Crown Boiler BSI345 XII Service and Maintenance, On a continuous basis, On an annual basis

Page 32

e)Turn off gas supply to boiler per the appropriate Lighting and Operating instructions on pages 25 - 28. Drain hot water from boiler through boiler drain valve to a location where hot water can be safely discharged. Refill the boiler to normal water line level. If water in the gauge glass does not look clear, repeat above boil-out procedure again until water is clears.

f)Reinstall safety valve and related piping.

g)Conduct pH and Alkalinity test of water in the system. The pH reading should be in 7 to 11 range.

NOTE

When substantial amount of make-up water is used due to lost condensate, or when make-up water is hard or corrosive, water treatment is required. Contact qualified water treatment company for recommended water treatment compounds and procedures.

XII Service and Maintenance

On a continuous basis:

1)Keep the area around the boiler free and clear from combustible materials, gasoline, and other flammable vapors and liquids.

2)Keep the area around the boiler and boiler room ventilation openings clear of objects which might obstruct the flow of combustion and ventilation air.

On at least a weekly basis:

For boilers equipped with a #67 low water cut-off, blow down the low water cut-off following the instructions on the yellow sticker adjacent to the low water cut-off. During this blow down, the low water cutoff should shut down the burners. If it does

not the low water cut-off should be replaced immediately.

On an annual basis:

1)Turn off electrical power and gas supply to the boiler

2)Inspect the flue passages for signs of blockage. If there is any carbon in the combustion chamber or the flue passages, clean the heat exchanger before proceeding further. See the cleaning procedure below.

3)Remove any debris found in the combustion chamber, being careful not to disturb combustion chamber insulation.

4)Remove all burners, noting the location of the pilot main burner. If burners show signs of deterioration, they should be replaced (some discoloration around the burner ports is normal). Clean the burners by first brushing the ports with a soft bristle brush and then vacuuming out any debris through the venturi opening.

5)Inspect the pilot assembly:

Standing Pilots - Check the thermocouple for deterioration (some discoloration of the thermocouple is normal). If any deterioration is present, replace the thermocouple. Inspect the pilot assembly for deposits and deterioration. Clean or replace the pilot assembly as necessary.

Intermittent Pilots - Clean any deposits found on the electrode and grounding strap. The ideal gap between the electrode and the ground strap is 1/8”. Inspect the porcelain for cracks or other deterioration. Replace pilot assembly if deterioration is found.

6)Inspect the combustion chamber insulation for deterioration.

7)(Intermittent Pilot Boilers) - Inspect the ignition cable insulation for cracks or other deterioration. If deterioration is found,

CAUTION

LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION. VERIFY PROPER OPERATION AFTER SERVICING

32

31

Image 32
Contents BSI Series Table of Contents Product DescriptionII Specifications BSI SpecificationsIII Before Installing IV Locating the BoilerAir for Combustion and Ventilation For Buildings of Other than Unusually Tight Construction ForBuildingsofUnusuallyTightConstructionBOILERINSTALLEDINCONFINEDSPACE, ALL AIR from Inside ALL AIR from OUTDOORS, Using Openings Into Boiler Room VI Venting Removing an Existing Boiler from a Common Chimney BSI Boilertypicalventsystem Installation and Components VII Gas Piping GasconnectiontoboilerViii System Piping General Piping NotesPipingInstallation Common NEAR-BOILER Piping Mistakes IX Indirect Water Heater Piping Indirectwater Heater BOILER-SIDE PipingWiring Indirect Water Heater Wiring Wiring Indirectwater Heater to Boiler BSI Control System Sequence of Operation Sequence of Operation, Standing PilotVent Damper Note Less Vent GAS Valve BSI379 Honeywell VR8204/VR8304 Series GAS Valves BSI069 Robertshaw XI Start-up and Checkout 2423Standing Pilot Burner Flame For Your Safety Read Before Operating For Your Safety Read Before Lighting For Your Safety Read Before Lighting Position Indicator High Altitude Burners GASVALVEDETAIL-HONEYWELLVR8200ORVR8300STANDINGPILOT XII Service and Maintenance On a continuous basisOn at least a weekly basis On an annual basisPage Heat Exchanger Cleaning Procedure Xiii Troubleshooting Start END Start END Standing Pilot Ignition System Troubleshooting Chart Intermittent Ignition System Troubleshooting Chart XIV Parts Page KEY # Page Boilers only Page Appendix a Knockdown Boiler Assembly Instructions Before InstallingFIGUREA1 BASE, Heat EXCHANGER, Flue Collector Assembly Gas Valve Installation Figure A2 Jacket Installation Electrical Wiring Connections Complete InstallationFigure A3 Tapping Locations see Text for Tapping Uses Crown

BSI069, BSI345, BSI207, BSI172, BSI241 specifications

Crown Boiler Company is renowned for its high-quality heating solutions, with a diverse range of models designed to meet various residential and commercial needs. Among their popular offerings are the BSI series, which includes the BSI379, BSI138, BSI310, BSI276, and BSI103 models. Each of these boilers comes with distinct features, technologies, and characteristics that cater to different applications and preferences.

The Crown Boiler BSI379 is a powerful and efficient boiler designed for residential use. It features a stainless steel heat exchanger that enhances durability and improves heat transfer efficiency. The BSI379 operates on natural gas, providing a high thermal efficiency rating which helps to reduce energy costs. With a compact design, it can fit conveniently in various installations, making it a versatile choice for homeowners.

The BSI138 model is another excellent option for smaller residential spaces. It is equipped with advanced technology that allows for quiet operation and minimal environmental impact. This boiler also offers a straightforward control interface, making it easy for homeowners to adjust settings according to their heating needs. The BSI138's lightweight construction and small footprint allow for flexible installation options.

Moving on to the BSI310, this model is designed for medium to larger-sized homes. It features an electronic ignition system that ensures reliable start-up while minimizing gas consumption. The BSI310 also incorporates multiple safety features, including pressure relief valves and limit controls, enhancing user safety during operation. Its robust design ensures efficient heating even in the coldest months.

The BSI276 model is characterized by its sealed combustion design, which improves indoor air quality by preventing drafts and ensuring that all combustion air is drawn from outside. This model is ideal for energy-conscious homeowners seeking environmentally friendly options. Its high-efficiency rating translates to significant energy savings over time, making it a financially wise investment.

Finally, the BSI103 is an entry-level model that retains the quality and reliability associated with Crown Boilers. It is particularly suited for smaller homes or apartments and offers ease of use and maintenance. The BSI103 combines affordability with efficiency, providing a cost-effective heating solution without compromising on performance.

In summary, the Crown Boiler BSI series, comprising the BSI379, BSI138, BSI310, BSI276, and BSI103, showcases a blend of innovative technologies and features. With options suitable for various household sizes and energy needs, Crown Boiler continues to deliver reliable heating solutions that cater to modern homeowners’ demands for efficiency, safety, and convenience. Each model's unique characteristics ensure that users can find the perfect boiler to meet their heating requirements.