WARNING

Exercise caution when handling phosphoric acid and follow the instructions on container label. Always use protective clothing and equipment when working with/near chemicals.

i.Wire brushing of the probe is not recommended as the soft platinum guard ring sandwiched between the ceramic insulators may be damaged. Care must be taken not to damage this ring in any way or the useful life of the probe may be shortened.

j.Clean the pipe threads of the probe to remove old, hardened pipe dope and other foreign matter.

k.Apply a moderate amount of good quality pipe dope to the pipe threads on the probe, leaving the two end threads bare. Do not use PTFE (Teflon) tape.

l.Screw the probe into the boiler tapping.

m.Mount the low water cutoff control on the probe.

n.Reconnect the control to probe wiring.

o.Fill the boiler.

p.Add boiler water treatment compound as needed.

q.Restore electric service to the boiler.

r.Fire burner to bring the water in the boiler to a boil to drive off free oxygen.

s.BEFORE RETURNING BOILER TO SERVICE: Follow the low water cutoff check out procedure, see Section V, Paragraph E, Item 3.

2.FLOAT TYPE LOW WATER CUTOFF

During the heating season, if an external low water cutoff is on the boiler, the blow off valve should be opened once a month (use greater frequency where conditions warrant), to flush out the sediment chamber so the device will be free to function properly.

Low water cutoffs should be dismantled annually by qualified personnel, to the extent necessary to insure freedom from obstructions and proper functioning of the working parts. Inspect connecting lines to boiler for accumulation of mud, scale, etc., and clean as required. Examine all visible wiring for brittle or worn insulation and make sure electrical contacts are clean and that they function properly. Give special attention to solder joints on bellows and float when this type of control is used. Check float for evidence of collapse and check mercury bulb (where applicable) for mercury separation or discoloration.

DO NOT ATTEMPT TO REPAIR MECHANISMS IN THE FIELD.

Complete replacement mechanisms, including necessary gaskets and installation instructions, are available from the manufacturer.

D.Check burner and controls at least once a year. See Section V, Paragraph E under Operating Instructions for control checks. See Burner Manual and Table XII for recommended burner tests and adjustments.

E.LUBRICATE BOILER COMPONENTS according to manufacturer’s instructions. Generally, this involves the burner and circulator. This includes the type of lubricant to use, frequency of lubrication, and points to lubricate.

F.GENERAL MAINTENANCE CONSIDERATIONS

1.Keep radiators and convectors clean.

2.If a hot water radiator is hot at the bottom but not at the top, it indicates that air has accumulated inside and should be vented. To vent radiator, hold small cup under air vent (located near top of radiator), open vent until water escapes and then close.

3.If a large volume of water is added to the system, it is advisable to heat the system to a high temperature and vent again. This will make less venting necessary during the winter.

4.Where an expansion tank is used, make sure that neither the tank nor its drain pipe is exposed to freezing temperatures. Never place valves in piping leading to or from expansion tank.

5.Boiler and system cleaning will help assure trouble free operation. See Section V, Paragraph F, under Operating Instructions for procedure.

G.ATTENTION TO BOILER WHILE NOT IN

OPERATION

WARNING

If boiler is not used during winter time, it must be fully drained to prevent freeze damage.

1.Spray inside surfaces with light lubricating or crankcase oil using a gun with an extended stem so as to reach all corners.

2.Always keep the manual fuel supply valve shut off if the burner is shut down for an extended period of time.

3.To recondition the heating system in the fall season after a prolonged shut down, follow the instructions outlined in Section V - Operating Instructions.

