Burnham FM01FD00B manual

Page 27

f.Install observation port sight glass. Locate 2”

x2-1/2” lg. nipple, sight glass envelope and 2” conduit bushing. Thread 2” nipple into observation port tapping directly above burner adapter opening on front of BSD. Open sight glass envelope and in this order place gasket, sight glass and gasket into conduit cap. Thread cap unto 2” nipple, hand tighten only until cap and glass are snug. Do not over tighten.

g.Do not install BSD on hinges at this time. Door must be installed after jacket assembly.

7.Mount C. I. flue collector to rear section - see Figure 9.

a.Use a wire brush to clean the rope groove on back surface of rear section.

b.Using the multi-purpose spray adhesive provided, apply the adhesive to the perimeter rope groove. Follow the directions on the can for application and tack time.

c.Locate remaining 158” length of silicone coated fiberglass rope from common parts carton.

Starting at 3 o’clock position, push rope into groove and continue around perimeter until rope overlaps the starting point. Rope should be approximately 4” longer than required. Use

apermanent black marker to mark the rope approximately 1/8” beyond point of overlap. Cut off excess with scissors or utility knife and wooden cutting block.

d.Apply a generous bead of red sealant to both ends of cut rope, push ends together and smooth excess sealant over joint with your finger.

e.Locate six (6) 3/8” flat washers and six (6) 3/8

-16 x 1-1/4” lg. cap screws from hardware bag. Thread one (1) washer and cap screw in each of the bottom tappings approximately four (4) turns. Lift flue collector and engage bottom slots over cap screws to position unit on rear section. Install remaining hardware in four (4) upper slots and hand tighten hardware. Using a wrench, tighten hardware evenly, use an alternating pattern from top to bottom.

8.Do not install Flue Collector Clean-out Covers at this time. Covers must be installed after Jacket Rear Panels are in place.

9.Install 1/4” NPT brass plug into tapping located at

10 o’clock position on flue outlet collar. Wrench tighten plug, but do not over tighten. See Figure 9.

10.Apply thread sealant and install 3” NPT pipe plug in lower tapping on front section. Wrench tighten until water tight. See Figure 9.

11.Install Supply Manifold and 4” NPT nipple - See Figure 9.

a.Locate supply and return manifold carton marked ‘S/RM CI’ and remove contents.

b.Apply thread sealing compound to both ends of the 4” NPT nipple and install one end of the

4” NPT nipple into the non-flow arrowed end of the CI Supply Manifold and hand tighten the assembly.

c.Then - Install the threaded end of the 4” NPT nipple into 4” NPT tapping located on top of rear section.

d.Wrench - CI Supply Manifold Assembly until water tight and 1½” NPT tappings (relief valve) are aligned with front and rear axis as shown in Figure 12.

Figure 12: Orientation of Supply Manifold

NOTICE

Orientation of supply manifold is critical for proper alignment of controls and relief valve piping.

B.Assemble and Install Return Water Mixing Tube (RWMT RC) and Return Manifold into Block Assembly.

1.Locate return water mixing tube carton marked ‘RWMT RC’ and remove contents.

2.Modular return water mixing tubes start as a two

(2) tube assembly with end cap and increase with block size to become a seven (7) tube assembly with end cap. Assemble each RWMT RC in exact order shown in Table VII based on boiler size. Also refer to Figure 13.

3.Per Table VII, starting at the front, install RWMT End Cap on tube shown in next column to the right. Open ‘RH’ hardware bag and locate 3 oz. tube of sealant. Apply a continuous bead of silver silicone sealant to end of tube opposite the flared collar or ring. The end cap and each tube has a series of holes for alignment when secured together. Align the holes, push end cap over tube end with sealant and secure with four (4) #8 x 1/2 hex head screws.

