Heat & Glo LifeStyle SLR32 H. Install Vertical Termination Cap, Figure, 16 Wall Thimble

Page 43
H. Install Vertical Termination Cap

H. Install Vertical Termination Cap

Attach the vertical termination cap by sliding the inner collar of the cap into the inner flue of the pipe section while placing the outer collar of the cap over the outer flue of the pipe section.

Secure the cap by driving three self-tapping screws (supplied) through the pilot holes in the outer collar of the cap into the outer flue of the pipe (see Figure 10.15).

TERMINATION CAP

(1 of 3)

STORM

COLLAR

SCREWS

CAULK I. Install Decorative Wall Components

Figure 10.15

I. Install Decorative Wall Components

A decorative wall thimble can be installed on wall through which the vent passes. The decorative wall thimble is used to cover the firestop.

Slide the decorative wall thimble over the last section of horizontal pipe before connecting the termination cap to the pipe.

Once the pipe section and the termination cap have been connected, slide the wall thimble up to the interior wall surface and attach with screws provided. See Figure 10.16.

J.Heat Shield Requirements for Horizontal Termination

WARNING! Risk of Fire! To prevent overheating and fire, heat shields must extend through the entire wall thick- ness.

DO NOT remove the heat shields attached to the wall shield firestop and the horizontal termination cap (shown in Figure 10.17).

Heat shields must overlap 1-1/2 in. (38 mm) mini- mum.

There are two sections of the heat shield. One section is factory-attached to the wall shield firestop. The other section is factory-attached to the cap. See Figure 10.17.

If the wall thickness does not allow the required 1-1/2 in. (38 mm) heat shield overlap when installed, an extended heat shield must be used.

If the wall thickness is less than 4 in./102 mm (DVP) or 4-3/8 in./ 111 mm (SLP), the heat shields on the cap and wall shield firestop must be trimmed. A minimum 1-1/2 in. (38 mm) overlap MUST be maintained.

Use an extended heat shield if the finished wall thickness is greater than 7-1/4 in. (184 mm).

The extended heat shield may need to be cut to length maintaining sufficient length for a 1-1/2 in. (38 mm) overlap between heat shields.

Attach the extended heat shield to either of the existing heat shields using the screws supplied with the extended heat shield. Refer to vent components diagrams in the back of this manual.

Rest the small leg on the extended heat shield on top of the pipe section to properly space it from the pipe section.

Important Notice: Heat shields may not be field constructed.

