ELECTRICAL
Figure 6.3: Wiring and Connection Diagram – Intermittent Ignition
2. Intermittent Ignition (see Figure 6.3 above)
a.The vent damper is continuously powered. On a call for heat, limit relay R is energized, which energizes:
●the circulator (when used) through contact R1, and
●the vent damper operator through contact R2, provided that the
The damper operator opens the vent damper.
b.Once the damper is proven open, the ignition circuit within the gas valve energizes, provided that all of the following conditions are met:
●the blocked vent switch is closed, and
●the flame rollout switch is closed.
c.When the call for heat ends:
●Limit relay R
●The circulator shuts down.
●The gas valve
●The vent damper closes.
d.If temperature exceeds limit setting, main burners shut off and circulator continues to operate.