Initial Installation

QUALIFIED INSTALLERS ONLY

VENT CONFIGURATIONS:

Figures 22 shows the range of venting options, it shows possible vent configurations if the unit is top vented, for vertical and horizontal terminations, any layout that remains within the shaded area is acceptable. Having the fewest number of elbows is ideal, as they tend to disrupt air movement. Using 45˚ elbows is preferable to using 90˚ elbows. Also, a shorter vent system will perform better than a longer one.

NOTE: The total length of the vent pipes can not exceed 33 ft (10.1 m). Any combination of rise and run can be used as long as it lays within the shaded area (a total of three (3) 90° elbows or six (6) 45° elbows can be used). In addition to what is shown, if a 90° elbow is used in the horizontal plane, 3 ft (91.4 cm) must be subtracted from the allowable horizontal run (for each 45° elbow, 11⁄2 ft must be subtracted from the allowable horizontal run).

Figure 22. Possible Vent Configurations; Vertical

and Horizontal Terminations.

VENT RESTRICTOR RING:

A vent restrictor ring is supplied with each direct vent fireplace. This restrictor ring is to be installed when the vertical chimney installation is over 6 ft (1.83 m). Before the chimney is placed onto the stove, place this vent restrictor ring into the 4 inch (10.2 cm) flue pipe (as shown), once the vent restrictor ring has been installed, the vertical sections of chimney can be installed.

Figure 23: Vent restrictor ring.

20

Image 20
Contents EG40 DV Safety Precautions GeneralTable of Contents Codes And Approvals Vented GAS Fireplace Heater EG40 DV NG/LPGSpecifications EG40 Exterior DimensionsFor Your Safety Read Completely Before Operating Operating InstructionsThere is a separate venturies for each burner, see Figure Component Sound & ReasonMaintenance and Service Removing the DoorBurner is lined up Kit Parts List Conversion Kit InstallationMust be not visible Removing valve ScrewInitial Installation Qualified Installers onlyCommon Vertical Installation Do not interfere with the structural integrity of the walls Vent Termination Restrictions KIT Components Assembly of Venting Kit Manufacturer Trade Name Nominal Sizes SV4EBR45 Vent restrictor ring End of the pipes and fittings, are Installing Vent Cap with Vinyl Siding Stand-Off Assemble the desired lengths of black pipe Use of Wall Straps Multi-Story Vent Pipe Installation Insulation33a-2002 Test Methods and the Resulting ITS/WH Must be connected to a grounding rod Must be bolted securely to the floorNatural Gas Propane Front Burner Rear BurnerManifold Pressure Min. Manifold PressureSecondary Installation Log PlacementRemove door to clean glass Trouble Shooting Problem Possible Cause SolutionParts List T. Nova Valve Convertible 50-1421Parts List Parts Diagram Chassis Parts Diagram Gas Tray & Door Warranty To the DealerWarranty Warranty Installation Data Sheet