Page 24 | ΒΡΑΔΦΟΡΔ ΩΗΙΤΕ ΧΟΡΠ. |
Section 5 |
|
ELECTRICAL CONNECTIONS |
|
WARNING |
|
The appliance must be electrically grounded in |
|
accordance with the requirements of the authority |
|
having jurisdiction or, in the absence of such |
|
requirements, with the latest edition of the National |
|
Electrical Code, ANSI/NFPA 70, in the U.S. and |
|
with latest edition of CSA C22.1 Canadian Electrical |
|
Code, Part 1, in Canada. Do not rely on the gas |
|
or water piping to ground the metal parts of the |
|
boiler. Plastic pipe or dielectric unions may isolate |
|
the boiler electrically. Service and maintenance |
|
personnel, who work on or around the boiler, may |
|
be standing on wet floors and could be electrocuted |
|
by an ungrounded boiler. Electrocution can result in |
|
severe injury or death. |
|
Single pole switches, including those of safety controls and protective devices must not be wired in a grounded line.
All electrical connections are made in the field wiring box that is located inside the appliance.
NOTE: All internal electrical components have been prewired. No attempt should be made to connect electrical wires to any other location except the wiring box.
Wiring connections are shown in Figures 17 through24.
5.1Main Power
Connect a properly sized and fused,
supply to the main power switch (hot leg is connected directly to switch). Neutral leg is connected directly to the white wire. Ground wire can be connected to the grounding screw in the box or on the switch.
5.2Pump Connections
The pump time delay relay will call the pump
to be energized upon a call for heat, and will keep the pump energized for a delay period after the call for heat has ended. The delay period is adjustable from 0.1 to 10 minutes.
Brute Magnum units have pumps that are wired at the factory to the pump time delay system. It is necessary to wire the pump to a separate 115V or 230V single phase circuit, per the wiring diagrams in Figures 17 through 20.
5.3Temperature Control — Boiler
Connect boiler field interlock wires to isolated
contacts on zone valves, circulator relays, sequencing controls (multiple boiler applications) or other temperature controlling devices.
The Brute Magnum temperature control
Figure 12. Temperature Control.
measures temperature on the boiler inlet, sensing return water temperature. Set the temperature control for the desired return temperature. If the return water temperature is less than 140°F (60°C), internal mixing will keep the outlet temperature at
The manual reset high limit is on the outlet of the Brute Magnum. Set the manual reset high limit at about 20°F (11°C) higher than the highest expected outlet temperature, to avoid nuisance lockouts.
5.4Temperature Control – Water Heater
5.4.1 Remote Water Heater
Temperature Control
The Brute Magnum water heater can be used with a
Caution
If the tank temperature control is set too high, a potential for hot water scalding may exist.
After a setting has been chosen for the tank
temperature control, set the heater temperature control 10°F (6°C) higher. The Brute Magnum temperature control measures temperature on the heater inlet, sensing return water temperature. If the return water