Burnham FM01FD00B Section I General Information, Table III Recommended Rear Service Clearance

Page 13

SECTION I - GENERAL INFORMATION (Continued)

A.INSPECT SHIPMENT carefully for any signs of damage.

1.ALL EQUIPMENT is carefully manufactured, inspected and packed. Our responsibility ceases upon delivery of crated Boiler to the carrier in good condition.

2.ANY CLAIMS for damage or shortage in shipment must be filed immediately against the carrier by the consignee. No claims for variances from,

or shortage in orders, will be allowed by the manufacturer unless presented within thirty (30) days after the receipt of goods.

B.LOCATE THE UNIT

NOTICE

Recommended clearance for service may be reduced to minimum clearance to combustible material. However, increased service and maintenance difficulty will result.

1.RECOMMENDED SERVICE CLEARANCE

-Locate the unit in the boiler room so as to provide ease of venting and adequate clearance for maintenance, serviceability, and installation of piping. Refer to Figure 1b and Table 1 for boiler dimensional data.

from Jacket Front Panel:

Provide 54” service clearance for removal, maintenance, and servicing of burner and controls.

Provide service clearance for removal of baffles to perform annual cleaning of flueways, refer to Table I, Dimension “C”.

From Jacket Rear Panel:

Provide a minimum service clearance from the boiler jacket for access to boiler supply and return piping, relief valve, drain valve, flue collector clean-out covers, vent piping and optional flue damper assembly. See

Table III.

Table III: Recommended Rear Service Clearance

Flue Outlet Size

Combustible or Non-Combustible

Surfaces

 

 

 

7” Dia.

36

8” Dia.

36

10” Dia.

36

12” Dia.

36

From Jacket Left Side Panel:

Provide clearance per Table I, Dimension ‘B’, for burner swing door (BSD), opened fully with burner mounted, otherwise 12” with burner removed.

18” access clearance to service rear of boiler if right side clearance is less than 12”.

12” minimum if right side clearance is 18” or larger to access and service rear of boiler.

From Jacket Right Side Panel:

See Table I, Dimension ‘B’ if BSD is hinged to swing to right side with burner mounted, otherwise 12” minimum if left side clearance is 18” or larger to access and service rear of boiler.

From Jacket Top Panel:

Provide a minimum clearance from the boiler jacket of 24”.

2.FOR MINIMUM CLEARANCES to combustible materials, See Table IV or Table V.

Table IV: Minimum Installation Clearances To

Combustible Materials (Inches) per

ANSI/NFPA 31 (Knockdown/Non-UL

Packaged Boiler)

 

 

 

C

 

 

 

A

B

Chimney

D

E

Boiler

Above

Front

Connector

Rear

Sides

 

 

 

 

 

 

MPC

6

24

18

6

6

Note: See Table III for recommended service clearance to access rear of boiler.

NOTE 1: Listed clearances comply with American National Standard ANSI/NFPA 31, Installation of Oil Burning Equipment.

NOTE 2: MPC Series boilers can be installed in rooms with clearances from combustible material as listed above. Listed clearances cannot be reduced for alcove or closet installations.

NOTE 3: For reduced clearances to combustible material, protection must be provided as described in the above ANSI/NFPA 31 Standard.

