Quick Installation Guide
Rosemount 2051
Power Supply for 4-20 mA HART
Transmitter operates on 10.5 - 42.4 Vdc. The dc power supply should provide power with less than two percent ripple.
Figure 8. Load Limitation
Maximum Loop Resistance = 43.5 * (Power Supply Voltage – 10.5)
Load (Ohms)
1387
1000
500Operating
Region
0 |
|
|
10.5 | 20 | 30 |
Voltage (V dc) | 42.4 |
|
The Field Communicator requires a minimum loop resistance of 250Ω for communication.
The total resistance load is the sum of the resistance of the signal leads and the load resistance of the controller, indicator, and related pieces. Note that the resistance of intrinsic safety barriers, if used, must be included.