70

Image 70
Contents Ialcastiron.com 101786-01R5-11/10Price $5.00 Knockdown Boiler Equipment Check List Castings Shipped Loose Field AssemblyParts Cartons On Bar Number Carton Qty. Req’d. Per Boiler Size Important Information Page Page Table of Contents Section Viii Repair Parts Section VI Service InstructionsSection VII Burner Specifications Rear CoverDimensional Information Table I Dimensional Information Section I General InformationTable II Ratings/Data Model MPC Boilers CombustionTable III Recommended Rear Service Clearance Section I General InformationBoiler Foundation MPC with Rear Outlet Vent Faulty Boiler Burner Operation Section II Cast Iron Block Assembly Instructions Hydrostatic Test Manual or Hydraulic Draw-up Section Assembly Vertical Bracing of Rear Section Page MPC4 DRAW-UP Page Section III Boiler Assembly Instructions Knockdown Boiler Section III Boiler Assembly Instructions KD Boiler Page Table VII Modular Return Water Mixing Tube Rwmt RC Return Water Mixing Tube RC Assembly and Installation Hand Form Support Channel Bracket Secure Brackets to Horizontal Channel Table Viii Frame/Bracket Mounting LocationsRear Section Horizontal Channel Assembly w/Mounting Hardware Mount Rear Section Horizontal Channel to Block Assembly Attachment of Lower Rear Section Bracket to Casting Leg Page Lower Tie Bar Installation Heat Exchanger Insulation One Piece and Modular Wrappers Internal Wiring Harness Components Page Internal Wiring Harness Components Install Protective Edging Table IX Internal Wiring Harness Adjustment ‘B’ ‘C’ ‘D’Page Step Table X Jacket Top Corner / Intermediate Panel ArrangementInstall Top Corner / Intermediate Panels Jacket Split Rear Panel Detail Installing Jacket Top Panels Viewed From Front Table XI Jacket Top Panel ArrangementInstall Jacket Top Panels Viewed From Rear Avoid Breathing Fiber Particulates and Dust Install 2nd Pass Flueway Baffles Secure Burner Swing Door for Tight Perimeter Seal Beckett ‘CF’ Series Burner Adapter Plate Power Flame ‘JR’ Series Burner Adapter PlateBeckett ‘CG’ Series Burner Adapter Plate Purpose of Tappings in Supply Manifold Install Standard Trim Operating Control Install Probe Low Water Cut Off Install Low Fire Hold Control MPC4 & MPC5 Install Jacket Panels for Optional Burner Swing Door Cover Section IV Installation Instructions Packaged Boiler Shipping InformationRecommended MPC Minimum Piping Single Boiler Application Recommended MPC Minimum Piping Multiple Boiler Application Alternate MPC Minimum Piping Single Boiler Application Alternate MPC Minimum Piping Multiple Boiler Application Parallel Piping Conversion Discharge Piping for Pressure Relief Valve Section V Operating Instructions Test Controls Frequent Water Addition Section VI Service Instructions Maintenance of LOW Water Cutoff Devices Operation Frequency Accomplished by Remarks Combustion Safety ControlsFuel Valves Table XII Recommended Periodic Testing Check List Section VII Burner Specifications Table XIIIb Beckett Gas Burner SpecificationsTable XIVa Power Flame #2 Oil Burner Specifications Table XIVb Power Flame Gas Burner Specifications500 C1-GO-10 16 / Closed Section Viii Repair Parts Repair Parts Cast Iron Section Assembly MPC Common Bare Boiler Components Repair Parts Common Bare Boiler Components MPC Common Bare Boiler Components Gas Burner Repair Parts Common Bare Boiler ComponentsOil Burner Oil, Gas, Gas/Oil Combo BurnerMPC Front & Center Section Frame Rail Assembly Repair Parts Front & Center Section Frame Rail Assembly MPC Rear Section Frame Rail Assembly Repair Parts Rear Section Frame Rail Assembly MPC Return Water Mixing Tube RC Assembly Repair Parts Return Water Mixing Tube RC Assembly RequiredMPC Heat Exchanger Insulation Wrapper Repair Parts Heat Exchanger Insulation Wrapper MPC Internal Wiring Harness Components Repair Parts Internal Wiring Harness Components MPC Jacket Panel Assembly Repair Parts Jacket Panel Assembly MPC Jacket Panel Assembly Repair Parts Jacket Panel Assembly MPC 2nd and 3rd Pass Flueway Baffles Repair Parts MPC 2ND and 3RD Pass Flueway Baffles Page Description 100 101 Optional Working Pressure Trim102 Repair Parts Common Optional Controls Appendix a Figures Description 106 Appendix B Tables Limited Warranty

FM01FD00B specifications

The Burnham FM01FD00B is a remarkable heating solution that combines efficiency, reliability, and advanced technology to meet the demands of modern homes and commercial spaces. Standing out in the crowded market of heating systems, the FM01FD00B is designed for those who prioritize both performance and energy savings.

One of the most significant features of the Burnham FM01FD00B is its advanced combustion technology. The system utilizes a high-efficiency burner that maximizes fuel usage, resulting in lower operating costs and reduced environmental impact. The unit is engineered to provide consistent heat distribution, ensuring that every corner of a room reaches a comfortable temperature quickly and effectively.

In addition to its efficient burning capabilities, the FM01FD00B is compatible with multiple heating mediums, allowing it to adapt to various fuel types, including natural gas and propane. This versatility makes it an excellent choice for homeowners looking for flexible heating options that can cater to their specific needs.

The FM01FD00B also comes equipped with a state-of-the-art control system that offers precise temperature management. Users can easily program their desired heating schedule, ensuring optimal comfort at all times. The intuitive interface allows for easy adjustments, making it simple to maintain a cozy environment whether at home or away.

Another key characteristic is the unit's robust construction. Built with high-quality materials, the Burnham FM01FD00B is designed to withstand harsh conditions and provide lasting performance. The durable exterior is resistant to corrosion, further enhancing its longevity and reliability.

Moreover, the system features built-in safety mechanisms that protect against overheating and other potential hazards, ensuring peace of mind for users. This focus on safety extends to its low emissions, making it an eco-friendly choice for those looking to reduce their carbon footprint.

In conclusion, the Burnham FM01FD00B is a high-efficiency heating solution that excels in performance, adaptability, and safety. Its advanced technologies, robust construction, and user-friendly features make it an ideal choice for anyone seeking a dependable and efficient heating system for their home or business. Whether you prioritize energy savings, reliability, or comfort, the FM01FD00B stands out as a top contender in the heating market.