13

Image 13
Contents Ialcastiron.com 101786-01R5-11/10Price $5.00 Knockdown Boiler Equipment Check List Castings Shipped Loose Field AssemblyParts Cartons On Bar Number Carton Qty. Req’d. Per Boiler Size Important Information Page Page Table of Contents Section VII Burner Specifications Section VI Service InstructionsSection Viii Repair Parts Rear CoverDimensional Information Section I General Information Table I Dimensional InformationCombustion Table II Ratings/Data Model MPC BoilersSection I General Information Table III Recommended Rear Service ClearanceBoiler Foundation MPC with Rear Outlet Vent Faulty Boiler Burner Operation Section II Cast Iron Block Assembly Instructions Hydrostatic Test Manual or Hydraulic Draw-up Section Assembly Vertical Bracing of Rear Section Page MPC4 DRAW-UP Page Section III Boiler Assembly Instructions Knockdown Boiler Section III Boiler Assembly Instructions KD Boiler Page Table VII Modular Return Water Mixing Tube Rwmt RC Return Water Mixing Tube RC Assembly and Installation Hand Form Support Channel Bracket Table Viii Frame/Bracket Mounting Locations Secure Brackets to Horizontal ChannelRear Section Horizontal Channel Assembly w/Mounting Hardware Mount Rear Section Horizontal Channel to Block Assembly Attachment of Lower Rear Section Bracket to Casting Leg Page Lower Tie Bar Installation Heat Exchanger Insulation One Piece and Modular Wrappers Internal Wiring Harness Components Page Internal Wiring Harness Components Install Protective Edging ‘B’ ‘C’ ‘D’ Table IX Internal Wiring Harness AdjustmentPage Table X Jacket Top Corner / Intermediate Panel Arrangement StepInstall Top Corner / Intermediate Panels Jacket Split Rear Panel Detail Table XI Jacket Top Panel Arrangement Installing Jacket Top Panels Viewed From FrontInstall Jacket Top Panels Viewed From Rear Avoid Breathing Fiber Particulates and Dust Install 2nd Pass Flueway Baffles Secure Burner Swing Door for Tight Perimeter Seal Beckett ‘CF’ Series Burner Adapter Plate Power Flame ‘JR’ Series Burner Adapter PlateBeckett ‘CG’ Series Burner Adapter Plate Purpose of Tappings in Supply Manifold Install Standard Trim Operating Control Install Probe Low Water Cut Off Install Low Fire Hold Control MPC4 & MPC5 Install Jacket Panels for Optional Burner Swing Door Cover Packaged Boiler Shipping Information Section IV Installation InstructionsRecommended MPC Minimum Piping Single Boiler Application Recommended MPC Minimum Piping Multiple Boiler Application Alternate MPC Minimum Piping Single Boiler Application Alternate MPC Minimum Piping Multiple Boiler Application Parallel Piping Conversion Discharge Piping for Pressure Relief Valve Section V Operating Instructions Test Controls Frequent Water Addition Section VI Service Instructions Maintenance of LOW Water Cutoff Devices Operation Frequency Accomplished by Remarks Combustion Safety ControlsFuel Valves Table XII Recommended Periodic Testing Check List Table XIIIb Beckett Gas Burner Specifications Section VII Burner SpecificationsTable XIVb Power Flame Gas Burner Specifications Table XIVa Power Flame #2 Oil Burner Specifications500 C1-GO-10 16 / Closed Section Viii Repair Parts Repair Parts Cast Iron Section Assembly MPC Common Bare Boiler Components Repair Parts Common Bare Boiler Components MPC Common Bare Boiler Components Oil Burner Repair Parts Common Bare Boiler ComponentsGas Burner Oil, Gas, Gas/Oil Combo BurnerMPC Front & Center Section Frame Rail Assembly Repair Parts Front & Center Section Frame Rail Assembly MPC Rear Section Frame Rail Assembly Repair Parts Rear Section Frame Rail Assembly MPC Return Water Mixing Tube RC Assembly Required Repair Parts Return Water Mixing Tube RC AssemblyMPC Heat Exchanger Insulation Wrapper Repair Parts Heat Exchanger Insulation Wrapper MPC Internal Wiring Harness Components Repair Parts Internal Wiring Harness Components MPC Jacket Panel Assembly Repair Parts Jacket Panel Assembly MPC Jacket Panel Assembly Repair Parts Jacket Panel Assembly MPC 2nd and 3rd Pass Flueway Baffles Repair Parts MPC 2ND and 3RD Pass Flueway Baffles Page Description 100 Optional Working Pressure Trim 101102 Repair Parts Common Optional Controls Appendix a Figures Description 106 Appendix B Tables Limited Warranty

FM01FD00B specifications

The Burnham FM01FD00B is a remarkable heating solution that combines efficiency, reliability, and advanced technology to meet the demands of modern homes and commercial spaces. Standing out in the crowded market of heating systems, the FM01FD00B is designed for those who prioritize both performance and energy savings.

One of the most significant features of the Burnham FM01FD00B is its advanced combustion technology. The system utilizes a high-efficiency burner that maximizes fuel usage, resulting in lower operating costs and reduced environmental impact. The unit is engineered to provide consistent heat distribution, ensuring that every corner of a room reaches a comfortable temperature quickly and effectively.

In addition to its efficient burning capabilities, the FM01FD00B is compatible with multiple heating mediums, allowing it to adapt to various fuel types, including natural gas and propane. This versatility makes it an excellent choice for homeowners looking for flexible heating options that can cater to their specific needs.

The FM01FD00B also comes equipped with a state-of-the-art control system that offers precise temperature management. Users can easily program their desired heating schedule, ensuring optimal comfort at all times. The intuitive interface allows for easy adjustments, making it simple to maintain a cozy environment whether at home or away.

Another key characteristic is the unit's robust construction. Built with high-quality materials, the Burnham FM01FD00B is designed to withstand harsh conditions and provide lasting performance. The durable exterior is resistant to corrosion, further enhancing its longevity and reliability.

Moreover, the system features built-in safety mechanisms that protect against overheating and other potential hazards, ensuring peace of mind for users. This focus on safety extends to its low emissions, making it an eco-friendly choice for those looking to reduce their carbon footprint.

In conclusion, the Burnham FM01FD00B is a high-efficiency heating solution that excels in performance, adaptability, and safety. Its advanced technologies, robust construction, and user-friendly features make it an ideal choice for anyone seeking a dependable and efficient heating system for their home or business. Whether you prioritize energy savings, reliability, or comfort, the FM01FD00B stands out as a top contender in the heating market.