Rosemount 2051

STEP 4: CONNECT THE WIRING AND POWER

Use the following steps to wire the transmitter:

1.Remove the housing cover on the FIELD TERMINALS side.

2.Connect the positive lead to the “+” terminal (PWR/COMM) and the negative lead to the “–” terminal.

Figure 5. 4–20 mA HART Transmitter Wiring Diagrams

Power

Supply

RL 250Ω

Figure 6. 1-5 Vdc HART Low Power Transmitter Wiring

Power

Supply

Voltmeter

Installation of the transient protection terminal block does not provide transient protection unless the 2051 case is properly grounded.

3.Ensure proper grounding. It is important that the instrument cable shield:

be trimmed close and insulated from touching the transmitter housing.

be connected to the next shield if cable is routed through a junction box.

be connected to a good earth ground at the power supply end.

9

Image 9
Contents Rosemount 2051CF Series Flowmeter Transmitter Quick Installation GuideProcess leaks may cause harm or result in death Explosions could result in death or serious injuryElectrical shock can result in death or serious injury Conduit/Cable EntriesMount the Transmitter ApplicationsFlow Optional Mounting Brackets Common Transmitter Assemblies Bolting ConsiderationsFlange Adapter Rings with Flange AdaptersRing Ptfe BasedConsider Housing Rotation Inline Gage Transmitter OrientationSET the Jumpers MA Hart RL ≥ 250Ω Connect the Wiring and PowerWiring Power Supply for 1-5 Vdc Hart Low Power Power Supply for 4-20 mA HartFunction MA Hart Verify ConfigurationUsing the Transmitter Zero Adjustment Buttons Using the Field CommunicatorTrim the Transmitter Zero TrimSafety Instrumented Systems InstallationConfiguration Reference Operation and MaintenanceProduct Certifications Safety Failure ValuesApproved Manufacturing Locations European Directive InformationHazardous Locations Certifications Hart ProtocolNorth American Certifications European CertificationsRosemount IECEx Certifications Tiis Certifications Inmetro CertificationsCCoE Certifications E1, I1, N1, and ND combination Combinations of CertificationsE4 and I4 combination E5 and I5 combinationRosemount Rosemount Rosemount