Enviro DV36 owner manual Vent restrictor is located in the center

Page 22

Initial Installation

QUALIFIED INSTALLERS ONLY

VENT CONFIGURATIONS AND RESTRICTOR SETTINGS:

Figures 23 shows the range of venting options, it shows possible vent configurations if the unit is top vented, for vertical and horizontal terminations, any layout that remains within the shaded area is acceptable. Having the fewest number of elbows is ideal, as they tend to disrupt air movement. Using 45˚ elbows is preferable to using 90˚ elbows. Also, a shorter vent system will perform better than a longer one.

The vent restrictor controls the amount of air moving through the vent pipe. Longer vertical vent lengths necessitate greater restriction; position 1 is open and position 5 is maximum restriction. Figure 31 shows the vent restrictor position required,

NOTE: The total length of the vent pipes can

relative to the length of vent pipe. The

not exceed 32 feet (15.12 m). Any combination

vent restrictor is located in the center of

of rise and run can be used as long as it lays

the fireplace, above the glass. Figure 32

within the shaded area (a total of three (3) 90°

shows the vent restrictor dial and the holes

elbows or six (6) 45° elbows can be used).

In addition to what is shown, if a 90°

that indicate the different levels. To avoid

elbow is used in the horizontal plane,

injury, it is best to make this adjustment

3 feet (91.4 cm) must be subtracted

when the fireplace is cool or use welder’s

from the allowable horizontal run

(for each 45° elbow, 11⁄2 feet

gloves or oven mitts.

must be subtracted from the

Note: 0,0 in Figure 31 represents a 90˚

allowable horizontal run).

 

bend directly off the outlet of the unit, 413⁄4

 

inches (106 cm) from floor, in all horizontal

 

instances except when using Selkirk and

 

having less than a 4 feet (1.22 m) rise

 

and 8 feet (2.44 m) horizontal offset. In

 

this case, a 1 foot (30.5 cm) rise must be

 

added below the 90˚ bend.

 

Note for rear vented: At 293⁄8 inches (75

 

cm) up, the maximum horizontal rear exit

 

vent length is 17 inches (43 cm) with a 45°

 

elbow (see Figure 17).

Figure 31. Possible Vent Configurations for Top Vented; Vertical Figure 32. Possible Vent Restrictor Positions. and Horizontal Terminations.

22

Image 22
Contents For Your Safety R E C T V E N T F I R E P L a C ESafety Precautions GeneralTable of Contents Vented GAS Fireplace Heater DV36 NG/LPG Codes And ApprovalsThis Enviro DV36 Fireplace Specifications Installation OptionsFor Your Safety Read Before Operating InstructionsBlue, the fireplace is getting too much To Turn GAS Fireplace OFF Component Sound & ReasonMaintenance And Service Never Operate Fireplace with the glass Removed Bottom latches for glassKit Parts List Completely cooled downConversion Kit Installation Removing valve ScrewRing on valve screw Initial Installation Qualified Installers onlyDo not interfere with the structural integrity of the walls Mantel Clearances Vent Termination Restrictions Installation Instructions KIT Components Installation of Fireplace Horizontal Vent Kit Manufacturer Trade Name Nominal Sizes4DSC Two 2 piece wall Vent restrictor is located in the center Being Attached to Wood Assemble Vertical Vent TerminationRoof Pitch Minimum Height H Feet Meters Use of Wall Straps Installation of Electrical Wiring for the Optional FAN KIT GAS Line Connection To Test Valve PressuresSecondary Installation Empty firebox with grate and locator pinsThird Stage Log Set Installation Never operate the fireplace with the glass door removed Complete log set-up with embersTurn off the gas control knob and allow the unit to cool Back Panel In PlaceKit Contents Installation of Kit Hook Fan Tabs Over Grommets at Unit BackTrouble Shooting Problem Possible Cause SolutionParts List Reference Part Description Part NumberParts List Options Parts Diagram To the Dealer WarrantyTo the Distributor Installation Data Sheet