I8 Water Cooker Computer Service
Pitco P/N PP11375
4.7.3Low Dead Band Adjustment:
This setting adjusts the vat temperature limit below the set temperature, where the heat demand output will be ON to apply heat to the vat. At vat temperatures below this value, heat will be applied to the vat. For example if the set temperature is 180°F, and the Low Dead Band value is 3, then at vat temperatures below 177°F, heat will be applied to the vat. The value range of this setting is 1 – 9 degrees
With the control display showing [MORE ], press product key 3. The display will now show [DB LO x], where x is the current Low Dead Band value. Enter the new value using product keys
3
4.7.4High Dead Band Adjustment:
This setting adjusts the vat temperature limit above the set temperature, where the heat demand output will be OFF. At vat temperatures equal to or greater than this value, the heat demand output will be OFF. For example if the set temperature is 180°F, and the High Dead Band value is 1, then at vat temperatures at or above 181°F, heat will not be applied to the vat. A setting of zero for this value will force the heat control output OFF when the vat temperature equals the set temperature. The value range of this setting is 0 – 9 degrees.
With the control display showing [MORE ], press product key 4. The display will now show [DB HI x], where x is the current High Dead Band value. Enter the new value using product keys
4 |
4.7.5 Control Temperature Average Setting:
This setting adjusts the number of times(per second) the vat temperature readings are averaged in the heat control process of the computer. The default value for this setting is 6. The value range of this setting is
With the control display showing [MORE ], press product key 5. The display will |
|
|
| 5 |
| ||||
show [AVER C x], where x is the current control temperature average setting. |
|
|
|
|
|
|
|
| |
Enter the new value using product keys |
|
|
| |
|
| |||
setting. The display will now show [MORE ]. Continue on to the remaining more |
|
| ||
|
| |||
service menu options below, or press the program key three times to return to normal |
| |||
operation(display shows either [READY], [ACT xxx’F], or [FILLING ]). |
|
4.7.6 Display Temperature Average Setting:
This option adjusts the number of times(per second) the vat temperature readings are averaged each second for displaying on the control display. The default value for this setting is 12. The value range for this setting is 7 – 32.
With the control display showing [MORE ], press product key 6. The display will show [AVER Dxx], where xx is the current display temperature average setting. Enter the new value using product keys
6
12 |