EL296UHE DIRECT VENT APPLICATION
USING EXISTING CHIMNEY
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
| OF ROOF SLOPE * |
| ||||||
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
| ||||||||
8” - 12” |
|
|
|
|
| |||||||||
| EXHAUST VENT |
|
| |||||||||||
(203MM - 305MM) |
| 1/2” (13MM) |
|
| ||||||||||
| WEATHERPROOF |
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
| INSULATION |
|
| |
Minimum 12” (305MM) |
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| SHOULDER OF FITTINGS |
|
| |||||
|
| INTAKE PIPE |
|
|
|
| ||||||||
above chimney top |
| INSULATION (optional) |
|
|
| PROVIDE SUPPORT |
|
| ||||||
|
|
|
|
|
|
|
| OF PIPE ON TOP PLATE |
|
| ||||
|
|
|
|
|
|
|
|
|
| |||||
plate or average snow |
|
| SHEET |
|
|
|
|
| ||||||
|
|
|
|
|
| ALTERNATE |
| |||||||
|
|
|
| |||||||||||
|
|
|
| METAL TOP |
|
|
|
|
|
| ||||
accumulation |
|
|
|
|
| INTAKE PIPE |
| |||||||
|
| PLATE |
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 3” - 8” | ||
| (76MM- | ||
INSULATE | 203MM) |
| |
EXTERIOR | |||
| |||
TO FORM |
| ||
| PORTION OF | ||
SEAL |
| ||
| CHIMNEY | ||
|
| ||
|
|
|
*SIZE TERMINATION PIPE PER TABLE 8.
NOTE - Do not discharge exhaust gases directly into any chimney or vent stack. If ver tical discharge through an existing unused chimney or stack is required, insert piping inside chimney until the pipe open end is above top of chimney and terminate as illus trated. In any exterior portion of chimney, the exhaust vent must be insulated.
FIGURE 46
Details of Exhaust Piping Terminations for Non‐Direct Vent Applications
Exhaust pipes may be routed either horizontally through an outside wall or vertically through the roof. In attic or closet installations, vertical termination through the roof is pre ferred. Figures 47 through 50 show typical terminations.
1 - Exhaust piping must terminate straight out or up as shown. The termination pipe must be sized as listed in table 8.The specified pipe size ensures proper veloc ity required to move the exhaust gases away from the building.
2 - On field supplied terminations for side wall exit, ex haust piping may extend a maximum of 12 inches (305MM) for 2” PVC and 20 inches (508MM) for 3” (76MM) PVC beyond the outside wall. See figure 48.
| SIZE TERMINATION | |
12” (305MM) | PIPE PER TABLE 8. | |
| ||
ABOVE AVE. |
| |
SNOW |
| |
ACCUMULATION | 1/2” (13MM) FOAM | |
| INSULATION | |
3” (76MM) OR | UNCONDITIONED | |
2” (51MM) PVC | ||
ATTIC SPACE | ||
| ||
PROVIDE SUPPORT |
| |
FOR EXHAUST LINES |
(15F75 or 44J41)
FIGURE 47
| 12” (305MM) MAX. for 2” (51MM) | |
| 20” (508MM) MAX. for 3” (76MM) | |
1/2” (13MM) ARMAFLEX |
| |
INSULATION IN |
| |
UNCONDITIONED SPACE | 1/2” (13MM) | |
| ARMAFLEX | |
INSULATION | ||
REDUCER MAY |
| |
BE REQUIRED TO |
| |
ADAPT LARGER |
| |
VENT PIPE SIZE | PVC REDUCER | |
TO TERMINATION | ||
12” MIN. | ||
SIZE TERMINATION | ||
(305MM) | ||
PIPE PER TABLE 8. | ||
Above Grade or | ||
| average snow | |
| accumulation |
(15F74) WALL TERMINATION KIT
FIGURE 48
3 - If exhaust piping must be run up a side wall to position above snow accumulation or other obstructions, pip ing must be supported every 24 inches (610MM) as shown in figure 49. When exhaust piping must be run up an outside wall, any reduction in exhaust pipe size must be done after the final elbow.
| 12” (305MM) MAX. for 2” (51MM) | |
UNCONDITIONED | 20” (508MM) MAX. for 3” (76MM) | |
| ||
SPACE |
| |
6” (152MM) |
| |
Max | SIZE TER | |
| MINATION | |
*WALL SUPPORT | PIPE PER | |
OUTSIDE WALL | TABLE 8. | |
| ||
12” (305MM) | ||
REDUCER MAY BE | ||
ABOVE GRADE OR | ||
REQUIRED TO | ||
AVERAGE SNOW | ||
ADAPT LARGER | ||
ACCUMULATION | ||
VENT PIPE SIZE TO | ||
| ||
TERMINATION |
|
1/2” (13MM) FOAM |
| |
INSULATION IN |
| |
UNCONDITIONED | 1/2” (13MM) FOAM | |
SPACE | ||
INSULATION | ||
|
*Use wall support every 24” (610). Use two supports if extension is
greater than 24” but less than 48”.
FIGURE 49
Page 33