Heat & Glo LifeStyle 6000TRI-SP manual Constructing the Fireplace Chase, Locating the Fireplace

Page 11

3Installing the Fireplace

Constructing the Fireplace Chase

A chase is a vertical box-like structure built to enclose the gas fireplace and/or its vent system. Vertical vents that run on the outside of a building may be, but are not required to be, installed inside a chase.

CAUTION: TREATMENT OF FIRESTOP SPACERS AND CONSTRUCTION OF THE CHASE MAY VARY WITH THE TYPE OF BUILDING. THESE INSTRUCTIONS ARE NOT SUBSTITUTES FOR THE REQUIREMENTS OF LOCAL BUILDING CODES. THEREFORE, YOUR LOCAL BUILD- ING CODES MUST BE CHECKED TO DETERMINE THE REQUIREMENTS FOR THESE STEPS.

Factory-built fireplace chases should be constructed in the manner of all outside walls of the home to prevent cold air drafting problems. The chase should not break the outside building envelope in any manner.

This means that the walls, ceiling, base plate and cantile- ver floor of the chase should be insulated. Vapor and air infiltration barriers should be installed in the chase as per regional codes for the rest of the home. Additionally, Heat & Glo recommends that the inside surfaces be sheetrocked and taped for maximum air tightness.

To further prevent drafts, the firestops should be caulked to seal gaps. Gas line holes and other openings should be caulked or stuffed with insulation. If the unit is being in- stalled on a cement slab, we recommend that a layer of plywood be placed underneath to prevent conducting cold up into the room. Be sure to include spark arrestors for woodburning units if they are required.

THE CHASE SHOULD BE CONSTRUCTED SO THATALL CLEARANCES TO THE FIREPLACE ARE MAINTAINED AS SPECIFIED WITHIN THIS INSTALLERS GUIDE.

Step 1. Locating the Fireplace

The following diagram shows space and clearance require- ments for locating a fireplace within a room.

Clearance Requirements

The top, back, and sides of the fireplace are defined by stand-offs. The minimum clearance to a perpendicular wall extending past the face of the fireplace is one inch (25 mm). The back of the fireplace may be recessed 21 1/2 inches (546 mm) into combustible construction.

1” MIN. (25mm)

B

A

ED

C

1/2” MIN. (13mm)

A B C D E

42” 22” 36” 51” 72”

Note* 42” 22” 40” 57” 80”

*If venting with (2) 900 elbows off rear of unit the dimensions C, D, and E, will change.

Figure 2. Fireplace Dimensions, Locations, and Space Requirements

Minimum Clearances

from the Fireplace to Combustible Materials

 

Inches

mm

Glass Front

36

914

Floor

0

0

Rear

1/2

13

Sides

1/2

13

Surround Sides*

0

0

Top

3 1/2

89

Ceiling**

31

787

*See Figure 3.

**The clearance to the ceiling is measured from the top of the unit, excluding the standoffs (see Figure 39).

The distance from the unit to combustible construction is to be measured from the unit outer wrap surface to the combustible construction, NOT from the screw heads that secure the unit together.

Minimum Clearances

from the Vent Pipe to Combustible Materials

 

Inches

mm

Vertical Sections

1

25

Horizontal Sections

 

 

Top

3

75

Bottom

1

25

Sides

1

25

At Wall Firestops

 

 

Top

3

75

Bottom

1

25

Sides

1

25

For minimum clearances, see the direct vent termination clearance diagrams on pages 24 and 25 in this manual.

Heat & Glo • 6000TRI-IPI, 6000TRI-SP385-901 Rev. F • 5/05

11

Image 11
Contents What to do if you smell gas Installers GuideSafety and Warning Information Table of Contents 6000TRI-IPI, 6000TRI-SP Log set assembly6000TRI-SP, 6000TRI-IPI Service Parts List / Liste des pièces de rechange6000TRI-IPI Intermittent Pilot Ignition Valve Assembly6000TRI-SP Standing Pilot Ignition Valve AssemblyCertification Installation CodesHigh Altitude Installations Appliance CertificationANY Such Action MAY Possibly Cause a Fire Hazard Pre-install PreparationIntroducing the Heat & Glo Gas Fireplaces Diagram of the 6000TRI-IPI, 6000TRI-SP Clearance Requirements Constructing the Fireplace ChaseLocating the Fireplace Framing the Fireplace Framing DimensionsDVP90ST Identifying Vent Components Installing the Vent SystemVent System Approvals Tems or Components MAY be UsedMAX .4 M Straight Up Vertical Venting Flue Restrictor InstructionsVertical Venting Chart Venting with One 90 Elbow Venting with ONE 1 90 ElbowVenting with Two 90 Elbows Venting with TWO 2 90 o ElbowsVenting with three 90 elbows Venting with Three 3 90 Elbows+ V 1 FT + H 1 FT Installing Vent Components Continue Adding Vent Components To Install the Heat ShieldInstall Support Brackets 12 Hole and Vent Pipe Attic Firestop Vent TerminationVent Termination Minimum Clearances Leveling and Securing of a Fireplace Positioning, Leveling, Securing the FireplaceProper Positioning Intermittent Pilot Ignition IPI System Installing the Optional Heat-Zone KitVice Must be Wired Directly to the FIRE- Place Junction BOX Gas Control SystemsPressure Natural Gas Propane Gas Supply LineGas Pressure Requirements Intermittent Pilot Ignition IPI Wiring Diagram Wiring the Fireplace Sealant Material Hearth Extensions FinishingInstalling Trim, Logs, and Ember Material Before Lighting the Fireplace Double-check for faulty componentsAir Shutter Setting Important Turn OFF the GAS Before Servicing Your Fireplace After the InstallationFireplace Maintenance Lighting the Fireplace