Lennox International Inc EL296UHE FIGURE Exiting Exhaust and Intake Vent, Figure Table

Models: EL296UHE Elite Series Gas Furnace

1 58
Download 58 pages 51.32 Kb
Page 28
Image 28
FIGURE 32

Details of Intake and Exhaust Piping Terminations for Direct Vent Installations

NOTE - In Direct Vent installations, combustion air is tak­ en from outdoors and flue gases are discharged to out­

Inches(MM)

3”(76MM) MAX.

SIZE TERMINATION PIPE PER TABLE 8.

UNCONDITIONED

doors.

NOTE - Flue gas may be slightly acidic and may adversely affect some building materials. If any vent termination is used and the flue gasses may impinge on the building ma­ terial, a corrosion-resistant shield (minimum 24 inches square) should be used to protect the wall surface. If the

8” (203MM) MIN

12” (305MM) ABOVE

AVERAGE SNOW

ACCUMULATION

ATTIC SPACE

1/2” (13MM) FOAM

INSULATION IN

UNCONDITIONED

SPACE

optional tee is used, the protective shield is recommended. The shield should be constructed using wood, plastic, sheet metal or other suitable material. All seams, joints, cracks, etc. in the affected area should be sealed using an appropriate sealant. See figure 35.

Intake and exhaust pipes may be routed either horizontally through an outside wall or vertically through the roof. In at­ tic or closet installations, vertical termination through the roof is preferred. Figures 32 through 46 show typical terminations.

1 - Intake and exhaust terminations are not required to be in the same pressure zone. You may exit the intake on one side of the structure and the exhaust on another side (figure 33). You may exit the exhaust out the roof and the intake out the side of the structure (figure 34).

2 - Intake and exhaust pipes should be placed as close together as possible at termination end (refer to il­ lustrations). Maximum separation is 3” (76MM) on roof terminations and 6” (152MM) on side wall termina­ tions.

NOTE - When venting in different pressure zones, the maximum separation requirement of intake and ex­ haust pipe DOES NOT apply.

3 - On roof terminations, the intake piping should termi­ nate straight down using two 90° elbows (See figure 32).

3” (76MM) OR 2” (51MM) PVC

PROVIDE SUPPORT

FOR INTAKE AND

EXHAUST LINES

DIRECT VENT ROOF TERMINATION KIT

(15F75 or 44J41)

FIGURE 32

Exiting Exhaust and Intake Vent

(different pressure zones)

Exhaust

Furnace

Inlet Air

(Minimum 12 in.

Pipe

 

305 MM) above

 

 

 

 

grade or snow

 

 

accumulation

FIGURE 33

Exiting Exhaust and Intake Vent

(different pressure zones)

4 - Exhaust piping must terminate straight out or up as shown. A reducer may be required on the exhaust pip­ ing at the point where it exits the structure to improve the velocity of exhaust away from the intake piping. See table 8.

NOTE - Care must be taken to avoid recirculation of ex­ haust back into intake pipe.

5 - On field-supplied terminations for side wall exit, ex­ haust piping may extend a maximum of 12 inches (305MM) for 2” PVC and 20 inches (508MM) for 3” (76MM) PVC beyond the outside wall. Intake piping

Roof Terminated (different pressure zones)FIGURE 34Manual background

Exhaust Pipe

Furnace

Manual background Inlet Air (Minimum 12 in. 305 MM) above grade or snow

accumulation

should be as short as possible. See figures 36 and 37.

6 - On field-supplied terminations, a minimum distance between the end of the exhaust pipe and the end of the intake pipe without a termination elbow is 8” and a minimum distance of 6” with a termination elbow. See figures 36 and 37.

FIGURE 34

TABLE 8

EXHAUST PIPE TERMINATION SIZE REDUCTION

EL296UHE

Termination

MODEL

Pipe Size

 

 

*045 and 070

1-1/2” (38MM)

*090

2” (51MM)

110

2” (51MM)

135

2” (51MM)

*EL296UHE-045, -070 and -090 units with the flush mount termination must use the 1-1/2”accelerator supplied with the kit.

Page 28

Page 28
Image 28
Lennox International Inc EL296UHE FIGURE Exiting Exhaust and Intake Vent, different pressure zones, Figure Table