tank is drawing down, the heater will react to sustain a minimum tank temperature. Boilers generally have higher differentials than water heaters, to minimize short cycling (see throttling range). The differential is set by removing the cover of the A350 control and adjusting the potentiometer marked “DIFF” (see Figure 13).

5.5.3Offset

The offset determines the temperature below the controller’s setpoint where the throttling range begins. It offsets the throttling range.

For instance, if the setpoint is 120°F (49°C) and the offset is 5°F (3°C), then the unit’s throttling range will begin at 115°F (46°C). Between 115°F (46°C) and 120°F (49°C), the Brute Magnum will be in low fire.

The offset can be adjusted between 0°F and 30°F (0°C and 17°C) by removing the cover of the S350P control and adjusting the Offset dial (see Figure 14).

5.5.4Throttling Range

The throttling range allows the Brute Magnum to match the BTU demands of varying systems, by allowing the user to choose the temperature range

through which the unit will modulate. This will tell the controller how fast to respond to a change in temperature. A small throttling range keeps the unit in high fire more, and quickens the response of the system. A larger throttling range allows the Brute Magnum to spread its modulating range over a larger temperature range.

Example, Imperial units: Using a temperature setpoint of 120°F, with a 20°F differential, a 5°F offset, and a throttling range of 10°F, the unit will come on at 100°F and shut off at 120°F. The offset will set the top of the throttling range 5°F under the setpoint, which is 115°F in this example. Therefore, the throttling range will cause the Brute Magnum to modulate between 25% and 100% of full fire between 115°F and 105°F. Between 115°F and 120°F, the unit will remain at low fire. Between 100°F and 105°F, the unit will be at full fire.

Example, Metric units: Using a temperature setpoint of 49°C, with a 11°C differential, a 3°C offset, and a throttling range of 5°C, the unit will come on at 38°C and shut off at 49°C. The offset will set the top of the throttling range 3°C under the setpoint, which is 46°C in this example. Therefore, the throttling range will cause the Brute Magnum to modulate between

Figure 14. Control Parameter Graph.

Image 26
Contents Βρυτε Μαγνυμ Βραδφορδ Ωηιτε Χορπ Troubleshooting Table of ContentsMaintenance Replacement PartsList of Tables List of FiguresModel Identification General InformationIntroduction Model DesignationLocating the Appliance WarrantyDimensions Inches 91cm horizontally Combustion Air From Room Venting and Combustion AIRCombustion Air Intake Combustion AirHorizontal Vent Terminal VentingLocating Vent & Combustion Air Terminals Combustion Air and Vent Through Side Wall Installation of Carbon Monoxide Detectors From Massachusetts Rules and Regulations 248 CMRVertical Vent Terminal Common Vent Test BoilersSide Wall Combustion Air Terminal Vertical Combustion Air TerminalGAS Supply and Piping Distance from Gas Meter or Last Stage Regulator4A.2 Cold Water Make-Up Boiler Water Connections Brute Magnum Boiler4A.1 Heating System Piping Hot Supply Connections Boiler 4B.1 Water System Piping Water Heater Water Connections Brute Magnum Water Heater4A.3 Freeze Protection Boiler 4B.2 Hot Water Supply Piping Water Heater4B.3 Water Flow Requirements Water Heater Hydronic Piping Multiple BoilersHydronic Piping Multiple Boilers Alternate Hydronic Piping One Boiler, Multi-Temperature System 4B.4 Combined Water potable Heating and Space HeatingHeater or in the pipes in the system. When water 4B.5 Freeze Protection Water HeaterWater Heater Piping One Heater, One Tank Water Heater Piping Multiple Heaters, One Tank Water Heater Piping One Heater, Multiple Tanks Water Heater Piping Multiple Heaters, Multiple Tanks Temperature Control Water Heater Main PowerTemperature Control Boiler Electrical ConnectionsTemperature Setpoint Temperature Control FeaturesInternal Water Heater Temperature Control Differential SettingOffset Throttling RangeMinimum Output Setting Integration ConstantMixing System and Control Control Parameter Possible InterferenceWiring Diagrams External Control ConnectionsWiring Diagram, Size 1200, Standard and Codes a and F Βρυτε Μαγνυμ Wiring Diagram, Size 1200, Code B Wiring Diagram, Sizes 1600, 2000 and 2400, Code B Wiring Schematic, Model 1200, Standard and Codes a and F Wiring Schematic, Model 1200, Code B Filling the Boiler System Operating the Burner and Set UpOperating Instructions Gas/Air Test Panel Appliance Maintenance Component Description MaintenanceSystem Maintenance Shutting Down the Brute MagnumGas Trains Modulating Gas Valve BurnerFilter Auto Reset Temperature Limit Safety Gas ValveManual Reset High Limit Control Mixing ControlMixing Actuator Ignitor / Flame Sensor AssemblyFlow Switch Ignition ControlGas Pressure Switches TroubleshootingMotorized Safety Valve Sequence of OperationShort Cycling Boiler Delayed Ignition Possible CausesResolving Lockouts High Gas Consumption Replacement PartsShort Cycling Water Heater Parts List Combustion Components See FigureElectrical Components See Figure Jacket See Figure Combustion Components Gas Train/Combustion Air Components Gas Train Components Electrical Components Heat Exchanger / Water Path Components Heat Exchanger / Water Path Components Jacket Components Litho in U.S.A. Bradford White 1102 Document