Regency U37-LP PROPANE, U37-NG NATURAL GAS General, Converting a Factory Built Metal Chimney

Page 14

INSTALLATION

CONVERTING A

CLASS-A METAL

CHIMNEY OR

MASONRY CHIMNEY TO A DIRECT VENT SYSTEM

General

There are two different types of direct vent conversion systems listed below. Follow the appropriate directions for your installation.

A)Through an existing factory built metal chim- ney going through the ceiling: A typical conversion of this type is shown in diagram

1.The concept of direct vent conversion is to connect an adaptor to an Underwriters Laboratories (UL) listed 4 inch diameter aluminum flex pipe which is then passed down through the center of the existing metal chimney system. Three sizes of Top Adaptors are available from Simpson Dura- Vent. The Retro Connector (909B) is at- tached to the bottom of the flex pipe. The Top Adaptor and the Retro Connector are at- tached to the existing chimney with sheet metal screws. The appliance is then con- nected to the chimney with appropriate black direct vent pipe and an adjustable length section.

B)Through the wall of an existing masonry chimney: A typical conversion of an exist- ing masonry chimney is shown in Diagram

6.A Top Adaptor (985K) and Flashing are used at the top of the masonry chimney. The

4inch aluminum liner is connected to the adaptor and is passed down the chimney and out through the masonry wall and attached to the Retro Connector (909B). The Retro Connector is attached to the masonry wall and then connected to the direct vent pipe leading to the appliance.

Prior to installation and connection of the vent system to a factory-built or masonry chimney, the chimney must be inspected and thoroughly cleaned by a qualified service person, such as a certified chim- ney sweep or home inspection service.

The direct vent system must not be con- nected to a damaged factory-built or ma- sonry chimney.

For factory built, zero clearance, and ma- sonry chimneys cleanout doors and caps or plugs for cleanout tee fittings and ash dumps shall be secured in place and sealed before installing a Direct Vent sys- tem within the chimney.

If the appliance shuts off during opera- tion, contact a qualified service person to determine if a negative pressure and/or leaky chimney condition exists. Do not operate the appliance until the problem is corrected.

Approved for US Installations Only

The use of an existing chimney as an air intake is not covered under the ANSI Z21.88b-2003/CSA 2.33b-2003 test meth- ods and the resulting ITS/WHI product certification. The code Authority Having Jurisdiction must be consulted prior to proceeding with this installation method.

Converting a Factory Built Metal

Chimney

1)Remove the existing chimney cap.

2)Measure the distance from the top end of the chimney to the bottom of the ceiling support box, add 3" (76mm) to this meas- urement, and cut a section of the 4" flex pipe to that length (the flex should already be extended to its nominal length).

Diagram 1

3) Connect the end of the flex pipe section to the underside of the Top Adaptor us- ing 3 sheet metal screws.

Diagram 2.

Diagram 2

4)Pass the flex pipe down through the center of the chimney system, and center the adaptor on the top of the chimney pipe. Drill four 1/8" diameter holes through the adap- tor and into the chimney top. Insure that you are in fact, drilling into the metal on the chimney. Twist-lock the Termination Cap

(Part# 980 or 991) onto the Adaptor. (Dia- gram 3 and 4).

Diagram 3

Diagram 4

5)Pull the flex pipe down through the ceiling support box, until it protrudes approximate- ly 3" (76mm). Connect the flex pipe to the Retro Connector by slipping it into the

4-3/4" diameter sleeve on the top side of the Connector. Use 3 sheet metal screws to assemble these two parts.

6)Push the flex pipe back up into the ceiling support box, center the Retro Connector, and attach it to the support box, or decora- tive sleeve for double wall solid packed pipe, with the sheet metal screws (sup- plied). The holes in the Retro Connector are pre-punched. Diagram 5.

Diagram 5

7)The connection between the appliance and the Retro Connector may be completed with sections of black direct vent pipe, together with an adjustable length.

14

U37 Regency ULTIMATE Rear Vent Direct Vent Freestanding Gas Heater

Image 14
Contents Installation Manual Regency To the New OwnerTable of Contents Dimensions de l’orifice Safety LabelCopy of Safety Label for U37 Serial No./No de serie 221General Safety Information InstallationSpecifications Save These InstructionsManufactured Mobile Home Additional Requirements Checklist Combustibles Locating Your Ultimate GAS StoveClearances to Combustion and Ventilation AIRAir supply outlet Planning Your Venting Installation Venting Installation PrecautionsSafety Precautions for Installer See page 7 for Exterior Vent Termination requirementsRigid Pipe Venting Components List 4DT-AJBVent Restrictor Position Straight Vertical TerminationsOffset to Vertical Terminations Alternate Snorkel Termination Cap Horizontal InstallationsOptional Components Snorkel TerminationsHint Apply sealant to female end Alternate Approved Caps Vertical Termination with CO-LINEAR Flex SystemRequired Parts Description General Converting a Factory Built Metal ChimneyConverting a Masonry Chimney Conversion Kit from Natural Gas to Propane GAS Connection Aeration AdjustmentLOG SET Installation High ElevationA02-65 GAS Pipe Pressure Testing Valve DescriptionFinal Check Optional RemoteControl Wiring Diagram Operating Instructions Copy of the Lighting Plate Instructions Temperatures keep children, clothingClean. See installation Maintenance Installing Glass Latch AdjustmentGlass Replacement Never operate your unit with bro- ken glassBefore removing the valve FAN MaintenanceRemoving Valve To remove fanMaintenance Parts List U37 Main AssemblyU37 Burner & LOG Assembly U37 Door Assemblies Warranty ConditionsInstaller Please complete the following information