Emerson Process Management 2051CF manual Rosemount

Page 18

Quick Installation Guide

Rosemount 2051

00825-0100-4101, Rev EA June 2010

N1 ATEX Type n

 

Certification No. Baseefa08ATEX0130X

II 3 G

Ex nAnL IIC T4 (–40 Ta +70 °C)

 

Ui = 42.4 Vdc max

 

IP66

 

Special Conditions for Safe Use (X):

When the optional transient protection terminal block is installed, the apparatus is not capable of withstanding a 500V r.m.s. test to case. This must be taken into account on any installation in which it is used, for example by assuring that the supply to the apparatus is galvanically isolated.

E1 ATEX Flame-Proof

 

 

 

Certification No. KEMA 08ATEX0090 X

II 1/2 G

Ex d IIC T6 (–50 Ta

65 °C)

 

Ex d IIC T5 (–50 Ta

80 °C)

 

IP66

 

 

 

1180

Vmax = 42.4 V dc

Special Conditions for Safe Use (X):

1.Appropriate ex d blanking plugs, cable glands, and wiring needs to be suitable for a temperature of 90 °C.

2.This device contains a thin wall diaphragm. Installation, maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer’s instructions for maintenance shall be followed in detail to assure safety during its expected lifetime.

3.The 2051 does not comply with the requirements of IEC 60079-1 Clause 5 for flameproof joints. Contact Emerson Process Management for information on the dimensions of flameproof joints.

ND ATEX Dust

Certification No. Baseefa08ATEX0182X II 1 D Dust Rating: Ex tD A20 T115 °C (–20 Ta 85 °C) Vmax = 42.4 V dc

A = 22 mA 1180

Special Conditions for Safe Use (X):

1.The user must ensure that the maximum rated voltage and current (42.4 volts, 22 milliampere, DC) are not exceeded. All connections to other apparatus or associated apparatus shall have control over this voltage and current equivalent to a category “ib” circuit according to EN 60079-1.

2.Cable entries must be used which maintain the ingress protection of the enclosure to at least IP66.

3.Unused cable entries must be filled with suitable blanking plugs which maintain the ingress protection of the enclosure to at least IP66.

4.Cable entries and blanking plugs must be suitable for the ambient range of the apparatus and capable of withstanding a 7J impact test.

18

Image 18
Contents Quick Installation Guide Rosemount 2051CF Series Flowmeter TransmitterElectrical shock can result in death or serious injury Explosions could result in death or serious injuryProcess leaks may cause harm or result in death Conduit/Cable EntriesMount the Transmitter ApplicationsFlow Optional Mounting Brackets Bolting Considerations Common Transmitter AssembliesRing Rings with Flange AdaptersFlange Adapter Ptfe BasedConsider Housing Rotation Inline Gage Transmitter OrientationSET the Jumpers MA Hart Connect the Wiring and Power RL ≥ 250ΩWiring Power Supply for 4-20 mA Hart Power Supply for 1-5 Vdc Hart Low PowerVerify Configuration Function MA HartTrim the Transmitter Using the Field CommunicatorUsing the Transmitter Zero Adjustment Buttons Zero TrimSafety Instrumented Systems InstallationConfiguration Operation and Maintenance ReferenceApproved Manufacturing Locations Safety Failure ValuesProduct Certifications European Directive InformationNorth American Certifications Hart ProtocolHazardous Locations Certifications European CertificationsRosemount IECEx Certifications Tiis Certifications Inmetro CertificationsCCoE Certifications E4 and I4 combination Combinations of CertificationsE1, I1, N1, and ND combination E5 and I5 combinationRosemount Rosemount Rosemount