Initial Installation
QUALIFIED INSTALLERS ONLY
Even though the DV36 can be installed at floor level without a hearth, there are a few options with raised fireplaces: raised with a floor level hearth (Figures 19), raised with a raised hearth (Figures 20), or raised with no hearth (Figures 21). If the fireplace is raised, it cannot be placed within 37 inches (1.04 m) of the ceiling. When installing a raised fireplace, it is imperative that the support stand is strong enough to hold the weight of the fireplace and venting.
Figure 21. Raised Fireplace with no Hearth
MANTEL CLEARANCES:
It is not necessary to install a mantel, but if one is desired it is important to follow the guidelines. Note: Louvers have different mantel clearances than when fascia or insets are installed.
Table 3: Mantel clearances.
  | Louvers Only  | Fascia or Insets  | 
  | 
  | 
  | 
Top of unit to horizontal framing  | 3” (7.6 cm)  | 3” (7.6 cm)  | 
  | 
  | 
  | 
Top of unit to bottom of 3” (7.6 cm) mantel  | 
  | 12” (30.5 cm)  | 
  | 
  | 
  | 
Top of unit to bottom of 31⁄2” (8.9 cm) mantel  | 8” (20.3 cm  | 
  | 
  | 
  | 
  | 
Top of unit to bottom of 10” (254 mm) mantel  | 10” (25.4 cm  | 14” (35.6 cm)  | 
  | 
  | 
  | 
Top of unit to bottom of 3⁄4” (19 mm) facing board  | 6” (15.2 cm)  | 6” (15.2 cm)  | 
  | 
  | 
  | 
Combustible board
3"
(76mm)
Top of unit
Combustible
front face
Figure 22. Combustible Shelf Clearance.
A shelf may be installed above the unit. We recommend that no heat sensitive items or components be placed on the shelf (see Figure 22).
10" (254mm) mantle  | 
  | 
3” (76mm) mantle  | 
  | 
3/4" (19mm) facing board  | 14"  | 
  | (356mm)  | 
  | 12"  | 
  | (305mm)  | 
3"  | 6"  | 
(76mm)  | |
  | (152mm)  | 
Top of unit  | 
  | 
  | Combustible front face  | 
Figure 23. Combustible Mantel Clearances for Fascia or | |
Insets.  | |
16