Lennox International Inc Elite Series Gas Furnace EL296UHE DIRECT VENT APPLICATION

Models: EL296UHE Elite Series Gas Furnace

1 58
Download 58 pages 51.32 Kb
Page 33
Image 33
EL296UHE DIRECT VENT APPLICATION

EL296UHE DIRECT VENT APPLICATION

USING EXISTING CHIMNEY

 

 

 

 

 

 

 

 

 

 

 

STRAIGHT-CUT OR

 

 

 

 

 

 

 

3”-8”

ANGLE-CUT IN DIRECTION

 

 

 

 

 

 

 

 

OF ROOF SLOPE *

 

 

 

 

 

 

(76MM-203MM)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8” - 12”

 

 

 

 

 

 

EXHAUST VENT

 

 

(203MM - 305MM)

 

1/2” (13MM)

 

 

 

WEATHERPROOF

 

 

 

 

 

 

 

 

 

 

 

 

 

INSULATION

 

 

Minimum 12” (305MM)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHOULDER OF FITTINGS

 

 

 

 

INTAKE PIPE

 

 

 

 

above chimney top

 

INSULATION (optional)

 

 

 

PROVIDE SUPPORT

 

 

 

 

 

 

 

 

 

 

OF PIPE ON TOP PLATE

 

 

 

 

 

 

 

 

 

 

 

 

plate or average snow

 

 

SHEET

 

 

 

 

 

 

 

 

 

 

 

ALTERNATE

 

 

 

 

 

 

 

 

 

METAL TOP

 

 

 

 

 

 

accumulation

 

 

 

 

 

INTAKE PIPE

 

 

 

PLATE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3” - 8”

 

(76MM-

INSULATE

203MM)

 

EXTERIOR

 

TO FORM

 

 

PORTION OF

SEAL

 

 

CHIMNEY

 

 

 

 

 

*SIZE TERMINATION PIPE PER TABLE 8.

NOTE - Do not discharge exhaust gases directly into any chimney or vent stack. If ver­ tical discharge through an existing unused chimney or stack is required, insert piping inside chimney until the pipe open end is above top of chimney and terminate as illus­ trated. In any exterior portion of chimney, the exhaust vent must be insulated.

FIGURE 46

Details of Exhaust Piping Terminations for Non‐Direct Vent Applications

Exhaust pipes may be routed either horizontally through an outside wall or vertically through the roof. In attic or closet installations, vertical termination through the roof is pre­ ferred. Figures 47 through 50 show typical terminations.

1 - Exhaust piping must terminate straight out or up as shown. The termination pipe must be sized as listed in table 8.The specified pipe size ensures proper veloc­ ity required to move the exhaust gases away from the building.

2 - On field supplied terminations for side wall exit, ex­ haust piping may extend a maximum of 12 inches (305MM) for 2” PVC and 20 inches (508MM) for 3” (76MM) PVC beyond the outside wall. See figure 48.

 

SIZE TERMINATION

12” (305MM)

PIPE PER TABLE 8.

 

ABOVE AVE.

 

SNOW

 

ACCUMULATION

1/2” (13MM) FOAM

 

INSULATION

3” (76MM) OR

UNCONDITIONED

2” (51MM) PVC

ATTIC SPACE

 

PROVIDE SUPPORT

 

FOR EXHAUST LINES

NON-DIRECT VENT ROOF TERMINATION KIT

(15F75 or 44J41)

FIGURE 47

 

12” (305MM) MAX. for 2” (51MM)

 

20” (508MM) MAX. for 3” (76MM)

1/2” (13MM) ARMAFLEX

 

INSULATION IN

 

UNCONDITIONED SPACE

1/2” (13MM)

 

ARMAFLEX

FIELD-PROVIDED

INSULATION

REDUCER MAY

 

BE REQUIRED TO

 

ADAPT LARGER

 

VENT PIPE SIZE

PVC REDUCER

TO TERMINATION

12” MIN.

SIZE TERMINATION

(305MM)

PIPE PER TABLE 8.

Above Grade or

 

average snow

 

accumulation

NON-DIRECT VENT FIELD SUPPLIED WALL TERMINATION OR

(15F74) WALL TERMINATION KIT

FIGURE 48

3 - If exhaust piping must be run up a side wall to position above snow accumulation or other obstructions, pip­ ing must be supported every 24 inches (610MM) as shown in figure 49. When exhaust piping must be run up an outside wall, any reduction in exhaust pipe size must be done after the final elbow.

 

12” (305MM) MAX. for 2” (51MM)

UNCONDITIONED

20” (508MM) MAX. for 3” (76MM)

 

SPACE

 

6” (152MM)

 

Max

SIZE TER­

 

MINATION

*WALL SUPPORT

PIPE PER

OUTSIDE WALL

TABLE 8.

 

FIELD-PROVIDED

12” (305MM)

REDUCER MAY BE

ABOVE GRADE OR

REQUIRED TO

AVERAGE SNOW

ADAPT LARGER

ACCUMULATION

VENT PIPE SIZE TO

 

TERMINATION

 

1/2” (13MM) FOAM

 

INSULATION IN

 

UNCONDITIONED

1/2” (13MM) FOAM

SPACE

INSULATION

 

NON-DIRECT VENT FIELD SUPPLIED WALL TERMINATION EXTENDED OR (15F74) WALL TERMINATION VENT PIPE EXTENDED

*Use wall support every 24” (610). Use two supports if extension is

greater than 24” but less than 48”.

FIGURE 49

Page 33

Page 33
Image 33
Lennox International Inc Elite Series Gas Furnace EL296UHE DIRECT VENT APPLICATION, Using Existing Chimney