Figure 10.16 Wall Thimble

Heat & Glo • SLR32 • 2269-900 Rev. E • 4/12

43

Image 43
Contents Owner’s Manual NOTICEModel SLR32 •What to do if you smell gasHomeowner Reference Information A. Congratulations3 Maintenance and Service Table of ContentsSafety Alert Key Installer Guide13 Finishing 14 Appliance Setup15 Troubleshooting  = Contains updated informationWARRANTY PERIOD B. Limited Lifetime WarrantyLIMITED LIFETIME WARRANTY WARRANTY COVERAGEThis warranty is void if B. Limited Lifetime Warranty continuedWARRANTY CONDITIONS WARRANTY EXCLUSIONSB. Tempered Glass Specifications D. High Altitude Installations1 Listing and Code Approvals A. Appliance CertificationInstallation of Carbon Monoxide Detectors WARNING! Choking Hazard! Keep glass rock media A. Gas Fireplace Safety2 Operating Instructions User Guide B. Your FireplaceG. Before Lighting Fireplace E. Fixed Glass AssemblyC. Clear Space D. Decorative Doors and FrontsLIGHTING INSTRUCTIONS IPI H. Lighting Instructions IPIFinal inspection by FOR YOUR SAFETY READ BEFORE LIGHTING•Some people may be sensitive to smoke and odors J. Frequently Asked QuestionsI. After Fireplace is Lit Initial Break-inProcedureRemote Control 3 Maintenance and ServiceA. Maintenance Tasks-Homeowner Glass CleaningFirebox B.Maintenance Tasks-QualifiedService TechnicianGasket Seal and Glass Assembly Inspection VentingWALL SWITCH Getting StartedA. Typical Appliance System Installer GuideC. Tools and Supplies Needed B. Design and Installation ConsiderationsD. Inspect Appliance and Components A. Selecting Appliance Location 5 Framing and ClearancesHeat & Glo • SLR32 • 2269-900Rev. E • 4/12 B. Constructing the Appliance ChaseMINIMUM FRAMING DIMENSIONS C. ClearancesFront Side Finishing Detail D. Mantel and Wall ProjectionsCombustible Mantels Non-combustibleMantelsSHEATHING Figure 5.8 Non-CombustibleZone5 IN WALLA. Vent Termination Minimum Clearances 6 Termination LocationsCovered Alcove Applications = AREA WHERE TERMINAL IS NOT PERMITTEDV= VENT TERMINAL X = AIR SUPPLY INLET B. Vent Table Key 7 Vent Information and DiagramsE. Vent Diagrams A. Approved PipeVenting with 1 elbow Top Vent - Horizontal TerminationTop Vent - Horizontal Termination 1. Top Vent - Horizontal Termination - continuedVenting with 2 elbows INSTALLED HORIZONTALLYH2 V2 H1 1. Top Vent - Horizontal Termination - continuedTop Vent - Horizontal Termination Venting with 3 elbowsPILOT HOLES Top Vent - Vertical Termination No ElbowsV1 = 44 ft. Max. 13.4 m Exhaust restrictor InstructionsV1 Minimum Top Vent - Vertical TerminationVenting with 2 elbows SLR32V1 Minimum Venting with 3 elbowsTop Vent - Vertical Termination SLR32V1 MIN Venting with 4 elbowsTop Vent - Vertical Termination V3 H2 H1 V1Clearances to Combustibles Coaxial to Colinear VentingPrior to installing the gas appliance Table•Vent this appliance directly outside TOP VENT•Use separate vent system for this appliance Between ceiling firestops 8 Vent Clearances and FramingA. Pipe Clearances to Combustibles B. Wall Penetration FramingC. Install the Ceiling Firestop Flat Ceiling Installation D. Install Attic Insulation ShieldVaulted Ceiling Installation A. Preparing Elbow Heat Shield 9 Appliance Preparation•Insulation backing or plastic B. Securing and Leveling the ApplianceWARNING! Risk of Fire! Prevent contact with •Sagging or loose insulationA. Assemble Vent Sections 10 Installing Vent Pipe SLP PipeC. Secure The Vent Sections B. Assemble Slip SectionsPilot hole D. Disassemble Vent Sections E. Install Decorative Ceiling ComponentsG. Assemble and Install Storm Collar F. Install Metal Roof FlashingCAULK Figure 10.16 Wall Thimble H. Install Vertical Termination CapI. Install Decorative Wall Components FigureFigure 10.17 Venting through the wall K. Install Horizontal Termination CapAccess Through the Valve Assembly 11 Gas InformationA. Fuel Conversion B. Gas Pressure•Ensure adequate ventilation C. Gas ConnectionD. High Altitude Installations Valve Pressure Taps12 Electrical Information A. Wiring RequirementsB. IntelliFire Ignition System Wiring C. Optional Accessories RequirementsE. Junction Box Installation D. Electrical Service and RepairFinishing Instructions 13 FinishingA. Framing and Finishing Instructions Setting the Fireplace into the FramingHeat & Glo • SLR32 • 2269-900Rev. E • 4/12 Figure 13.3 Finishing DetailsFinishing Around Opening with Gypsum Wallboard PaintingWallboard Joint-CrackPrevention and Repair Finish and Sealing JointsFailure to comply could cause fire B. Mantel and Wall ProjectionsCombustible Mantel Legs Or Wall Projections Extending Past The Face Of The FireplaceNon-CombustibleFinish Materials C. Facing Material0 - 1 inch thickness-OverlapFit Method 3/4 IN Non-CombustibleFinish Materials0 Inches to 4 Inches Thick-InsideFit Method Non-CombustibleFinish Material 0-4Inches ThickFigure 13.14 Dimensions of Tonic Decorative Front D. Decorative FrontsTable 1. Dimensions of Tonic Decorative Front Table 1. Dimensions of Martini Decorative FrontD. Accessories 14 Appliance SetupA. Remove Fixed Glass Assembly C. Clean the Appliance• GLASS32-LINER • MEDIA-AMBER • MEDIA-BLACK • MEDIA-CLEAR• MEDIA-COBALT • MEDIA-BK2-GEMS • MEDIA-WH2-GEMS • MEDIA-STONES-2 • SLR32-LOGS • MEDIA-CL2-GEMSRemoving Fixed Glass Assembly F. Fixed Glass AssemblyG. Install the Mesh H. Air Shutter SettingPossible Cause 15 TroubleshootingA. IntelliFire Ignition System SymptomCorrective Action IntelliFire Ignition System - continuedSymptom Possible CauseM K L J I Ø A B E F C D A. Appliance Dimension Diagram16 Reference Materials N R Q S P2-3/4in B. Vent Components Diagrams9 in 12-1/2inSLP90- 90 Elbow B. Vent Components Diagrams continuedEffective Height Length SLP-45- 45 ElbowSLP-TVHW B. Vent Components Diagrams continuedSLK-SNKD SLP-CCS-BKHORIZONTAL TERMINATION CAP SLP-HRC-SS SLP-HRC-ZC-SSDESCRIPTION COAXIAL to COLINEAR VENTINGB. Vent Components Diagrams continued Optional Wire HarnessStocked C. Service Partsat depot SLR32#11 Valve Assembly SLR32at Depot C. Service Partsat Depot SLR32Stocked C. Service PartsNOTICE D. Contact Information