Bradford-White Corp BRHHH GAS Supply and Piping, Distance from Gas Meter or Last Stage Regulator

Page 13

Βρυτε Μαγνυμ

Page 13

 

At the time of removal of an existing boiler, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation.

1.Seal any unused openings in the common venting system.

2.Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.

3.Insofar as it is practical, close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.

4.Place in operation the appliance being inspected. Follow the lighting instructions. Adjust thermostat so appliance will operate continuously.

5.Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle, or smoke from a cigarette, cigar or pipe.

6.After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas burning appliance to their previous conditions of use.

7.Any improper operation of the common venting system should be corrected so that the installation conforms to the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CSA B149.1, Installation Codes. When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size

as determined using the appropriate tables and guidelines in the National Fuel Gas Code, ANSI Z223.1 NFPA 54 and/or CSA B149.1, Installation Codes.

Section 3

GAS SUPPLY AND PIPING

3.1Gas Supply and Piping

Gas piping should be supported by suitable

hangers or floor stands, not the appliance. Review the following instructions before

proceeding with the installation.

1.Verify that the appliance is fitted for the proper type of gas by checking the rating plate. Appliances are normally equipped to operate at elevations up to 2000 feet (610m). However, the appliance will function properly without the use of high altitude modification at elevations up to 10,000 feet (3050 m).

2.The maximum inlet gas pressure must not exceed 13" W.C. (3.2kPa). The minimum inlet natural gas pressure is 4" W.C. (1.0kPa) and minimum inlet propane gas pressure is 6" (1.5kPa).

3.Refer to Table 6, size supply.

4.Run gas supply line in accordance with all applicable codes.

Note: If you have a boiler/water heater with a normally open vent valve, install a vent line from the vent valve to an outside location as required by your installation code or IRI requirement. Do not remove 3/4 inch pipe plug from the vent valve if venting from the normally open vent valve is not required by your installation code.

5.Locate and install manual shutoff valves in accordance with state and local requirements.

6.A sediment trap must be provided upstream of the gas controls.

Size and

 

 

Distance from Gas Meter or Last Stage Regulator

 

 

Gas Type

0-50 feet

0-15m

50-100 feet

15-31m

100-200 feet

31-61m

200-300 feet

61-91m

1200 natural

2"

5.1cm

2-1/2"

6.4cm

2-1/2"

6.4cm

3"

7.6cm

1200 propane

1-1/2"

3.8cm

2"

5.1cm

2"

5.1cm

2-1/2"

6.4cm

1600 natural

2-1/2"

6.4cm

2-1/2"

6.4cm

3"

7.6cm

3"

7.6cm

1600 propane

2"

5.1cm

2"

5.1cm

2-1/2"

6.4cm

2-1/2"

6.4cm

2000 natural

3"

7.6cm

3"

7.6cm

3"

7.6cm

3-1/2"

8.9cm

2000 propane

2-1/2"

6.4cm

2-1/2"

6.4cm

2-1/2"

6.4cm

3"

7.6cm

2400 natural

2-1/2"

6.4cm

3"

7.6cm

3"

7.6cm

3-1/2"

8.9cm

2400 propane

2"

5.1cm

2-1/2"

6.4cm

2-1/2"

6.4cm

3"

7.6cm

Notes: 1. These figures are based on 1/2" 0.12kPa water column pressure drop.

2. Check supply pressure and local code requirements before proceeding with work.

3. Pipe fittings must be considered when determining gas pipe sizing.

Table 6. Gas Piping Sizes.

Image 13
Contents Βρυτε Μαγνυμ Βραδφορδ Ωηιτε Χορπ Maintenance Table of ContentsTroubleshooting Replacement PartsList of Figures List of TablesIntroduction General InformationModel Identification Model DesignationDimensions WarrantyLocating the Appliance Inches 91cm horizontally Combustion Air Venting and Combustion AIRCombustion Air From Room Intake Combustion AirLocating Vent & Combustion Air Terminals VentingHorizontal Vent Terminal Combustion Air and Vent Through Side Wall From Massachusetts Rules and Regulations 248 CMR Installation of Carbon Monoxide DetectorsSide Wall Combustion Air Terminal Common Vent Test BoilersVertical Vent Terminal Vertical Combustion Air TerminalDistance from Gas Meter or Last Stage Regulator GAS Supply and Piping4A.1 Heating System Piping Hot Supply Connections Boiler Water Connections Brute Magnum Boiler4A.2 Cold Water Make-Up Boiler 4A.3 Freeze Protection Boiler Water Connections Brute Magnum Water Heater4B.1 Water System Piping Water Heater 4B.2 Hot Water Supply Piping Water HeaterHydronic Piping Multiple Boilers 4B.3 Water Flow Requirements Water HeaterHydronic Piping Multiple Boilers Alternate 4B.4 Combined Water potable Heating and Space Heating Hydronic Piping One Boiler, Multi-Temperature System4B.5 Freeze Protection Water Heater Heater or in the pipes in the system. When waterWater Heater Piping One Heater, One Tank Water Heater Piping Multiple Heaters, One Tank Water Heater Piping One Heater, Multiple Tanks Water Heater Piping Multiple Heaters, Multiple Tanks Temperature Control Boiler Main PowerTemperature Control Water Heater Electrical ConnectionsInternal Water Heater Temperature Control Temperature Control FeaturesTemperature Setpoint Differential SettingThrottling Range OffsetIntegration Constant Minimum Output SettingControl Parameter Possible Interference Mixing System and ControlExternal Control Connections Wiring DiagramsWiring Diagram, Size 1200, Standard and Codes a and F Βρυτε Μαγνυμ Wiring Diagram, Size 1200, Code B Wiring Diagram, Sizes 1600, 2000 and 2400, Code B Wiring Schematic, Model 1200, Standard and Codes a and F Wiring Schematic, Model 1200, Code B Operating Instructions Operating the Burner and Set UpFilling the Boiler System Gas/Air Test Panel System Maintenance MaintenanceAppliance Maintenance Component Description Shutting Down the Brute MagnumGas Trains Filter BurnerModulating Gas Valve Manual Reset High Limit Control Safety Gas ValveAuto Reset Temperature Limit Mixing ControlFlow Switch Ignitor / Flame Sensor AssemblyMixing Actuator Ignition ControlMotorized Safety Valve TroubleshootingGas Pressure Switches Sequence of OperationResolving Lockouts Delayed Ignition Possible CausesShort Cycling Boiler Short Cycling Water Heater Replacement PartsHigh Gas Consumption Combustion Components See Figure Parts ListElectrical Components See Figure Jacket See Figure Combustion Components Gas Train/Combustion Air Components Gas Train Components Electrical Components Heat Exchanger / Water Path Components Heat Exchanger / Water Path Components Jacket Components Litho in U.S.A. Bradford White 1102 Document