Desa FPVF33PRA, VYGF33NRC installation manual Test Pressures Equal To or Less Than Psig 3.5 kPa

Page 16

Installation

Continued

2.

Cap off open end of gas pipe where equipment

 

shutoff valve was connected.

3.

Pressurize supply piping system by either

 

opening propane/LP supply tank valve for

 

propane/LP gas or opening main gas valve

 

located on or near gas meter for natural gas

 

or using compressed air.

Equipment

Open

Shutoff

 

Valve

 

 

Closed

Figure 25 - Equipment Shutoff Valve

4.

Check all joints of gas supply piping system.

 

Apply noncorrosive leak detection fluid to all

 

joints. Bubbles forming show a leak.

5.

Correct all leaks at once.

6.

Reconnect fireplace and equipment shutoff

 

valve to gas supply. Check reconnected fittings

 

for leaks.

Test Pressures Equal To or Less Than

1/2 PSIG (3.5 kPa)

1. Close equipment shutoff valve (see Figure 25).

Gas Control Valve

Equipment Shutoff Valve

Gas Meter

2. Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas or opening main gas valve located on or near gas meter for natural gas or using compressed air.

3. Check all joints from gas meter to equipment shutoff valve for natural gas or propane/LP sup- ply to equipment shutoff valve for propane/LP (see Figures 26 or 27). Apply noncorrosive leak detection fluid to all joints. Bubbles forming show a leak.

4. Correct all leaks at once.

Pressure Testing Fireplace Gas

Connections

1. Open equipment shutoff valve (see Figure 25).

2. Open main gas valve located on or near gas meter for natural gas or open propane/LP supply tank valve.

3. Make sure control knob of fireplace is in the OFF position.

4. Check all joints from equipment shutoff valve to gas control valve (see Figures 26 or 27). Apply noncorrosive leak detection fluid to all joints. Bubbles forming show a leak.

5. Correct all leaks at once.

6. Light fireplace (see Operating Fireplace, page

19. Check all other internal joints for leaks.

7. Turn off fireplace (see To Turn Off Gas to Appliance, page 21).

Figure 26 - Checking Gas Joints for

Natural Gas

Equipment Shutoff Valve

Propane/LP

Supply Tank

Gas Control Valve

Figure 27 - Checking Gas Joints for

Propane/LP Gas

16

www.desatech.com

113109-01C

Image 16
Contents VYGF33PRC, VYGF33NRC, FPVF33PRA millivolt FPVF33NRA MillivoltRemote-Ready Gas Fireplace Systems Patent PendingTable of Contents Safety InformationSafety Information Troubleshooting, Product IdentificationProduct Features Local CodesUnpacking Air For Combustion VentilationProviding Adequate Ventilation Determining FRESH-AIR Flow for Heater LocationUnusually Tight Construction Confined and Unconfined SpaceVentilation Air From Inside Building Ventilation AIRVentilation Air From Outdoors Installation Installing HoodCheck GAS Type Electrical HookupInstallation Clearances Repeat steps 1 through 6 for other sideConventional Fireplace Installation Placing Hearth Base Accessory Against WallChecking Gas Connections, Models VYGF33PRB and VYGF33NRBConnecting Duplex Outlet Models FPVF33PRA and FPVF33NRAMantel Clearances for Built-In Installation Installing Gas Piping to Fireplace LocationInstallation Items Needed Connecting Fireplace to GAS Supply Accessories,Natural Gas From Gas Meter 5 W.C.** to Propane/LPChecking Gas Connections Checking GAS ConnectionsNatural Gas Pressure Testing Fireplace Gas Connections Test Pressures Equal To or Less Than Psig 3.5 kPaInstalling Logs Vygf Models OnlyInstalling Remote Receiver Unit Fpvf Models OnlyInstalling 9-Volt Batteries For Your Safety Read Before LightingInstalling 9-Volt Battery in Receiver Installing 9-Volt Battery in Hand-Held Remote Control UnitOperating Fireplace Lighting Instructions MANUAL Lighting Procedure To Turn OFF GAS To ApplianceOptional Hand-Held Remote OperationThermostat Series Model HRC200 Optional Blower OperationInspecting Burner Pilot Flame PatternBurner Flame Pattern Burner Primary AIR HolesBurner Injector Holder and Pilot Air Inlet Hole Cleaning MaintenanceLogs Observed Problem Possible Cause Remedy TroubleshootingIng and Maintenance, Maintenance, Diagram,See Cleaning and Mainte On windows Tilation air See Checking Gas Connec Gas leak. See WarningStalling Logs, Wiring Diagram SpecificationsReplacement Parts Technical ServiceIllustrated Parts Breakdown Models VYGF33PRC and VYGF33NRC ShownParts List Models FPVF33PRA and FPVF33NRA KEY Description Firebox Models VYGF33PRC and VYGF33NRC Parts List Firebox Models FPVF33PRA and FPVF33NRA 101357-01 Accessories Wall Cabinet Mantel and Base Accessory with FireplacePerimeter Trim Not Shown Keep this Warranty Warranty InformationLimited Warranty VENT-FREE GAS Fireplace