Crown Boiler BSI103, BSI241, BSI276, BSI345, BSI379, BSI138, BSI172 Heat Exchanger Cleaning Procedure

Page 34

disturbed during the inspection process for leaks.

Heat Exchanger Cleaning Procedure

1)Turn off electrical power and gas supply to the boiler

2)Disconnect the damper and vent connector from the boiler.

3)Remove the upper front and top jacket panels. If possible, remove the rear and left side jacket panels

4)Remove the burners.

5)Remove the blocked vent (“spill”) switch

6)Remove the ¼-20 nuts and washers holding the flue collector onto the heat exchanger.

7)Carefully remove the flue collector gasket strips and set them aside.

8)Remove the flue collector from the heat exchanger.

9)Clean the flue passageways using a stiff bristle brush. Be certain that all foreign material is removed from the gaps between the pins

10)Clean the bottom surfaces of the heat exchanger

11)Put a light in the combustion chamber and look through the flue passages from the top to verify that they have been thoroughly cleaned.

12)Replace the flue collector gasket strips. If desired, RTV silicone sealant with a 500F intermittent duty temperature may be substituted for this rope gasket. The flue collector must be thoroughly sealed to the heat exchanger.

13)Replace the ¼-20 nuts and washers that hold down the flue collector

14)Reattach all the jacket components.

15)Reinstall burners, being careful to put the pilot main burner in its original location.

WARNING

SOOT DEPOSITS IN THE FLUE PASSAGES ARE A SIGN THAT THE BOILER MAY BE OPERATING AT HIGH CARBON MONOXIDE (CO) LEVELS. AFTER CLEANING THE BOILER OF SOOT DEPOSITS, CHECK THE CO LEVEL IN THE FLUE GAS TO INSURE THAT THE BOILER IS OPERATING PROPERLY.

If it is necessary to check CO, use a combustion analyzer, or other instrument which is designed to measure CO in flue gas. A CO “sniffer” designed for testing CO levels in ambient air cannot be used to check boiler combustion. Take a flue gas sample by inserting a sample probe through the draft diverter opening and into the flue collector so that the sample is taken in the area directly over the heat exchanger. Do not take a sample until the boiler has been firing for at least five minutes.

A normal CO reading for a BSI series boiler is less than 50ppm (0.005%). A reading of more than 100ppm (0.01%) is indica- tive of a combustion problem.

Some causes of excessive CO include:

Incorrectly sized main burner orifice for the altitude at which boiler is installed

Crooked or out-of-round orifice holes (never attempt to drill orifice for this boiler in the field)

Partially plugged flue passages

Improper manifold pressure

Foreign material in burner venturis or burner ports

Leak in seal between flue collector and heat exchanger

Inadequate supply of combustion air

16) Replace the blocked vent switch.

17) Reconnect the damper and vent system.

34

33

Image 34
Contents BSI Series Table of Contents Product DescriptionII Specifications BSI SpecificationsIII Before Installing IV Locating the BoilerAir for Combustion and Ventilation For Buildings of Other than Unusually Tight Construction ForBuildingsofUnusuallyTightConstructionBOILERINSTALLEDINCONFINEDSPACE, ALL AIR from Inside ALL AIR from OUTDOORS, Using Openings Into Boiler Room VI Venting Removing an Existing Boiler from a Common Chimney BSI Boilertypicalventsystem Installation and Components VII Gas Piping GasconnectiontoboilerViii System Piping General Piping NotesPipingInstallation Common NEAR-BOILER Piping Mistakes IX Indirect Water Heater Piping Indirectwater Heater BOILER-SIDE PipingWiring Indirect Water Heater Wiring Wiring Indirectwater Heater to Boiler BSI Control System Sequence of Operation Sequence of Operation, Standing PilotVent Damper Note Less Vent GAS Valve BSI379 Honeywell VR8204/VR8304 Series GAS Valves BSI069 Robertshaw XI Start-up and Checkout 2423Standing Pilot Burner Flame For Your Safety Read Before Operating For Your Safety Read Before Lighting For Your Safety Read Before Lighting Position Indicator High Altitude Burners GASVALVEDETAIL-HONEYWELLVR8200ORVR8300STANDINGPILOT On at least a weekly basis XII Service and MaintenanceOn a continuous basis On an annual basisPage Heat Exchanger Cleaning Procedure Xiii Troubleshooting Start END Start END Standing Pilot Ignition System Troubleshooting Chart Intermittent Ignition System Troubleshooting Chart XIV Parts Page KEY # Page Boilers only Page Appendix a Knockdown Boiler Assembly Instructions Before InstallingFIGUREA1 BASE, Heat EXCHANGER, Flue Collector Assembly Gas Valve Installation Figure A2 Jacket Installation Electrical Wiring Connections Complete InstallationFigure A3 Tapping Locations see Text for Tapping Uses Crown