Proper Combustion

Proper Combustion

High Altitude Information

Furnace should operate minimum 15 minutes with correct manifold pressure and gas flow rate before checking com­ bustion. Take combustion sample beyond the flue outlet and compare to the tables below.

TABLE 16

EL296

CO2% For Nat

CO2% For L.P

Model

Low Fire High Fire

Low Fire High Fire

0455.4 - 6.4 7.5 - 8.5 6.4 - 7.4 8.8 - 9.8

0705.3 - 6.3 7.4 - 8.4 6.3 - 7.3 8.7 - 9.7

0905.8 - 6.8 7.6 - 8.6 6.8 - 7.8 8.9 - 9.9

110

6.1 - 7.1

8.0 - 9.0

7.1 - 8.1

9.3 - 10.3

 

 

 

 

 

135

6.1 - 7.1

7.8 - 8.8

7.1 - 8.2

9.1 - 10.1

The maximum carbon monoxide reading should not exceed 50 ppm.

NOTE - In Canada, certification for installations at eleva­ tions over 4500 feet (1372 m) is the jurisdiction of local au­ thorities.

Units may be installed at altitudes up to 10,000 ft. above sea level without manifold adjustment. Units installed at al­ titude of 4501 - 10,000 feet (1373 to 3048m) may require a pressure switch change which can be ordered separately. Table 18 lists conversion kit and pressure switch require­ ments at varying altitudes.

The combustion air pressure switch is factory-set and re­ quires no adjustment.

TABLE 17

Manifold and Supply Line Pressure 0-10,000ft.

EL296

 

Manifold Pressure in.wg.

Supply Line Pressure in. w.g.

Gas

 

 

 

 

Unit

 

 

 

 

Low Fire

High Fire

Min

Max

 

 

 

 

 

 

 

 

 

 

Natural

1.7

3.5

4.5

10.5

All Sizes

 

 

 

 

 

LP/propane

4.9

10.0

11.0

13.0

 

 

 

 

 

 

 

NOTE - A natural to L.P. propane gas changeover kit is necessary to convert this unit. Refer to the changeover kit installation instruction for the conversion procedure.

TABLE 18

LP/Propane Conversion Kit and Pressure Switch Requirements at Varying Altitudes

 

Natural to

High Altitude

High Altitude

 

 

 

Natural Burner

LP/Propane Burner

High Altitude Pressure Switch

EL296

LP/Propane

Orifice Kit

Orifice Kit

 

 

 

 

 

Unit

 

 

 

 

 

0 - 7500 ft

7501 - 10,000 ft

7501 - 10,000 ft

4501 - 7500 ft

7501 -10,000 ft

 

 

(0 - 2286m)

(2286 - 3038m)

(2286 - 3038m)

(1373 - 2286m)

(2286 - 3048m)

 

 

 

 

 

 

-045

 

 

 

93W81

93W84

 

 

 

 

 

 

-070

 

 

 

93W80

93W85

 

 

 

 

 

 

-090

*78W93

73W37

*78W96

93W82

93W80

 

 

 

 

 

 

-110

 

 

 

93W80

93W85

 

 

 

 

 

 

-135

 

 

 

93W83

93W85

 

 

 

 

 

 

* Conversion requires installation of a gas valve manifold spring which is provided with the gas conversion kit.

Pressure switch is factory set. No adjustment necessary. All models use the factory-installed pressure switch from 0-4500 feet (0-1370 m).