Emerson Process Management 2051CF manual Operation and Maintenance, Reference

Page 15

Quick Installation Guide

00825-0100-4101, Rev EA June 2010

Rosemount 2051

Operation and Maintenance

Proof Test and Inspection

The following proof tests are recommended. Proof test results and corrective actions taken must be documented at www.emersonprocess.com/rosemount/safety/certtechdocumentation.htm in the event that an error is found in the safety functionality.

Use "Table 1: Field Communicator Fast Key Sequence" to perform a Loop Test, Analog Output Trim, or Sensor Trim. See the 2051 reference manual (00809-0100-4101) for additional information.

Proof Test

This proof test will detect 99% of DU failures not detected by the 2051 automatic diagnostics.

1.Conduct a Loop Test. On HART host/communicator enter the Fast Key Sequence 1, 2, 2.

a.Enter the milliampere value representing a high alarm state

b.Check the reference meter to verify the mA output corresponds to the entered value.

c.Enter the milliampere value representing a low alarm state

d.Check the reference meter to verify the mA output corresponds to the entered value.

2.Perform a minimum two point sensor calibration check using the 4-20mA range points as the calibration points.

a.If necessary, use one of the “Trim” procedures available in the 2051 reference manual to calibrate.

NOTE

The user determines the proof-test requirements for impulse piping.

Visual Inspection

Not required.

Special Tools

Not required

Product Repair

All failures detected by the transmitter diagnostics or by the proof-test must be reported. Feedback can be submitted electronically at www.emersonprocess.com/rosemount/safety/certtechdocumentation.htm.

The 2051 is repairable by major component replacement. Follow the instructions in the 2051 reference manual (document number 00809-0100-4101) for additional information.

Reference

Specifications

The 2051 must be operated in accordance to the functional and performance specifications provided in the 2051 reference manual.

Failure Rate Data

The FMEDA report includes failure rates and common cause Beta factor estimates. This report is available at www.emersonprocess.com/rosemount.

15

Image 15
Contents Rosemount 2051CF Series Flowmeter Transmitter Quick Installation GuideConduit/Cable Entries Explosions could result in death or serious injuryProcess leaks may cause harm or result in death Electrical shock can result in death or serious injuryMount the Transmitter ApplicationsFlow Optional Mounting Brackets Common Transmitter Assemblies Bolting ConsiderationsPtfe Based Rings with Flange AdaptersFlange Adapter RingConsider Housing Rotation Inline Gage Transmitter OrientationSET the Jumpers MA Hart RL ≥ 250Ω Connect the Wiring and PowerWiring Power Supply for 1-5 Vdc Hart Low Power Power Supply for 4-20 mA HartFunction MA Hart Verify ConfigurationZero Trim Using the Field CommunicatorUsing the Transmitter Zero Adjustment Buttons Trim the TransmitterSafety Instrumented Systems InstallationConfiguration Reference Operation and MaintenanceEuropean Directive Information Safety Failure ValuesProduct Certifications Approved Manufacturing LocationsEuropean Certifications Hart ProtocolHazardous Locations Certifications North American CertificationsRosemount IECEx Certifications Tiis Certifications Inmetro CertificationsCCoE Certifications E5 and I5 combination Combinations of CertificationsE1, I1, N1, and ND combination E4 and I4 combinationRosemount Rosemount Rosemount
Related manuals
Manual 152 pages 41.56 Kb