PB Heat MIH manual Problem Possible Causes Corrective Actions

Page 31

TROUBLESHOOTING

Table 8.1: Boiler Troubleshooting Guide

PROBLEM

POSSIBLE CAUSES

CORRECTIVE ACTIONS

Burners not functioning.

1.

No power.

1.

Check line voltage wiring and fuses.

 

2.

Limit (Aquastat) not working.

2.

Check wiring and contacts, relay, temperature

 

 

 

 

setting. Clean and adjust as necessary.

 

3.

Flame rollout switch open.

3.

Replace switch. Locate cause and correct.

 

4.

Blocked vent switch open.

4.

Reset blocked vent switch. Locate cause and correct.

 

5.

Gas off at boiler gas valve.

5.

Start boiler using Lighting/Operating

 

 

 

 

Instructions.

 

6.

Gas off external to boiler.

6.

Check any gas valves in the line.

 

7.

Plugged orifice spuds.

7.

Check, clean and re-install.

 

8.

Defective gas valve.

8.

Use Figure 8.1 to troubleshoot intermittent

 

 

 

 

ignition gas valve. Replace if necessary.

 

9.

Improper wiring.

9.

Check and correct in accordance with wiring

 

 

 

 

diagrams in Section 6.

 

10.

Vent damper malfunctioning.

10.

Refer to vent damper manufacturer’s instructions.

 

 

 

 

Replace if necessary.

 

 

 

 

 

Burners will not shut

1.

Defective gas valve.

1.

Use Figure 8.1 to troubleshoot intermittent

down.

 

 

 

ignition gas valve. Replace if necessary.

 

2.

Short circuit.

2.

Check and correct wiring.

 

 

 

 

 

Flashback or burning

1.

Manifold gas pressure too low.

1.

Adjust to proper pressure.

at orifice spuds.

2.

Improperly sized/drilled orifice spuds.

2.

Install correct spuds.

 

 

3.

Leaking gas valve.

3.

Replace valve.

 

4.

Burrs on orifice.

4.

Remove burrs.

 

5.

Low supply gas pressure.

5.

Contact gas supplier if natural gas. Adjust

 

 

 

 

regulator if LP gas.

 

6.

Excessive downdraft or draft problems in

6.

Check air supply, ventilation and venting system.

 

 

boiler room.

 

 

 

 

 

 

 

Delayed ignition.

1.

Insufficient pilot flame.

1.

Increase pilot gas flow.

 

2.

Pilot burner/orifice clogged.

2.

Clean pilot burner and orifice.

 

3.

Overfiring.

3.

Reduce rate to input on rating label.

 

4.

Misaligned burners or pilot.

4.

Realign burners or pilot.

 

5.

Draft problem in boiler room.

5.

Check air supply, ventilation and venting

 

 

 

 

system.

 

 

 

 

 

Excessive condensation in

1.

Underfiring.

1.

Increase rate to input on rating label.

vent.

2.

Limit (Aquastat) set too low.

2.

Reset aquastat to higher setting.

 

 

3.

Vent pipe too long.

3.

Reposition boiler to reduce length.

 

4.

Inadequate chimney or venting system.

4.

Check chimney and venting recommendations.

 

 

 

 

 

Boiler not heating

1.

Underfiring.

1.

Increase rate to input on rating label.

properly.

2.

Limit set too low.

2.

Reset aquastat to higher setting.

 

 

3.

Air in system.

3.

Vent air from all points in system.

 

4.

Circulator malfunctioning.

4.

Check circulator, replace if necessary.

 

5.

Circulation system clogged.

5.

Shut down and cool boiler, drain and flush

 

 

 

 

system.

 

6.

Incorrect thermostat heat anticipator setting.

6.

Adjust heat anticipator.

 

 

 

 

 

Fumes or gas odors

1.

Leaks in gas piping or fittings.

1.

Locate and repair or replace.

 

2.

Leaks in gas service line or meter.

2.

Shut down boiler and notify gas provider.

 

3.

Obstructed chimney.

3.

Check, repair and/or clean chimney.

 

4.

Obstructed flueways or vent.

4.

Clean flueways or vent and remove obstructions.

 

5.

Undersized chimney or vent, high draft loss

5.

Check National Fuel Gas Code and vent

 

 

in vent.

 

manufacturer’s recommendations.

 

6.

Draft problem in boiler room.

6.

Check air supply, ventilation and venting system.

 

7.

Overfiring.

7.

Reduce rate to input on rating label.

 

8.

Vent damper malfunctioning.

8.

Refer to vent damper manufacturer’s instructions.

 

 

 

 

Replace if necessary.

 

 

 

 

 

29

Image 31
Contents Series MI/MIH Table of Contents Installation Sequence Using this ManualSpecial Attention Boxes AIR for Combustion and Ventilation PreinstallationAccessibility Clearances Clearance from Combustible ConstructionAir Openings All Air from Indoors on Different Floors Air Openings All Air from Outdoors through Vertical Ducts Planning the Layout Installation SurveyBoiler SET-UP Boiler Supply and Return Water Piping and ControlsParallel Hook-Up with Water Chiller Safety Relief ValveZone Piping with Zone Valves Piping for Zoned SystemsINDIRECT-FIRED Water Heater Expansion TankFreeze Protection Venting Vent Damper Installation GeneralIntegral Draft Hood Venting with Vent Damper in Vertical Position Vent Piping and ChimneySeal any unused openings in the common venting system Boiler Removal from Common Venting SystemGas Connection to Boiler GAS PipingMIH Boiler Natural Gas Zoned System Wiring Wiring ControlsElectrical Sequence of Operation Wiring and Connection Diagram Intermittent Ignition Intermittent Ignition System Operating Sequence Zone Wiring with Zone Valves Completing the Installation START-UP ProceduresValve Tapping and Adjustment Screw Locations Operating Instructions For Your Safety Read Before Lighting Adjustment of Pilot GAS Flow Adjustment of GAS Pressure RegulatorControl Descriptions Checking Burner Input CHECK-OUT ProcedureSTART-UP Procedures Troubleshooting Guides TroubleshootingProblem Possible Causes Corrective Actions Intermittent Ignition System Troubleshooting Sequence Maintenance Monthly with Boiler in USE GeneralDaily with Boiler in USE Weekly with Boiler in USEStanding Pilot and Main Burner Flame Annually Before Start of Heating SeasonSeries MI/MIH Boiler Dimensions Boiler Dimensions & RatingsRepair Parts Series MI/MIH GAS Boiler Repair Parts2Manifold Manifold/Gas Train MI Standing Pilot 3b Gas Valve and Pilot Intermittent 4Block/Draft Hood 4a Block/Draft Hood 5Jacket 6Controls/Circulator/Vent Damper Series MI/MIH