Accessory Terminals
One line voltage “ACC” 1/4” spade terminal is provided on the furnace integrated control. See figure 65 for integrated
control configuration. This terminal is energized when the indoor blower is operating. Any accessory rated up to one amp can be connected to this terminal with the neutral leg of the circuit being connected to one of the provided neutral
terminals. If an accessory rated at greater than one amp is connected to this terminal, it is necessary to use an exter nal relay.
An unpowered, normally open (dry) set of contacts with a 1/4” spade terminal “HUM” are provided for humidifier con
nections and may be connected to 24V or 120V. Any hu midifier rated up to one amp can be connected to these ter minals. In 120V humidifier applications the neutral leg of the circuit can be connected to one of the provided neutral terminals. This terminal is energized in the heating mode.
Install the room thermostat according to the instructions provided with the thermostat. See figure 64 for thermostat designations. If the furnace is being matched with a heat pump, refer to the FM21 installation instruction or appropri ate dual fuel thermostat instructions.
Indoor Blower Speeds
1 - When the thermostat is set to “FAN ON,” the indoor blower will run continuously on the field selectable fan speed (“LOW HEAT” is default) when there is no cool ing or heating demand.
2 - When the EL296UHE is running in the heating mode, the indoor blower will run on the 'LOW HEAT” or “HIGH HEAT” speed per demand.
3 - When there is a cooling demand, the indoor blower will run on the “LOW COOL” or “HIGH COOL” speed per demand.
Generator Use - Voltage Requirements
The following requirements must be kept in mind when specifying a generator for use with this equipment:
DThe furnace requires 120 volts + 10% (Range: 108 volts to 132 volts).
DThe furnace operates at 60 Hz + 5% (Range: 57 Hz to 63 Hz).
DThe furnace integrated control requires both polarity and proper ground. Both polarity and proper grounding should be checked before attempting to operate the furnace on either permanent or temporary power.
DGenerator should have a wave form distortion of less than 5% THD (total harmonic distortion).
On-Board Links and Diagnostic Push Button (Figure 65)
WARNING
Carefully review all configuration information pro vided. Failure to properly set DIP switches, jumpers and
On-Board Link W914 Dehum
On-Board Link W951 Heat Pump (R to O)
On-Board Link W915 2 Stage Compr (Y1 to Y2)
Diagnostic Push Button
The diagnostic push button is located adjacent to the