Compressor runs, but evaporator does not
| 1. Faulty blower | • Evaporator coil probably frozen |
| motor or broken wire | • Shut off power to condensing unit |
| connection | |
| • Call a CERTIFIED HVAC service technician for repair | |
|
| |
|
|
|
| 2. Defective low | • Compressor would continue to run when thermostat |
| pressure switch not | is satisfied and shuts blower and solenoid off. When |
| shutting compressor off | space warms up to set point, blower starts and the |
| when pressure drops | system runs normally. |
|
| • Prolonged running without refrigerant flow will |
|
| damage or destroy compressor. If this condition |
|
| exists, call a CERTIFIED HVAC service technician. |
|
|
|
Compressor short cycles, which is different from running intermittently | ||
|
|
|
| 1. System pressure | Call a CERTIFIED HVAC service technician to verify and |
| controls defective. | repair. |
|
|
|
| 2. System low on | Observe for flashing in refrigerant sight glass located |
| refrigerant. | in 1/4” copper tube at condensing unit. If flashing with |
|
| bubbles, call a CERTIFIED HVAC service technician for |
|
| leak location, repair, and adding refrigerant. |
|
|
|
| 3. Condenser fan motor | • Fan does not run with compressor. |
| defective | • ¼” copper tube at sight glass – very hot, compressor |
|
| |
|
| very hot, runs short time, shuts off. |
|
| • Shut power off to condensing unit |
|
| • Call a CERTIFIED HVAC service technician for repair. |
|
|
|
| 4. Compressor starting | • Compressor very hot and hums when trying to start. |
| components defective. | • Shut power off to condensing unit. |
|
| • Call a CERTIFIED HVAC service technician. |
|
|
|
Evaporator coil freezes |
| |
|
|
|
| 1. Air filter, if | Clean or replace filter |
| equipped, dirty |
|
|
|
|
| 2. Evaporator coil and/ | Clean coil and blower |
| or blower dirty |
|
|
|
|
| 3. Thermostat set point | Set point should not be lower than 50°. If so, increase to |
| too low. | above 50° |
|
|
|
| 4. System low on | Check refrigerant “sight glass” in 1/4” tubing. Check |
| refrigerant | for bubbles after system has run for several minutes. If |
|
| bubbles present, call a CERTIFIED HVAC service technican. |
|
| If sight is clear of bubbles, refrigerant level is OK. |
|
|
|