Emerson Process Management 2051 Inline Gage Transmitter Orientation, Consider Housing Rotation

Page 7

Quick Installation Guide

00825-0100-4101, Rev EA June 2010

Rosemount 2051

E. Inline Gage Transmitter Orientation

The low side pressure port (atmospheric reference) on the inline gage transmitter is located in the neck of the transmitter, behind the housing. The vent path is 360° around the transmitter between the housing and sensor. (See Figure 3.)

Keep the vent path free of any obstruction, including but not limited to paint, dust, and lubrication by mounting the transmitter so that the contaminants can drain away.

Figure 3. Inline Gage Transmitter

Low side pressure port (atmospheric reference)

STEP 2: CONSIDER HOUSING ROTATION

To improve field access to wiring or to better view the optional LCD display:

1.Loosen the housing rotation set screw.

2.First rotate the housing clockwise to the desired location. If the desired location cannot be achieved due to thread limit, rotate the housing counter clockwise to the desired location (up to 360° from thread limit).

3.Retighten the housing rotation set screw.

Housing Rotation Set Screw

(5/64-inch)

STEP 3: SET THE JUMPERS

If alarm and security jumpers are not installed, the transmitter will operate normally with the default alarm condition alarm high and the security off.

1.If the transmitter is installed, secure the loop, and remove power.

2.Remove the housing cover opposite the field terminal side. Do not remove the instrument cover in explosive atmospheres when the circuit is live.

3.Reposition the jumper. Avoid contact with the leads and the terminals. See Figure 4 for the location of the jumper and the ON and OFF positions.

4.Reattach the transmitter cover. The cover must be fully engaged to comply with explosion-proof requirements.

7

Image 7
Contents Rosemount 2051CF Series Flowmeter Transmitter Quick Installation GuideConduit/Cable Entries Explosions could result in death or serious injuryProcess leaks may cause harm or result in death Electrical shock can result in death or serious injuryApplications Mount the TransmitterFlow Optional Mounting Brackets Common Transmitter Assemblies Bolting ConsiderationsPtfe Based Rings with Flange AdaptersFlange Adapter RingInline Gage Transmitter Orientation Consider Housing RotationSET the Jumpers MA Hart RL ≥ 250Ω Connect the Wiring and PowerWiring Power Supply for 1-5 Vdc Hart Low Power Power Supply for 4-20 mA HartFunction MA Hart Verify ConfigurationZero Trim Using the Field CommunicatorUsing the Transmitter Zero Adjustment Buttons Trim the TransmitterInstallation Safety Instrumented SystemsConfiguration Reference Operation and MaintenanceEuropean Directive Information Safety Failure ValuesProduct Certifications Approved Manufacturing LocationsEuropean Certifications Hart ProtocolHazardous Locations Certifications North American CertificationsRosemount IECEx Certifications Inmetro Certifications Tiis CertificationsCCoE Certifications E5 and I5 combination Combinations of CertificationsE1, I1, N1, and ND combination E4 and I4 combinationRosemount Rosemount Rosemount