Βρυτε Μαγνυμ | Page 45 |
|
8.5Short Cycling — Water Heater
Short cycling will generally occur only in
combination space heating and water heating applications when the water heater is operating in the
If short cycling occurs in a water heater application, it is probably caused by undersized piping between the water heater and the storage tank or by some other factor that restricts proper water flow through the water heater. The cause should be determined and corrected.
8.6High Gas Consumption
Appliances operating with an improper air/
fuel ratio are very inefficient and consequently, have very high gas consumption. Because efficiency is high when the CO2 is high (or O2 is low), appliances operating with low CO2 or high O2 (especially LP appliances) consume more gas. Adjust the CO2 or O2 for optimum efficiency. If no combustion analyzing equipment (CO2 or O2) is available then a proper adjustment of the air/fuel ratio (CO2 or O2) can not be accomplished. However, by briefly sniffing the flue gases it is possible to determine if the CO2 or O2 is within the proper range. No significant flue gas odor should be detected when combustion is proper. A strong piercing smell indicates poor combustion and generally a lean mixture - low CO2 or high O2 . The CO2 should be 8 to 9% at all firing rates. Do not attempt to correct combustion. Contact factory if the CO2 is not within this range.
Section 9
REPLACEMENT PARTS
Only genuine Bradford White replacement parts should be used.
9.1General Information
To order or purchase parts for the Brute
Magnum, contact your nearest Bradford White dealer or distributor. If they cannot supply you with what you need, contact Customer Service (see back cover for information).