Lennox International Inc Elite Series Gas Furnace, EL296UHE Other Unit Adjustments, Primary Limit

Models: EL296UHE Elite Series Gas Furnace

1 58
Download 58 pages 51.32 Kb
Page 53
Image 53
Other Unit Adjustments

Other Unit Adjustments

Primary Limit.

The primary limit is located on the heating compartment vestibule panel. This limit is factory set and requires no ad­ justment.

Flame Rollout Switches (Two)

These manually reset switches are located on the front of the burner box.

Pressure Switch

The pressure switch is located in the heating compartment on the cold end header box. This switch checks for proper combustion air inducer operation before allowing ignition trial. The switch is factory-set and must not be adjusted.

Temperature Rise

Place the unit into operation with a second-stage heating demand. After supply and return air temperatures have stabilized, check the temperature rise. If necessary, adjust the heating blower speed to maintain the temperature rise within the range shown on the unit nameplate. Increase the blower speed to decrease the temperature rise. Decrease the blower speed to increase the temperature rise. Failure to properly adjust the temperature rise may cause erratic limit operation.

Electrical

1 - Check all wiring for loose connections.

2 - Check for the correct voltage at the furnace (furnace operating). Correct voltage is 120VAC + 10%

3 - Check amp-draw on the blower motor with blower ac­ cess panel in place.

Unit Nameplate__________Actual__________

Exhaust and Air Intake Pipe

1 - Check exhaust and air intake connections for tightness and to make sure there is no blockage.

2 - Is pressure switch closed? Obstructed exhaust pipe will cause unit to shut off at pressure switch. Check ter­ mination for blockages.

3 - Obstructed pipe or termination may cause rollout switches to open. Reset manual flame rollout switches on burner box assembly if necessary.

Heating Sequence of Operation

Electronic Ignition

The two-stage, variable speed integrated control used in EL296UHE units has an added feature of an internal Watch­ guard control. The feature serves as an automatic reset de­ vice for ignition control lockout caused by ignition failure. Af­ ter one hour of continuous thermostat demand for heat, the Watchguard will break and remake thermostat demand to the furnace and automatically reset the control to begin the ignition sequence.

NOTE - The ignition control thermostat selection DIP switch is factory-set in the “TWO-STAGE” position.

Applications Using a Two-Stage Thermostat

A - Heating Sequence -- Integrated Control Thermostat

Selection DIP Switch 1 OFF in “Two-Stage” Position

(Factory Setting)

1 - On a call for heat, thermostat first-stage contacts close sending a signal to the integrated control. The inte­ grated control runs a self‐diagnostic program and checks high temperature limit switches for normally closed contacts and pressure switches for normally open contacts. The combustion air inducer is ener­ gized at low speed.

2 - Once the control receives a signal that the low pres­ sure switch has closed, the combustion air inducer be­ gins a 15-second pre-purge in low speed.

NOTE - If the low fire pressure switch does not close the combustion air inducer will switch to high fire. After a 15 second pre-purge the high fire pressure switch will close and the unit will begin operation on high fire. After 10 to 20 seconds of high fire operation the unit will switch to low fire..

3 - After the pre-purge is complete, a 20-second initial ig­ nitor warm-up period begins. The combustion air in­ ducer continues to operate at low speed.

4 - After the 20-second warm-up period has ended, the gas valve is energized on low fire (first stage) and ignition oc­ curs. At the same time, the control module sends a sig­ nal to begin an indoor blower 30-second ON-delay. When the delay ends, the indoor blower motor is ener­ gized on the low fire heating speed, the HUM contacts close energizing the humidifier and 120V ACC termi­ nal is energized. The furnace will continue this opera­ tion as long as the thermostat has a first-stage heating demand.

5 - If second-stage heat is required, the thermostat sec­ ond-stage heat contacts close and send a signal to the integrated control. The integrated control initiates a 30-second second-stage recognition delay.

6 - At the end of the recognition delay, the integrated con­ trol energizes the combustion air inducer at high speed. The control also checks the high fire (second stage) pressure switch to make sure it is closed. The high fire (second stage) gas valve is energized and the indoor blower motor is energized for operation at the high fire heating speed.

7 - When the demand for high fire (second stage) heat is satisfied, the combustion air inducer is switched to the low-fire heating speed and the high-fire (second stage) gas valve is de-energized. The low-fire (first stage) gas valve continues operation. The indoor blower motor is switched to the low-fire heating speed.

8 - When the thermostat demand for low-fire (first stage) heat is satisfied, the gas valve is de-energized and the field-selected indoor blower off delay begins. The combustion air inducer begins a 5-second post-purge period.

9 - When the combustion air post-purge period is com­ plete, the inducer, the HUM contacts as well as the 120V ACC terminals are de-energized. The indoor blower is de-energized at the end of the off delay.

Page 53

Page 53
Image 53
Lennox International Inc Elite Series Gas Furnace Other Unit Adjustments, Heating Sequence of Operation, Primary Limit