Emerson Process Management 2051 Trim the Transmitter, Zero Trim, Using the Field Communicator

Page 13

Quick Installation Guide

00825-0100-4101, Rev EA June 2010

Rosemount 2051

STEP 6: TRIM THE TRANSMITTER

NOTE

Transmitters are shipped fully calibrated per request or by the factory default of full scale (span = upper range limit).

Zero Trim

A zero trim is a single-point adjustment used for compensating mounting position effects. When performing a zero trim, ensure that the equalizing valve is open and all wet legs are filled to the correct level.

There are two methods to compensate for mounting effects:

Field Communicator

Transmitter Zero Adjustment Buttons

Select the appropriate method and follow instructions below.

Using the Field Communicator

If zero offset is within 3% of URL, follow the “Using the Field Communicator” instructions below. This zero trim will affect the 4-20 mA value, the HART PV, and the display value.

HART Fast Keys

Steps

1, 2, 3, 3, 2

1. Equalize or vent the transmitter and connect Fieldbus communicator.

 

2.

At the menu, input the Fast Key sequence.

 

3.

Follow the commands to perform a zero trim.

Using the Transmitter Zero Adjustment Buttons

Using the Transmitter Zero Adjustment Buttons, the Lower Range Value (LRV) will be set to the pressure applied to the transmitter. This adjustment will affect the 4-20 mA value only. Perform the following steps to perform a rerange using the zero adjustment buttons.

1.Loosen the certifications label screw and slide the label to expose the zero adjustment buttons. See Figure 9.

2.Set the 4 mA point by pressing the zero button for 2 seconds. Verify that the output is 4 mA. The optional LCD will display ZERO PASS.

Figure 9. Zero and Span buttons

Span

Zero

13

Image 13
Contents Rosemount 2051CF Series Flowmeter Transmitter Quick Installation GuideProcess leaks may cause harm or result in death Explosions could result in death or serious injuryElectrical shock can result in death or serious injury Conduit/Cable EntriesApplications Mount the TransmitterFlow Optional Mounting Brackets Common Transmitter Assemblies Bolting ConsiderationsFlange Adapter Rings with Flange AdaptersRing Ptfe BasedInline Gage Transmitter Orientation Consider Housing RotationSET the Jumpers MA Hart RL ≥ 250Ω Connect the Wiring and Power Wiring Power Supply for 1-5 Vdc Hart Low Power Power Supply for 4-20 mA HartFunction MA Hart Verify ConfigurationUsing the Transmitter Zero Adjustment Buttons Using the Field CommunicatorTrim the Transmitter Zero TrimInstallation Safety Instrumented SystemsConfiguration Reference Operation and MaintenanceProduct Certifications Safety Failure ValuesApproved Manufacturing Locations European Directive InformationHazardous Locations Certifications Hart ProtocolNorth American Certifications European CertificationsRosemount IECEx Certifications Inmetro Certifications Tiis CertificationsCCoE Certifications E1, I1, N1, and ND combination Combinations of CertificationsE4 and I4 combination E5 and I5 combinationRosemount Rosemount Rosemount
Related manuals
Manual 152 pages 41.56 Kb