wall K. Install Horizontal Termination CapAccess Through the Valve Assembly 11 Gas InformationA. Fuel Conversion B. Gas Pressure•Ensure adequate ventilation C. Gas ConnectionD. High Altitude Installations Valve Pressure Taps12 Electrical Information A. Wiring RequirementsB. IntelliFire Ignition System Wiring C. Optional Accessories RequirementsE. Junction Box Installation D. Electrical Service and RepairFinishing Instructions 13 FinishingA. Framing and Finishing Instructions Setting the Fireplace into the FramingHeat & Glo • SLR32 • 2269-900Rev. E • 4/12 Figure 13.3 Finishing DetailsFinishing Around Opening with Gypsum Wallboard PaintingWallboard Joint-CrackPrevention and Repair Finish and Sealing JointsFailure to comply could cause fire B. Mantel and Wall ProjectionsCombustible Mantel Legs Or Wall Projections Extending Past The Face Of The Fireplace0 - 1 inch thickness-OverlapFit Method C. Facing MaterialNon-CombustibleFinish Materials 3/4 IN Non-CombustibleFinish Materials0 Inches to 4 Inches Thick-InsideFit Method Non-CombustibleFinish Material 0-4Inches ThickFigure 13.14 Dimensions of Tonic Decorative Front D. Decorative FrontsTable 1. Dimensions of Tonic Decorative Front Table 1. Dimensions of Martini Decorative FrontD. Accessories 14 Appliance SetupA. Remove Fixed Glass Assembly C. Clean the Appliance• GLASS32-LINER • MEDIA-AMBER • MEDIA-BLACK • MEDIA-CLEAR• MEDIA-COBALT • MEDIA-BK2-GEMS • MEDIA-WH2-GEMS • MEDIA-STONES-2 • SLR32-LOGS • MEDIA-CL2-GEMSRemoving Fixed Glass Assembly F. Fixed Glass AssemblyG. Install the Mesh H. Air Shutter SettingPossible Cause 15 TroubleshootingA. IntelliFire Ignition System SymptomCorrective Action IntelliFire Ignition System - continuedSymptom Possible CauseM K L J I Ø A B E F C D A. Appliance Dimension Diagram16 Reference Materials N R Q S P2-3/4in B. Vent Components Diagrams9 in 12-1/2inSLP90- 90 Elbow B. Vent Components Diagrams continuedEffective Height Length SLP-45- 45 ElbowSLP-TVHW B. Vent Components Diagrams continuedSLK-SNKD SLP-CCS-BKHORIZONTAL TERMINATION CAP SLP-HRC-SS SLP-HRC-ZC-SSDESCRIPTION COAXIAL to COLINEAR VENTINGB. Vent Components Diagrams continued Optional Wire HarnessStocked C. Service Partsat depot SLR32#11 Valve Assembly SLR32at Depot C. Service Partsat Depot SLR32Stocked C. Service PartsNOTICE D. Contact Information