Return Air Guidelines

Side Return AirWARNING

Improper installation of the furnace can result in per­ sonal injury or death. Combustion and flue products must never be allowed to enter the return air system or air in the living space. Use sheet metal screws and joint tape to seal return air system to furnace.

In platform installations with furnace return, the fur­ nace should be sealed airtight to the return air ple­ num. A door must never be used as a portion of the return air duct system. The base must provide a stable support and an airtight seal to the furnace. Al­ low absolutely no sagging, cracks, gaps, etc.

For no reason should return and supply air duct sys­ tems ever be connected to or from other heating de­ vices such as a fireplace or stove, etc. Fire, explo­ sion, carbon monoxide poisoning, personal injury and/or property damage could result.

 

Installation Clearances

 

Top

Left Side

Right Side

Return Air Guidelines

Return air can be brought in through the bottom or either side of the furnace installed in an upflow application. If the furnace is installed on a platform with bottom return, make an airtight seal between the bottom of the furnace and the platform to ensure that the furnace operates properly and safely. The furnace is equipped with a removable bottom panel to facilitate installation.

Markings are provided on both sides of the furnace cabinet for installations that require side return air. Cut the furnace cabinet at the maximum dimensions shown on page 2.

Refer to Product Specifications for additional information.

EL296UHE applications which include side return air and a condensate trap installed on the same side of the cabinet (trap can be installed remotely within 5 ft.) re­ quire either a return air base or field-fabricated transi­ tion to accommodate an optional IAQ accessory taller than 14.5”. See figure 13.

Side Return Air

(with transition and filter)

 

Bottom (Floor)

 

 

Top/Plenum

1 in. (25 mm)

 

 

*Front

0

 

 

Back

0

 

 

Sides

0

Vent

0

 

 

Floor

0

*Front clearance in alcove installation must be 24 in. (610 mm). Maintain a minimum of 24 in. (610 mm) for front service access.

Allow proper clearances to accommodate condensate trap.

1−1/2”

Transition Manual background

20” X 25” X 1” (508mmX635mmX25mm) Air Filter

Return

Air

Plenum

For installations on a combustible floor, do not install the furnace directly on carpeting, tile or other combustible materials other than wood flooring.

FIGURE 12

FIGURE 13

Page 10

Page 10
Image 10
Lennox International Inc EL296UHE Return Air Guidelines, Side Return Air with transition and filter