PB Heat MIH manual START-UP Procedures

Page 29

b.Intermittent Ignition System:

i)Turn gas supply off.

ii)Set thermostat or controller above room temperature to call for heat. Watch for igniter glow at pilot burner.

iii)Igniter will continue to glow for 30 seconds, de-energize for 30 seconds, then re-energize and glow for another 30 seconds. It will then de-energize for 5 minutes before restarting the sequence.

iv)Turn gas supply on.

v)Reset the boiler and control by following Operating Instructions.

vi)Observe boiler operation through one complete cycle.

3.Low Water Cut-Off (if used) – Consult the manufacturer’s instructions for the low water cut-off operational check procedure.

4.Check the system to make sure there are no leaks or overfilling problems which might cause excessive make-up water to be added. Make-up water causes liming in the boiler and brings in oxygen. Oxygen can cause severe damage to the boiler though oxygen corrosion pitting.

START-UP PROCEDURES

5.Check the expansion tank and automatic fill valve (if used) to confirm that they are operating correctly. If either of these components causes high pressure in the system, the boiler relief valve will weep or open, allowing fresh water to enter the system.

6.Do not allow the system controls to subject the boiler to excessively low water temperatures, which would cause condensation of flue gases and corrosion of the boiler. Operate the boiler at a temperature above 130°F (54°C). Adjust the boiler limit as required to maintain boiler temperature above this level.

7.Check the general condition of the system including piping support, joints, etc. Check cleanliness of the radiators, baseboard units and/or convectors. Clean them to the extent possible. If radiators do not heat evenly, vent any remaining air from them.

8.Review operation and User’s Information Manual with end-user.

9.Complete the Warranty Card and submit it to PB Heat, LLC.

10.Hang the Installation, Operation and Maintenance Manual and User’s Information Manual in an accessible position near the boiler.

27

Image 29
Contents Series MI/MIH Table of Contents Special Attention Boxes Using this ManualInstallation Sequence Accessibility Clearances PreinstallationClearance from Combustible Construction AIR for Combustion and VentilationAir Openings All Air from Indoors on Different Floors Air Openings All Air from Outdoors through Vertical Ducts Planning the Layout Installation SurveyBoiler SET-UP Boiler Supply and Return Water Piping and ControlsParallel Hook-Up with Water Chiller Safety Relief ValveZone Piping with Zone Valves Piping for Zoned SystemsFreeze Protection Expansion TankINDIRECT-FIRED Water Heater Integral Draft Hood Vent Damper Installation GeneralVenting Venting with Vent Damper in Vertical Position Vent Piping and ChimneySeal any unused openings in the common venting system Boiler Removal from Common Venting SystemGas Connection to Boiler GAS PipingMIH Boiler Natural Gas Electrical Wiring ControlsZoned System Wiring Sequence of Operation Wiring and Connection Diagram Intermittent Ignition Intermittent Ignition System Operating Sequence Zone Wiring with Zone Valves Completing the Installation START-UP ProceduresValve Tapping and Adjustment Screw Locations Operating Instructions For Your Safety Read Before Lighting Control Descriptions Adjustment of GAS Pressure RegulatorAdjustment of Pilot GAS Flow Checking Burner Input CHECK-OUT ProcedureSTART-UP Procedures Troubleshooting Guides TroubleshootingProblem Possible Causes Corrective Actions Intermittent Ignition System Troubleshooting Sequence Maintenance Daily with Boiler in USE GeneralWeekly with Boiler in USE Monthly with Boiler in USEStanding Pilot and Main Burner Flame Annually Before Start of Heating SeasonSeries MI/MIH Boiler Dimensions Boiler Dimensions & RatingsRepair Parts Series MI/MIH GAS Boiler Repair Parts2Manifold Manifold/Gas Train MI Standing Pilot 3b Gas Valve and Pilot Intermittent 4Block/Draft Hood 4a Block/Draft Hood 5Jacket 6Controls/Circulator/Vent Damper Series MI/MIH