EL296UHE with Evaporator Coil Using a Separate Drain
(Unit shown in horizontal
Evaporator
Coil
4”min
5”max
5’ max.
PVC Pipe Only
Condensate
Drain Connection
Drain Pan
Piping from furnace and evaporator coil must slope down a minimum 1/4” per ft. toward trap
.
Field Provided Vent
(4” min. to 5” max. above condensate connection)
FIGURE 56
EL296UHE with Evaporator
Coil Using a Common Drain
Evaporator drain
line required
(1” min. to 2” Max.above condensate drain connection)
Condensate
Drain Connection
IMPORTANT
When combining the furnace and evaporator coil drains together, the A/C condensate drain outlet must be vented to relieve pressure in or der for the furnace pressure switch to operate properly.
FIGURE 57
EL296UHE with Evaporator Coil Using a Common Drain
(Unit shown in horizontal left−hand discharge position)
Evaporator
Coil
4”min |
5”max |
5’ max.
PVC Pipe Only
Condensate Drain
Connection
(4” min. to 5” Max.above condensate drain connection)
Drain Pan
Piping from furnace and evaporator coil must slope down a minimum 1/4” per ft. toward trap
FIGURE 58