Heat & Glo LifeStyle 6000TRI-SP, 6000TRI-IPI manual Hole and Vent Pipe

Page 23

5. Install Firestops

For Horizontal Runs - Firestops are REQUIRED on both sides of a combustible wall through which the vent passes.

NOTE: Model DVP-TRAP does not need an exterior firestop on an exterior combustible wall.

To install firestops for horizontal runs that pass through either interior or exterior walls:

Cut a 10-inch by 12-inch (254mm x 305mm) hole through the wall.

NOTE: The center of the hole is one (1) inch (25.4mm) above the center of the horizontal vent pipe.

Position the firestops on both sides of the hole previ- ously cut and secure the firestops with nails or screws.

The heat shields of the firestops MUST BE placed to- wards the top of the hole.

Continue the vent run through the firestops.

NOTE: There must be NO INSULATION or other combustibles inside the framed firestop opening.

10"

INTERIOR

WALL SHIELD

12"

Figure 23. 10" x 12" Hole and Vent Pipe

HEAT SHIELD

TRIM HEAT SHIELD IF TOO LONG, ADD TO SHIELD IF TOO SHORT

EXTERIOR

FIRESTOP

INTERIOR

FIRESTOP

For Vertical Runs - One ceiling firestop is REQUIRED at the hole in each ceiling through which the vent passes.

To install firestops for vertical runs that pass through ceilings:

Position a plumb bob directly over the center of the verti- cal vent component.

Mark the ceiling to establish the centerpoint of the vent.

Drill a hole or drive a nail through this centerpoint.

Check the floor above for any obstructions, such as wir- ing or plumbing runs.

Reposition the fireplace and vent system, if necessary, to accommodate the ceiling joists and/or obstructions.

Cut an 10-inch X 10-inch (254mm X 254mm) hole through the ceiling, using the centerpoint previously marked.

Frame the hole with framing lumber the same size as the ceiling joists.

10" (254mm)

10" (254mm)

 

 

CHIMNEY

 

HOLE

NEW

EXISTING CEILING

JOISTS

FRAMING

 

MEMBERS

 

CEILING

 

Figure 25. 10" x 10" Hole & New Framing Members

Figure 24. Heat Shield, Interior & Exterior Firestops

Heat & Glo • 6000TRI-IPI, 6000TRI-SP385-901 Rev. F • 5/05

23

Image 23
Contents What to do if you smell gas Installers GuideSafety and Warning Information Table of Contents 6000TRI-IPI, 6000TRI-SP Log set assembly6000TRI-SP, 6000TRI-IPI Service Parts List / Liste des pièces de rechange6000TRI-IPI Intermittent Pilot Ignition Valve Assembly6000TRI-SP Standing Pilot Ignition Valve AssemblyCertification Installation CodesHigh Altitude Installations Appliance CertificationANY Such Action MAY Possibly Cause a Fire Hazard Pre-install PreparationIntroducing the Heat & Glo Gas Fireplaces Diagram of the 6000TRI-IPI, 6000TRI-SP Clearance Requirements Constructing the Fireplace ChaseLocating the Fireplace Framing the Fireplace Framing DimensionsDVP90ST Identifying Vent Components Installing the Vent SystemVent System Approvals Tems or Components MAY be UsedMAX .4 M Straight Up Vertical Venting Flue Restrictor InstructionsVertical Venting Chart Venting with One 90 Elbow Venting with ONE 1 90 ElbowVenting with Two 90 Elbows Venting with TWO 2 90 o ElbowsVenting with three 90 elbows Venting with Three 3 90 Elbows+ V 1 FT + H 1 FT Installing Vent Components Continue Adding Vent Components To Install the Heat ShieldInstall Support Brackets 12 Hole and Vent Pipe Attic Firestop Vent TerminationVent Termination Minimum Clearances Leveling and Securing of a Fireplace Positioning, Leveling, Securing the FireplaceProper Positioning Intermittent Pilot Ignition IPI System Installing the Optional Heat-Zone KitVice Must be Wired Directly to the FIRE- Place Junction BOX Gas Control SystemsPressure Natural Gas Propane Gas Supply LineGas Pressure Requirements Intermittent Pilot Ignition IPI Wiring Diagram Wiring the Fireplace Sealant Material Hearth Extensions FinishingInstalling Trim, Logs, and Ember Material Before Lighting the Fireplace Double-check for faulty componentsAir Shutter Setting Important Turn OFF the GAS Before Servicing Your Fireplace After the InstallationFireplace Maintenance Lighting the Fireplace