Emerson Process Management 2051CF manual Mount the Transmitter, Applications, Flow

Page 3

Quick Installation Guide

00825-0100-4101, Rev EA June 2010

Rosemount 2051

STEP 1: MOUNT THE TRANSMITTER

A. Applications

Liquid Flow Applications

1.Place taps to the side of the line.

2.Mount beside or below the taps.

3.Mount the transmitter so that the drain/vent valves are oriented upward.

 

w

lo

F

 

Gas Flow Applications

1.Place taps in the top or side of the line.

2.Mount beside or above the taps.

Flow

Steam Flow Applications

1.Place taps to the side of the line.

2.Mount beside or below the taps.

3.Fill impulse lines with water.

 

w

lo

F

 

3

Image 3
Contents Rosemount 2051CF Series Flowmeter Transmitter Quick Installation GuideConduit/Cable Entries Explosions could result in death or serious injuryProcess leaks may cause harm or result in death Electrical shock can result in death or serious injuryMount the Transmitter ApplicationsFlow Optional Mounting Brackets Common Transmitter Assemblies Bolting ConsiderationsPtfe Based Rings with Flange AdaptersFlange Adapter RingConsider Housing Rotation Inline Gage Transmitter OrientationSET the Jumpers MA Hart RL ≥ 250Ω Connect the Wiring and PowerWiring Power Supply for 1-5 Vdc Hart Low Power Power Supply for 4-20 mA HartFunction MA Hart Verify ConfigurationZero Trim Using the Field CommunicatorUsing the Transmitter Zero Adjustment Buttons Trim the TransmitterSafety Instrumented Systems InstallationConfiguration Reference Operation and MaintenanceEuropean Directive Information Safety Failure ValuesProduct Certifications Approved Manufacturing LocationsEuropean Certifications Hart ProtocolHazardous Locations Certifications North American CertificationsRosemount IECEx Certifications Tiis Certifications Inmetro CertificationsCCoE Certifications E5 and I5 combination Combinations of CertificationsE1, I1, N1, and ND combination E4 and I4 combinationRosemount Rosemount Rosemount
Related manuals
Manual 152 pages 41.56 Kb