27

Image 27
Contents 101786-01R5-11/10 Ialcastiron.comPrice $5.00 Castings Shipped Loose Field Assembly Knockdown Boiler Equipment Check ListParts Cartons On Bar Number Carton Qty. Req’d. Per Boiler Size Important Information Page Page Table of Contents Rear Cover Section VI Service InstructionsSection VII Burner Specifications Section Viii Repair PartsDimensional Information Section I General Information Table I Dimensional InformationCombustion Table II Ratings/Data Model MPC BoilersSection I General Information Table III Recommended Rear Service ClearanceBoiler Foundation MPC with Rear Outlet Vent Faulty Boiler Burner Operation Section II Cast Iron Block Assembly Instructions Hydrostatic Test Manual or Hydraulic Draw-up Section Assembly Vertical Bracing of Rear Section Page MPC4 DRAW-UP Page Section III Boiler Assembly Instructions Knockdown Boiler Section III Boiler Assembly Instructions KD Boiler Page Table VII Modular Return Water Mixing Tube Rwmt RC Return Water Mixing Tube RC Assembly and Installation Hand Form Support Channel Bracket Table Viii Frame/Bracket Mounting Locations Secure Brackets to Horizontal ChannelRear Section Horizontal Channel Assembly w/Mounting Hardware Mount Rear Section Horizontal Channel to Block Assembly Attachment of Lower Rear Section Bracket to Casting Leg Page Lower Tie Bar Installation Heat Exchanger Insulation One Piece and Modular Wrappers Internal Wiring Harness Components Page Internal Wiring Harness Components Install Protective Edging ‘B’ ‘C’ ‘D’ Table IX Internal Wiring Harness AdjustmentPage Table X Jacket Top Corner / Intermediate Panel Arrangement StepInstall Top Corner / Intermediate Panels Jacket Split Rear Panel Detail Table XI Jacket Top Panel Arrangement Installing Jacket Top Panels Viewed From FrontInstall Jacket Top Panels Viewed From Rear Avoid Breathing Fiber Particulates and Dust Install 2nd Pass Flueway Baffles Secure Burner Swing Door for Tight Perimeter Seal Power Flame ‘JR’ Series Burner Adapter Plate Beckett ‘CF’ Series Burner Adapter PlateBeckett ‘CG’ Series Burner Adapter Plate Purpose of Tappings in Supply Manifold Install Standard Trim Operating Control Install Probe Low Water Cut Off Install Low Fire Hold Control MPC4 & MPC5 Install Jacket Panels for Optional Burner Swing Door Cover Packaged Boiler Shipping Information Section IV Installation InstructionsRecommended MPC Minimum Piping Single Boiler Application Recommended MPC Minimum Piping Multiple Boiler Application Alternate MPC Minimum Piping Single Boiler Application Alternate MPC Minimum Piping Multiple Boiler Application Parallel Piping Conversion Discharge Piping for Pressure Relief Valve Section V Operating Instructions Test Controls Frequent Water Addition Section VI Service Instructions Maintenance of LOW Water Cutoff Devices Operation Combustion Safety Controls Frequency Accomplished by RemarksFuel Valves Table XII Recommended Periodic Testing Check List Table XIIIb Beckett Gas Burner Specifications Section VII Burner SpecificationsTable XIVb Power Flame Gas Burner Specifications Table XIVa Power Flame #2 Oil Burner Specifications500 C1-GO-10 16 / Closed Section Viii Repair Parts Repair Parts Cast Iron Section Assembly MPC Common Bare Boiler Components Repair Parts Common Bare Boiler Components MPC Common Bare Boiler Components Oil, Gas, Gas/Oil Combo Burner Repair Parts Common Bare Boiler ComponentsOil Burner Gas BurnerMPC Front & Center Section Frame Rail Assembly Repair Parts Front & Center Section Frame Rail Assembly MPC Rear Section Frame Rail Assembly Repair Parts Rear Section Frame Rail Assembly MPC Return Water Mixing Tube RC Assembly Required Repair Parts Return Water Mixing Tube RC AssemblyMPC Heat Exchanger Insulation Wrapper Repair Parts Heat Exchanger Insulation Wrapper MPC Internal Wiring Harness Components Repair Parts Internal Wiring Harness Components MPC Jacket Panel Assembly Repair Parts Jacket Panel Assembly MPC Jacket Panel Assembly Repair Parts Jacket Panel Assembly MPC 2nd and 3rd Pass Flueway Baffles Repair Parts MPC 2ND and 3RD Pass Flueway Baffles Page Description 100 Optional Working Pressure Trim 101102 Repair Parts Common Optional Controls Appendix a Figures Description 106 Appendix B Tables Limited Warranty

FM01FD00B specifications

The Burnham FM01FD00B is a remarkable heating solution that combines efficiency, reliability, and advanced technology to meet the demands of modern homes and commercial spaces. Standing out in the crowded market of heating systems, the FM01FD00B is designed for those who prioritize both performance and energy savings.

One of the most significant features of the Burnham FM01FD00B is its advanced combustion technology. The system utilizes a high-efficiency burner that maximizes fuel usage, resulting in lower operating costs and reduced environmental impact. The unit is engineered to provide consistent heat distribution, ensuring that every corner of a room reaches a comfortable temperature quickly and effectively.

In addition to its efficient burning capabilities, the FM01FD00B is compatible with multiple heating mediums, allowing it to adapt to various fuel types, including natural gas and propane. This versatility makes it an excellent choice for homeowners looking for flexible heating options that can cater to their specific needs.

The FM01FD00B also comes equipped with a state-of-the-art control system that offers precise temperature management. Users can easily program their desired heating schedule, ensuring optimal comfort at all times. The intuitive interface allows for easy adjustments, making it simple to maintain a cozy environment whether at home or away.

Another key characteristic is the unit's robust construction. Built with high-quality materials, the Burnham FM01FD00B is designed to withstand harsh conditions and provide lasting performance. The durable exterior is resistant to corrosion, further enhancing its longevity and reliability.

Moreover, the system features built-in safety mechanisms that protect against overheating and other potential hazards, ensuring peace of mind for users. This focus on safety extends to its low emissions, making it an eco-friendly choice for those looking to reduce their carbon footprint.

In conclusion, the Burnham FM01FD00B is a high-efficiency heating solution that excels in performance, adaptability, and safety. Its advanced technologies, robust construction, and user-friendly features make it an ideal choice for anyone seeking a dependable and efficient heating system for their home or business. Whether you prioritize energy savings, reliability, or comfort, the FM01FD00B stands out as a top contender in the heating market.