Proper Combustion
High Altitude Information
Furnace should operate minimum 15 minutes with correct manifold pressure and gas flow rate before checking com bustion. Take combustion sample beyond the flue outlet and compare to the tables below.
TABLE 16
EL296 | CO2% For Nat | CO2% For L.P |
Model | Low Fire High Fire | Low Fire High Fire |
0455.4 - 6.4 7.5 - 8.5 6.4 - 7.4 8.8 - 9.8
0705.3 - 6.3 7.4 - 8.4 6.3 - 7.3 8.7 - 9.7
0905.8 - 6.8 7.6 - 8.6 6.8 - 7.8 8.9 - 9.9
110 | 6.1 - 7.1 | 8.0 - 9.0 | 7.1 - 8.1 | 9.3 - 10.3 |
|
|
|
|
|
135 | 6.1 - 7.1 | 7.8 - 8.8 | 7.1 - 8.2 | 9.1 - 10.1 |
The maximum carbon monoxide reading should not exceed 50 ppm.
NOTE - In Canada, certification for installations at eleva tions over 4500 feet (1372 m) is the jurisdiction of local au thorities.
Units may be installed at altitudes up to 10,000 ft. above sea level without manifold adjustment. Units installed at al titude of 4501 - 10,000 feet (1373 to 3048m) may require a pressure switch change which can be ordered separately. Table 18 lists conversion kit and pressure switch require ments at varying altitudes.
The combustion air pressure switch is
TABLE 17
Manifold and Supply Line Pressure 0-10,000ft.
EL296 |
| Manifold Pressure in.wg. | Supply Line Pressure in. w.g. | |||
Gas |
|
|
|
| ||
Unit |
|
|
|
| ||
Low Fire | High Fire | Min | Max | |||
| ||||||
|
| |||||
|
|
|
|
|
| |
| Natural | 1.7 | 3.5 | 4.5 | 10.5 | |
All Sizes |
|
|
|
|
| |
LP/propane | 4.9 | 10.0 | 11.0 | 13.0 | ||
| ||||||
|
|
|
|
|
|
NOTE - A natural to L.P. propane gas changeover kit is necessary to convert this unit. Refer to the changeover kit installation instruction for the conversion procedure.
TABLE 18
LP/Propane Conversion Kit and Pressure Switch Requirements at Varying Altitudes
| Natural to | High Altitude | High Altitude |
|
| |
| Natural Burner | LP/Propane Burner | High Altitude Pressure Switch | |||
EL296 | LP/Propane | |||||
Orifice Kit | Orifice Kit |
|
| |||
|
|
| ||||
Unit |
|
|
|
|
| |
0 - 7500 ft | 7501 - 10,000 ft | 7501 - 10,000 ft | 4501 - 7500 ft | 7501 | ||
| ||||||
| (0 - 2286m) | (2286 - 3038m) | (2286 - 3038m) | (1373 - 2286m) | (2286 - 3048m) | |
|
|
|
|
|
| |
|
|
| 93W81 | 93W84 | ||
|
|
|
|
|
| |
|
|
| 93W80 | 93W85 | ||
|
|
|
|
|
| |
*78W93 | 73W37 | *78W96 | 93W82 | 93W80 | ||
|
|
|
|
|
| |
|
|
| 93W80 | 93W85 | ||
|
|
|
|
|
| |
|
|
| 93W83 | 93W85 | ||
|
|
|
|
|
|
* Conversion requires installation of a gas valve manifold spring which is provided with the gas conversion kit.
Pressure switch is factory set. No adjustment necessary. All models use the
Page 51