IV. Operating and Service Instructions

A.ALWAYS INSPECT INSTALLATION BEFORE STARTING BURNER.

B.FILL HEATING SYSTEM WITH WATER.

1.Hot Water Boilers: Fill entire Heating System with water and vent air from system. Use the following procedure on a Series Loop System installed as per Figure 9:

a.Close all but one zone valve.

b.Open drain valve on boiler.

c.Open fill valve.

d.Close purge valve.

e.Open relief valve on boiler.

f.Allow water to run out of drain valve until zone has been purged of air and filled with water.

g.Open zone valve to the second zone to be purged, then close the first. Repeat this step until all zones have been purged but always have one zone open. At completion open all zone valves.

h.Close drain valve.

i.When water discharges from relief valve, release the lever on the top of the relief valve, allowing it to close.

j.Continue filling the system until the pressure gauge reads 12 psi. Close fill valve.

C.CHECK CONTROLS, WIRING AND BURNER to be sure that all connections are tight and burner is rigid, that all electrical connections have been completed and fuses installed, and that oil tank is filled and oil lines have been tested.

D.LUBRICATION

1.Follow instruction on burner and circulator label to lubricate, if oil lubricated. Most motors currently used on residential type burners employ permanently lubricated bearings and thus do not require any field lubrication. Water lubricated circulators do not need field lubrication.

2.Do not over-lubricate. This can cause as much trouble as no lubrication at all.

E.ADJUST CONTROL SETTINGS with burner service switch turned “ON”.

1.SET ROOM THERMOSTAT about 10°F below room temperature.

2.On WATER BOILERS WITHOUT TANKLESS HEATERS equipped with L7248 electronic aquastat controller, set High Limit (HL) at 180°F. This temperature can be varied to suit installation requirements. L7248 controller has the High Limit adjustment range from 180°F to 240°F (82°C to

116°C). High Limit Differential is fixed at 15°F

(8°C).

3.On WATER BOILERS WITH TANKLESS HEATERS equipped with L7224 electronic aquastat controller, set operating control (low limit [LL])

at 190°F and high limit (HL) at 210°F. Operating control (low limit) setting must be a minimum of 20°F below high limit setting.

L7224 controller has the High Limit adjustment range from 130°F to 240°F (55°C to 116°C), and the Low Limit adjustment range from 110°F to 220°F (43°C to 104°C). High Limit Differential is fixed at 10°F (6°C), and Low Limit Differential has adjustment range from 10°F (6°C) to 25°F (14°C).

4.ADJUSTING AQUASTAT CONTROLLER SETTINGS. To discourage unauthorized changing of Aquastat settings, a procedure to enter the ADJUSTMENT mode is required. To enter the ADJUSTMENT mode, press the UP, DOWN, and I buttons (refer to Figure 22) simultaneously for three seconds. Press the I button until the feature requiring adjustment is displayed:

HL_­  High Limit.

LL_­  Low Limit.

Ldf  Low Limit Differential.

°F  °C.

Then, press the UP and/or DOWN buttons to move the set point to the desired value. After 60 seconds without any button inputs, the control will automatically return to the RUN mode.

Note that L7224 Aquastat Controller will display all four (4) above-listed adjustment features, but L7248 Aquastat Controller will not display Low Limit and Low Limit Differential adjustment features.

5.DISPLAY READOUT

In the RUN mode, the Aquastat will flash "bt"

(boiler temp) followed by the temperature (i.e., 220), followed by °F or °C.

