Sherwood EG40 DV owner manual Trouble Shooting, Problem Possible Cause Solution

Page 31

Trouble Shooting

Problem

Possible Cause

Solution

 

 

 

The main burner does not

The gas valve may not be on.

• Check that the gas control knob is in the “ON” position.

ignite when called for.

 

 

Thermostat is not calling for

• Adjust the thermostat several degrees above ambient

 

 

heat.

temperature.

 

 

 

 

Problem with gas valve.

• Use a DC voltmeter to measure the voltage across the

 

 

TPTH and TP terminals. Main operator voltage: Open

 

 

circuit ≥ 325mV Closed circuit ≥ 100mV

 

 

• If voltage is not present, check the control circuit for

 

 

proper operation.

 

 

• If proper control system voltage is present, replace the

 

 

gas control.

 

 

 

Spark will not light the pilot

Defective piezo ignitor.

• Check connections to ignitor.

after repeatedly pressing the

 

• If ignitor connections are good but no spark, replace

spark ignitor.

 

ignitor.

 

 

 

 

Broken spark electrode.

• Check for broken ceramic insulation, replace electrode if

 

 

broken.

 

 

 

 

Misaligned spark electrode.

• If spark is not arcing from electrode to pilot, loosen the

 

 

screws on the pilot base adjust and tighten.

 

 

 

Pilot will not remain lit.

Problem with thermocouple

• Check for proper connection of the thermocouple to the

 

circuit.

rear of the valve. If loose, fully tighten.

 

 

• Check pilot for full flame impingement around

 

 

thermocouple. If flame is too small, check gas pressure,

 

 

adjust pilot rate screw, check pilot head for damage.

 

 

• Check thermocouple voltage at valve. It must be greater

 

 

than 5 mV. If low, replace thermocouple.

 

 

 

 

Air in gas line (pilot dies while

• Bleed line.

 

knob is depressed).

• Check gas line pressure.

 

 

• Contact dealer.

 

 

 

Burners will not remain lit.

Problem with thermopile

• Check gas line pressure .

 

circuit.

• Check for flame impingement on thermopile. If low, see

 

 

“Pilot will not remain lit”.

 

 

• Check thermopile for minimum of 300 mV when burner is

 

 

switched on.

 

 

• Check wiring to thermostat for breaks.

 

 

 

Flame lifting

Leak in vent pipe

• Check for leaks in vent connections.

 

 

 

 

Improper vent configuration

• Check vent configuration with manual.

 

 

 

 

Terminal may be recirculating

• Check to see if terminal is on correctly.

 

flue gases

• May need to install high wind termination cap.

 

 

• Contact dealer.

 

 

 

Glass fogs up

Normal Condition: after the appliance warms up the glass will clear.

 

**Due to additives in gas, glass may get hazy during operation** Clean as needed.

 

 

 

Blue Flames

Normal during start up: flames will yellow as the fireplace heats up.

 

 

 

Flames are burning “dirty” or

Flame impingement

• Check log positioning.

sooting

 

• Increase primary air by opening the venturi shutter and/

 

 

or by opening the vent restrictor.

 

 

See also “Burners will not remain lit.”

 

 

 

Remote control doesn’t work

Problem with the remote

• One or more of the batteries are dead. See remote

 

 

control instructions.

 

 

 

 

Problem with fireplace

• The on/off switch is turned to OFF.

 

 

• The gas control valve is turned to PILOT or OFF.

 

 

• The pilot has gone out.

 

 

 

31

Image 31
Contents EG40 DV General Safety PrecautionsTable of Contents Vented GAS Fireplace Heater EG40 DV NG/LPG Codes And ApprovalsEG40 Exterior Dimensions SpecificationsOperating Instructions For Your Safety Read Completely Before OperatingComponent Sound & Reason There is a separate venturies for each burner, see FigureRemoving the Door Maintenance and ServiceBurner is lined up Conversion Kit Installation Kit Parts ListRemoving valve Screw Must be not visibleQualified Installers only Initial InstallationCommon Vertical Installation Do not interfere with the structural integrity of the walls Vent Termination Restrictions KIT Components Assembly of Venting Kit Manufacturer Trade Name Nominal Sizes SV4EBR45 Vent restrictor ring End of the pipes and fittings, are Installing Vent Cap with Vinyl Siding Stand-Off Assemble the desired lengths of black pipe Use of Wall Straps Insulation Multi-Story Vent Pipe Installation33a-2002 Test Methods and the Resulting ITS/WH Must be bolted securely to the floor Must be connected to a grounding rodMin. Manifold Pressure Natural Gas Propane Front BurnerRear Burner Manifold PressureLog Placement Secondary InstallationRemove door to clean glass Problem Possible Cause Solution Trouble ShootingT. Nova Valve Convertible 50-1421 Parts ListParts List Parts Diagram Chassis Parts Diagram Gas Tray & Door To the Dealer WarrantyWarranty Warranty Installation Data Sheet