Before Installing Boiler CONTINUED
Provide air for combustion and ventilation:
Adequate combustion and ventilation air:
•Assures proper combustion.
•Reduces risk of severe personal injury or death from possible flue gas leakage and carbon
monoxide emissions.
Do not install exhaust fan in boiler room.
Older buildings with
New construction or remodeled buildings are most often built tighter. Windows and doors are
Follow state, provincial or local codes when sizing adequate combustion and ventilation air openings. In absence of codes, use the following guidelines when boiler is in a confined room (defined by NFPA 31 as less than 7200 cubic feet per 1 GPH input of all appliances in area. A room 8 ft. high x 33.5 ft. x
33.5 ft. is 7200 cu. ft.):
Provide two permanent openings — one within 12 inches of ceiling, one within 12 inches of floor. Minimum height or length dimension of each rectangular opening should be at least 3 inches.
When inside air is used — each opening must freely connect with areas having adequate infiltration from outside. Each opening should be at least 140 sq. in. per 1 GPH input (1 sq. in. per 1000 Btu input) of all
When outside air is used — connect each opening directly or by ducts to the outdoors or to crawl or attic space that freely connects with outdoors. Size per below:
•Through outside wall or vertical ducts — at least 35 sq. in. per 1 GPH input (1 sq. in. per 4000 Btu input) of all fuel burning appliances plus requirements for any equipment that can pull air from room (including clothes dryer
and fireplace).
•Through horizontal ducts — at least 70 sq. in. per 1 GPH boiler input (1 sq. in. per 2000 Btu input) of all
and fireplace).
•Where ducts are used, they should have same
—Wood louvers, which provide
—Metal louvers or grilles, which provide
Lock louvers in open position or interlock with equipment to prove open before boiler operation.
Lay a foundation, if needed:
Boiler may be installed on
For residential garage installation, install boiler so burner is at least 18 inches above floor to avoid contact with gasoline fumes.
A level concrete or masonry foundation is required when:
•Floor could possibly become flooded.
•
Solid concrete blocks can be used to create a pad.
BOILER FOUNDATION SIZE TABLE
|
|
| MIN. |
BOILER | LENGTH | WIDTH | HEIGHT |
MODEL | INCHES | INCHES | INCHES |
17 | 22 | 2 | |
20 | 22 | 2 | |
23 | 22 | 2 | |
26 | 22 | 2 | |
29 | 22 | 2 | |
32 | 22 | 2 | |
35 | 22 | 2 | |
|
|
|
|
Go to page 6 to install boiler
Go to page 7 to install boiler
5