Figure 22: L7248/L7224 Circuit Board Layout -

Horizontal Mount

24

Image 24
Contents Price $3.00 Important Information Please Read this page Carefully Page Table of Contents General InformationCL3 Thru CL5 Water Boiler Less Tankless Heater Boiler Dimensions Minimum Chimney Size Approx. Water Rating data II. Installation Instructions Remove CrateRemoval of Boiler from Skid Inspect Combustion Target Wall and Combustion Chamber LinerInstallation/Removal of Drawer Assembly Electrode Setting Recommended Boiler Piping for Series Loop Hot Water System Connect Field Wiring Connect Supply and Return Piping to Heating SystemWater Boiler Steam BoilerOxygen Contamination Schematic Tankless Heater Piping Tankless Heater Data Recommended Smokepipe Arrangement Chimney Requirements Fuel Units and OIL Lines Single stage units 3450 rpm two pipe systemsSequence of Operation Wiring Diagram, Water without Tankless Heater, Riello Burner Sequence of Operation Page Sequence of Operation Page III. Indirect Water Heater Piping Indirect Water Heater Piping on CL Series Water BoilerIV. Operating and Service Instructions LubricationDisplay Readout LEd error codes OperationRemove GUN Assembly High Limit ControllerLOW Limit and Circulator Controller Adjust OIL Burner Before Starting Open ALL OIL Line ValvesStart OIL Burner Adjust OIL Burner While Operating CAD Cell Location and ServiceCheck for Clean CUT OFF of Burner Flame FailureCheckout Procedure Test ControlsPrimary Relay Test Remove JumperMaintenance and Service Instructions Water Boilers Excessive MAKE-UP Water Hints on CombustionSuction Line Leaks High Altitude Installations VI. Boiler Cleaning Clean TOP of Boiler SectionsClean the Firebox Reassemble BoilerAvoid Breathing Fiber Particulates and Dust Trouble Shooting Carlin 40200 Oil Primary Control Carlin 40200 OIL Primary ControlVII. Repair Parts Bare Boiler Assembly Exploded View Boiler Assembly Jacket Assembly Exploded View CL3 Thru CL5 Water Boilers Trim and Controls CL3 Thru CL5 Steam Boilers Trim and Controls Beckett OIL Burner Parts List Beckett OIL Burner Part NOS. for CL Series Boilers VIII. Low Water Cut Off Lwco WhenBeckett AFG Riello OIL Burner Part Numbers for CL Series BOILERS  Service Record Service Record Service Record Page Limited Warranties

F3, F5, 40 Series, CL Series specifications

Energy Tech Laboratories has made significant strides in innovation and sustainability with its well-regarded CL Series, 40 Series, F5, and F3 product lines. Each series is designed to provide scalable energy solutions tailored to meet diverse industry demands while promoting efficiency and environmental responsibility.

The CL Series stands out for its compact design and modular construction. It is ideal for small to medium-sized enterprises looking to optimize energy consumption. One of the primary features of the CL Series is its advanced energy management system, which uses real-time data analytics to help users monitor and analyze their energy usage patterns. Additionally, it is equipped with a regenerative braking technology that captures and reuses energy, making it exceptionally efficient.

In contrast, the 40 Series is targeted towards larger industrial applications. This series boasts high-capacity energy storage solutions and integrates seamlessly with existing systems. One of its most remarkable features is its adaptive load management system, which intelligently distributes power based on real-time demand, ensuring maximum efficiency and minimal waste. The 40 Series is also built with robust safety protocols, including fire suppression systems and advanced fault detection technologies.

The F5 model is engineered for ultimate performance. It incorporates cutting-edge battery technology that enhances energy density, resulting in longer operational life and reduced maintenance costs. Its real-time monitoring capabilities offer users the ability to track performance metrics from anywhere, further enabling proactive decision-making. Additionally, the F5 features a modular battery design, allowing for easy upgrades and expansions as energy needs grow.

Finally, the F3 series exemplifies the future of energy technology with its innovative approach to renewable energy integration. The F3 is designed to work with solar and wind energy systems, leveraging advanced algorithms to maximize energy capture from these sources. Users benefit from its intelligent grid interface, which allows for efficient energy distribution within microgrid configurations.

In summary, Energy Tech Laboratories’ CL Series, 40 Series, F5, and F3 combine robust engineering and innovative technologies to address the varying energy needs of users. With features like real-time monitoring, adaptive load management, and renewable energy integration, these product lines not only enhance operational efficiency but also contribute to a sustainable energy future. As industries increasingly look towards improving energy practices, these series stand out as relevant, viable solutions in the evolving landscape of energy technology.