1.4SERVICING AND REMOVAL OF THE GAS VALVE
1.4.1 Setting the gas pressures
1
B
A
VG003Aa
2
D
Setting the maximum power of the boiler
1. Check that the supply pressure to the gas valve is a minimum of 20 mbar | ||
for natural gas. Turn off the gas supply at the isolation point under the | ||
boiler |
|
|
2. To do this, slacken the screw “A”. |
| |
Fit the pipe of the pressure gauge to the inlet pressure test point of the gas | ||
valve “B”. |
|
|
Turn on the gas supply at the isolation point under the boiler and with | ||
the boiler running, read the inlet working pressure on the gauge. | ||
When you have completed this operation, turn off the gas supply at the | ||
isolation point under the boiler, remove the pressure gauge and tighten | ||
the screw “A” securely into its housing to seal off the gas. Turn on the gas | ||
supply at the isolation point under the boiler and test the screw for | ||
gas escaping with an approved soap and water solution. | ||
3. To check the pressure supplied by the gas valve to the burner, with the | ||
boiler turned off, slacken the screw “C”. Fit the pipe of the pressure gauge | ||
to the outlet pressure test point of the gas valve “D”. | ||
Disconnect the compensation pipe “E”either from the gas valve or from | ||
the sealed chamber. |
|
|
4. Push the On/Off button to “ON” positiongreen- | light- and push the Heating | |
button to “ON” positiongreen- | light- |
|
Turn on the boiler by setting the external controls. |
C
VG003Ab
3
E
Adjust the 10mm nut “F” to set the gas pressure Turn the nut clockwise to | |
increase and anti clockwise to decrease the pressure until the required | |
pressure is achieved (see TABLE A page 9) | |
5. When you have completed the above operations, turn off the external | |
controls, | |
and replace the cap on the screw of the modureg. | |
Setting pressure for soft ignition. | |
The soft light pressure is factory set. | |
If the ignition is not regular (e.g: not complete burner ignition or ignition | |
noise) check the soft light regulator position. | |
The soft light pressure will need adjusting as follows: | |
- | Turn off electrical supply; |
- | referring to picture 4, open the dust cap of the soft light regulator, by |
| unscrewing in clockwise direction the white screw; |
F
VG003Ac
- turn the adjustment screw one step in the direction max to increase or in |
the direction min to decrease the soft light pressure; |
- after each adjustment of the regulator, turn on the electrical supply and |
recheck burner ignition (wait 20 seconds between each cycle to allow |
the gas valves’ internal servo system to reset). When the required level |
is achieved, close the dust cap. |