Bradford-White Corp BRHHV, BRHHH warranty Venting and Combustion AIR, Combustion Air From Room

Page 8

Page 8

ΒΡΑΔΦΟΡΔ ΩΗΙΤΕ ΧΟΡΠ.

 

 

 

 

Section 2

VENTING AND COMBUSTION AIR

2.1Combustion Air

Brute Magnum boilers and water heaters must

have provisions for combustion and ventilation air in accordance with the applicable requirements for Combustion Air Supply and Ventilation in the National Fuel Gas Code, ANSI Z223 1; or in Canada, the Natural Gas and Propane Installation Code, CSA B149.1. All applicable provisions of local building codes must also be adhered to.

A Brute Magnum unit can take combustion air from the space in which it is installed, or the combustion air can be ducted directly to the unit. Ventilation air must be provided in either case.

2.1.1Combustion Air From Room

In the United States, the most common

requirements specify that the space shall communicate with the outdoors in accordance with method 1 or 2, which follow. Where ducts are used, they shall be of the same cross-sectional area as the free area of the openings to which they connect.

Method 1: Two permanent openings, one commencing within 12" (300mm) of the top and one commencing within 12" (300mm) of the bottom, of the enclosure shall be provided. The openings shall communicate directly, or by ducts, with the outdoors or spaces that freely communicate with the outdoors. When directly communicating with the outdoors, or when communicating to the outdoors through vertical ducts, each opening shall have a minimum free area of

1 square inch per 4000 Btu/hr (550 square mm/kW) of total input rating of all equipment in the enclosure. When communicating to the outdoors through horizontal ducts, each opening shall have a minimum free area of not less than 1square inch per 2000 Btu/hr (1100 square mm/kW) of total input rating of all equipment in the enclosure.

Method 2: One permanent opening, commencing within 12" (300mm) of the top of the enclosure, shall be permitted. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces that directly communicate with the outdoors and shall have a minimum free area of 1square inch per 3000 Btu/hr (734 square mm/kW) of the total input rating of all equipment located in the enclosure. This opening must not be less than the sum of the areas of all vent connectors in the confined space.

Other methods of introducing combustion and ventilation air are acceptable, providing they conform to the requirements in the applicable codes listed above.

In Canada, consult local building and safety codes or, in absence of such requirements, follow CAN/CGA B149.

2.1.2 Intake Combustion Air

The combustion air can be taken through the wall, or through the roof. When taken from the wall, it must be taken from out-of-doors by means of the horizontal wall terminal, shown in Table 3. See Table 2 to select the appropriate diameter air pipe. When taken from the roof, a field-supplied rain cap or an elbow arrangement must be used to prevent entry of rain water (see Figure 2).

Figure 2. Combustion Air and Vent Through Roof.

Use single-wall galvanized pipe for the combustion air intake (see Table 4), sized per Section

1.8.Route the intake to the heater as directly as possible. Seal all joints with tape. Provide adequate hangers. The unit must not support the weight of the combustion air intake pipe. Maximum linear pipe length allowed is 50 feet (15.2m). Up to five elbows can be used with the 50 feet of pipe. Subtract 10 allowable linear feet for every additional elbow used.

The connection for the intake air pipe is in the back of the unit. Take the plate off the back to reveal the collar on the filter box. Run a bead of silicone around the collar and slide the pipe over the collar. Secure with sheet metal screws.

Size

Horizontal Combustion

Horizontal Vent

Air Terminal

Terminal

 

1200

20260701

D2004500

1600

20260703

D2004500

2000

20260703

D2004600

2400

20260703

D2006200

Table 3. Horizontal Vent and Air Terminals

for Indoor Installations.

Image 8
Contents Βρυτε Μαγνυμ Βραδφορδ Ωηιτε Χορπ Table of Contents MaintenanceTroubleshooting Replacement PartsList of Tables List of FiguresGeneral Information IntroductionModel Identification Model DesignationLocating the Appliance WarrantyDimensions Inches 91cm horizontally Venting and Combustion AIR Combustion AirCombustion Air From Room Intake Combustion AirHorizontal Vent Terminal VentingLocating Vent & Combustion Air Terminals Combustion Air and Vent Through Side Wall Installation of Carbon Monoxide Detectors From Massachusetts Rules and Regulations 248 CMRCommon Vent Test Boilers Side Wall Combustion Air TerminalVertical Vent Terminal Vertical Combustion Air TerminalGAS Supply and Piping Distance from Gas Meter or Last Stage Regulator4A.2 Cold Water Make-Up Boiler Water Connections Brute Magnum Boiler4A.1 Heating System Piping Hot Supply Connections Boiler Water Connections Brute Magnum Water Heater 4A.3 Freeze Protection Boiler4B.1 Water System Piping Water Heater 4B.2 Hot Water Supply Piping Water Heater4B.3 Water Flow Requirements Water Heater Hydronic Piping Multiple BoilersHydronic Piping Multiple Boilers Alternate Hydronic Piping One Boiler, Multi-Temperature System 4B.4 Combined Water potable Heating and Space HeatingHeater or in the pipes in the system. When water 4B.5 Freeze Protection Water HeaterWater Heater Piping One Heater, One Tank Water Heater Piping Multiple Heaters, One Tank Water Heater Piping One Heater, Multiple Tanks Water Heater Piping Multiple Heaters, Multiple Tanks Main Power Temperature Control BoilerTemperature Control Water Heater Electrical ConnectionsTemperature Control Features Internal Water Heater Temperature ControlTemperature Setpoint Differential SettingOffset Throttling RangeMinimum Output Setting Integration ConstantMixing System and Control Control Parameter Possible InterferenceWiring Diagrams External Control ConnectionsWiring Diagram, Size 1200, Standard and Codes a and F Βρυτε Μαγνυμ Wiring Diagram, Size 1200, Code B Wiring Diagram, Sizes 1600, 2000 and 2400, Code B Wiring Schematic, Model 1200, Standard and Codes a and F Wiring Schematic, Model 1200, Code B Filling the Boiler System Operating the Burner and Set UpOperating Instructions Gas/Air Test Panel Maintenance System MaintenanceAppliance Maintenance Component Description Shutting Down the Brute MagnumGas Trains Modulating Gas Valve BurnerFilter Safety Gas Valve Manual Reset High Limit ControlAuto Reset Temperature Limit Mixing ControlIgnitor / Flame Sensor Assembly Flow SwitchMixing Actuator Ignition ControlTroubleshooting Motorized Safety ValveGas Pressure Switches Sequence of OperationShort Cycling Boiler Delayed Ignition Possible CausesResolving Lockouts High Gas Consumption Replacement PartsShort Cycling Water Heater Parts List Combustion Components See FigureElectrical Components See Figure Jacket See Figure Combustion Components Gas Train/Combustion Air Components Gas Train Components Electrical Components Heat Exchanger / Water Path Components Heat Exchanger / Water Path Components Jacket Components Litho in U.S.A. Bradford White 1102 Document