MAINTENANCE
E.ANNUALLY (BEFORE START OF HEATING SEASON)
DANGER
When servicing or replacing components, be absolutely certain that the following conditions are met:
●Water, gas and electricity are off.
●The boiler is at room temperature.
●There is no pressure in the boiler.
1.Check flueways and burners for cleanliness and clean if necessary. Use the following procedure if cleaning is required:
a.Refer to the Lighting/Operating Instructions in Figures 7.4 and 7.5 to properly turn off the gas to the boiler.
b.Turn off all electrical power to the boiler.
c.Remove burners and brush orifice spuds lightly using a soft bristle brush.
d.Remove the vent pipe, vent damper, top jacket panels and flue collector/draft diverter. Remove baffles on MIH models.
e.Brush flueways with wire brush.
f.To the extent possible, inspect inside of vent pipe and vent damper for obstructions in flow or vent damper movement. Remove or replace as necessary.
g.
h.
i.
2.Inspect entire venting system for corrosion, support and joint integrity. Repair as necessary.
3.Check the pilot and main burner flame. See Figures
9.1and 9.2. The pilot should provide a steady flame enveloping 3/8″ to 1/2″ (1 cm to 1.2 cm) of the flame sensor. If required, adjust the pilot as stated in the gas valve manufacturer’s instructions or
paragraph 7.D. The main burner flame inner cone should be approximately
Figure 9.1: Standing Pilot and Main Burner Flame
Figure 9.2: Intermittent Pilot and Main
Burner Flame